W E L C O M E T O A L L W E T
(PORTIONS COPYRIGHT 1985 BY MICHAEL FUERST)
!!!!! SET YOUR KEYBOARD TO UPPER CASE MODE !!!!!
THIS VERSION OF ALLWET CAN HANDLE A MAXIMUM OF 400 NODES, 400 PIPES,
25 RESERVOIRS, 25 BOOSTER STATIONS AND 20 PRVS AND CHECK VALVES.
DO YOU WISH THIS JOB TO BE INTERACTIVE OR BATCH?
TYPE 'I' FOR INTERACTIVE OR 'B' FOR BATCH :
WHAT IS THE NAME OF YOUR SYSTEM DESCRIPTION FILE?
(INCLUDE DRIVE AND PATH NAMES IF NEEDED)
I>I
TITLE FOR THIS DATA SET IS
SAMPLE PROBLEM FOR ALLWET USER MANUAL
HAZEN-WILLIAMS FORMULA USED
LENGTH DIAMETER FLOW HEADLOSS ELEV PRESSURE VELOC
UNITS FEET INCHES US GPM FEET FEET PSI FT/SEC
READING OF INPUT DATA COMPLETE. THE SYSTEM CONTAINS
8 NODES, 10 PIPES, 1 PRESSURE REDUCING VALVE(S),
0 BOOSTER PUMP STATION(S), 0 CHECK VALVE(S).
OF THE NODES, 3 EITHER HAVE RESERVOIRS OR HAVE FIXED PRESSURES.
ENTER NEXT MAIN COMMAND.
I>LIST
ENTER IN, INPUT OR OUTPUT
I>INPUT
INDICATE TYPE OF ELEMENT TO BE LISTED-- NODE, PIPE, CHECK, RESE, PRV,
BOOS, OR ALL (TO GET ALL OF THE LAST THREE).
I>NODES
INDICATE WHICH NODES SHOULD BE LISTED.
TYPE HELP IF MORE INFORMATION NEEDED.
I>CC U
DEMAND A DEMAND B XCOOR
NODE CL ND DEMAND C DEMAND D YCOOR ELEV PRESS
CC 1 2 125.0000 .0000 2750.00 415.0 30.0
125.0000 .0000 1750.00
T-1 1 2 .0000 .0000 1000.00 400.0
.0000 .0000 3000.00
T-2 1 2 .0000 .0000 4000.00 375.0
.0000 .0000 500.00
ENTER NEXT MAIN COMMAND.
I>LIST
ENTER IN, INPUT OR OUTPUT
I>INPUT
INDICATE TYPE OF ELEMENT TO BE LISTED-- NODE, PIPE, CHECK, RESE, PRV,
BOOS, OR ALL (TO GET ALL OF THE LAST THREE).
I>PIPE
INDICATE WHICH PIPES SHOULD BE LISTED.
TYPE HELP IF MORE INFORMATION NEEDED.
I>TO NODE T-1
FROM TO ROUGHNESS
PIPE NODE NODE LENGTH DIAM COEFF
1 T-1 1 500.0 10.0 100.0000
2 T-1 AA 2500.0 10.0 100.0000
Figure 5a. Sample ALLWET Terminal SessionĂ¢
ENTER NEXT MAIN COMMAND.
I>NODE
EITHER
(1) INPUT A NODE NAME (UP TO 8 CHARACTERS IN LENGTH)
OR (2) CANCEL NODE INSTRUCTION
OR (3) INDICATE X (AND ALLWET WILL SELECT THE NODE NAME)
I>4
INDICATE HORIZONTAL AND VERTICAL COORDINATES OF NODE
I>4000 5000
INDICATE NODE CLASS, ELEVATION AND PRESSURE SETTING AT THIS NODE.
ENTER ZERO FOR PRESSURE SETTING IF THERE IS NONE.
I>2 475 0
ENTER FOUR DEMAND VALUES. FOUR VALUES MUST BE ENTERED,
EVEN IF SOME ARE ZERO.
I>0 0 0 60
THANK YOU.
ENTER NEXT MAIN COMMAND.
I>PIPE
ENTER NUMBER FOR NEW PIPE OR ENTER X TO ALLOW ALLWET TO
ASSIGN THE PIPE NUMBER.
I>X
ALLWET WILL ASSIGN NUMBER 11 TO PIPE BEING ENTERED.
ENTER THE FROM NODE FOR THE NEW PIPE.
I>2
ENTER THE TO NODE FOR THE NEW PIPE.
I>4
ENTER THE PIPE DIAMETER, C FACTOR AND LENGTH AS 3 CONSECUTIVE NUMBERS.
ALLWET CALCULATES LENGTH FROM NODE AND PSEUDONODE COORDINATES IF
THE NUMBER ZERO IS ENTERED FOR THE LENGTH.
I>6 100 500
ARE THERE ANY PSEUDONODES FOR THIS PIPE? (YES OR NO)
I>NO
ENTER NEXT MAIN COMMAND.
I>BOOSTER
IDENTIFY A PIPE. TYPE HELP IF MORE INSTRUCTIONS NEEDED.
I>11
INDICATE EITHER PP, CURVE, OR DONE.
I>CURVE
HOW MANY POINTS WILL BE ENTERED?
I>5
ENTER 5 VALUES OF H
I>60 55 45 30 10
ENTER 5 VALUES OF Q
I>0 40 80 120 160
INDICATE EITHER PP, CURVE, OR DONE.
I>DONE
ENTER NEXT MAIN COMMAND.
I>RUN
SAMPLE PROBLEM FOR ALLWET USER MANUAL
HAZEN-WILLIAMS FORMULA USED
LENGTH DIAMETER FLOW HEADLOSS ELEV PRESSURE VELOC
UNITS FEET INCHES US GPM FEET FEET PSI FT/SEC
THERE ARE 11 PIPES, 9 NODES, 1 BOOSTER PUMP(S),
1 PRESSURE REDUCING VALVE(S), AND 0 CHECK VALVES.
OF THE NODES, 3 EITHER HAVE RESERVOIRS, OR ARE PRESSURE NODES.
REFERENCE RESERVOIR IS CC
CONFIRM WITH YES OR CHOOSE ONE OF THE FOLLOWING:
CC T-1 T-2
TYPE HELP FOR MORE INFORMATION.
I>YES
Figure 5b. Sample ALLWET Terminal Session
EPSI= .100E-02 US GPM CONFIRM WITH YES; OR ENTER A NEW VALUE.
I>YES
PERC= 1.00 CONFIRM WITH YES; OR ENTER A NEW VALUE.
I>YES
MULTIPLICATIVE FACTORS FOR SYSTEM ARE
A B C D
1 1.00 1.00 1.00 1.00
2 1.00 1.00 1.00 1.00
3 1.00 1.00 1.00 1.00
IF THESE ARE SATISFACTORY, TYPE YES. OTHERWISE, REVISE.
TYPE HELP FOR MORE DETAILED INSTRUCTIONS.
I>2 1.3 .9 1. 1.
I>DONE
MULTIPLICATIVE FACTORS FOR SYSTEM ARE
A B C D
1 1.00 1.00 1.00 1.00
2 1.30 .90 1.00 1.00
3 1.00 1.00 1.00 1.00
IF THESE ARE SATISFACTORY, TYPE YES. OTHERWISE, REVISE.
TYPE HELP FOR MORE DETAILED INSTRUCTIONS.
I>YES
THE SUM OF DEMANDS FROM NODES WHICH ARE NOT PRESSURE NODES AND
WHICH DO NOT HAVE RESERVOIRS IS 730.00
OUTFLO-INFLO= .00000
FIND BASIC SET OF CIRCUITS
BANDWIDTH = 4
NUMBER OF LOOPS = 5
1ST ITERATION CONDITION OF RESERVOIRS, PRESSURE NODES AND BOOSTER PUMPS
NODE HGL FROM TOTAL HGL TOTAL FLOW
NAME PUMP ALONE AT NODE AT NODE
CC .00 484.30 .00
T-1 .00 485.00 -219.00
T-2 137.66 517.66 -511.00
PIPE HEAD GAIN THROUGH PUMP FLOW BM
11 50.625 60.000 -.25000
PRVS AND/OR CHECKVALVES BECOME TESTABLE AFTER 7 ITERATIONS
PRV IN PIPE 10 IS BEING TURNED ON AT ITER NO. 7
NUMBER OF ITERATIONS= 9
MAX UNBALANCED HEAD IN A PSEUDO-LOOP IS .0000
ASSOCIATED WITH RESERVOIR AT NODE T-2
MAXIMUM UNBALANCED HEAD IN ANY LOOP .0000 IN LOOP NO 2
FLOW ANALYSIS SUCCESSFUL. USE LIST OR BATCH COMMANDS TO INSPECT RESULTS.
ENTER NEXT MAIN COMMAND
I>LIST
ENTER IN, INPUT OR OUTPUT
I>OUTPUT
INDICATE TYPE OF ELEMENT TO BE LISTED-- NODE, PIPE, CHECK, RESE, PRV,
BOOS, OR ALL (TO GET ALL OF THE LAST THREE).
I>NODE
INDICATE WHICH NODES SHOULD BE LISTED.
TYPE HELP IF MORE INFORMATION NEEDED.
I>ALL
Figure 5c. Sample ALLWET Terminal Session
NODE ELEVATION FLOW HGL PRESSURE
1 385.0 100.0 485.21 43.38
2 450.0 115.0 488.33 16.59
3 350.0 130.0 419.30 30.00
4 475.0 60.0 538.63 27.54
AA 410.0 150.0 484.97 32.45
BB 410.0 175.0 485.36 32.62
CC 415.0 220.6 484.30 30.00
T-1 400.0 153.4 485.00 36.80
T-2 375.0 -1104.0 495.28 52.07
ENTER NEXT MAIN COMMAND.
I>LIST
ENTER IN, INPUT OR OUTPUT
I>OUTPUT
INDICATE TYPE OF ELEMENT TO BE LISTED-- NODE, PIPE, CHECK, RESE, PRV,
BOOS, OR ALL (TO GET ALL OF THE LAST THREE).
I>PIPE
INDICATE WHICH PIPES SHOULD BE LISTED.
TYPE HELP IF MORE INFORMATION NEEDED.
I>TO PIPE 8
HEAD HEAD/UNIT
PIPE FROM TO FLOW LOSS LENGTH VEL.
4 1 CC 106.0 .91 .468E-03 .7
5 1 BB -62.8 -.15 -.597E-04 -.3
7 T-2 BB 604.9 9.92 .397E-02 2.5
8 BB CC 114.6 1.06 .540E-03 .7
9 BB AA 252.6 .39 .787E-03 1.0
ENTER NEXT MAIN COMMAND.
I>BATCH
WHAT IS THE NAME OF YOUR BATCH OUTPUT DATA FILE
(BE SURE TO INCLUDE THE DRIVE NAME, FOLLOWED BY A COLON,
FOLLOWED BY THE FILE NAME):
I>SAMPLE.OUT
DONE.
ENTER NEXT MAIN COMMAND.
I>REVISE
INDICATE AN ELEMENT TYPE TO BE REVISED OR CANCEL REVISE COMMAND.
I>NODE
EITHER
(1) INPUT A NODE NAME (UP TO 8 CHARACTERS IN LENGTH)
OR (2) CANCEL REVI NODE INSTRUCTION
I>CC
ENTER NAME, COOR, CLASS, ELEVATION, DEMAND, PRESSURE, DONE OR CANCEL.
I>PRESS
ENTER THE NEW VALUE.
I>25
ENTER NAME, COOR, CLASS, ELEVATION, DEMAND, PRESSURE, DONE OR CANCEL.
I>DONE
ENTER NEXT MAIN COMMAND.
I>TITLE
INPUT THE NEW TITLE.
I>SAMPLE PROBLEM FOR ALLWET USERS' MANUAL (FIRE FLOW TEST)
NEW TITLE IS
SAMPLE PROBLEM FOR ALLWET USERS' MANUAL (FIRE FLOW TEST)
INDICATE YES TO CONFIRM, NO IF AN ERROR HAS BEEN MADE.
I>YES
Figure 5d. Sample ALLWET Terminal Session
ENTER NEXT MAIN COMMAND.
I>RUN
SAMPLE PROBLEM FOR ALLWET USER MANUAL (FIRE FLOW TEST)
HAZEN-WILLIAMS FORMULA USED
LENGTH DIAMETER FLOW HEADLOSS ELEV PRESSURE VELOC
UNITS FEET INCHES US GPM FEET FEET PSI FT/SEC
THERE ARE 11 PIPES, 9 NODES, 1 BOOSTER PUMP(S),
1 PRESSURE REDUCING VALVE(S), AND 0 CHECK VALVES.
OF THE NODES, 3 EITHER HAVE RESERVOIRS, OR ARE PRESSURE NODES.
REFERENCE RESERVOIR IS CC
CONFIRM WITH YES OR CHOOSE ONE OF THE FOLLOWING:
CC T-1 T-2
TYPE HELP FOR MORE INFORMATION.
I>YES
EPSI= .100E-02 US GPM CONFIRM WITH YES; OR ENTER A NEW VALUE.
I>YES
PERC= 1.00 CONFIRM WITH YES; OR ENTER A NEW VALUE.
I>YES
MULTIPLICATIVE FACTORS FOR SYSTEM ARE
A B C D
1 1.00 1.00 1.00 1.00
2 1.30 .90 1.00 1.00
3 1.00 1.00 1.00 1.00
IF THESE ARE SATISFACTORY, TYPE YES. OTHERWISE, REVISE.
TYPE HELP FOR MORE DETAILED INSTRUCTIONS.
I>YES
THE SUM OF DEMANDS FROM NODES WHICH ARE NOT PRESSURE NODES AND
WHICH DO NOT HAVE RESERVOIRS IS 730.00
OUTFLO-INFLO= .00000
FIND BASIC SET OF CIRCUITS
BANDWIDTH = 4
NUMBER OF LOOPS = 5
1ST ITERATION CONDITION OF RESERVOIRS, PRESSURE NODES AND BOOSTER PUMPS
NODE HGL FROM TOTAL HGL TOTAL FLOW
NAME PUMP ALONE AT NODE AT NODE
CC .00 472.75 .00
T-1 .00 485.00 -219.00
T-2 137.66 517.66 -511.00
PIPE HEAD GAIN THROUGH PUMP FLOW BM
11 50.625 60.000 -.25000
PRVS AND/OR CHECKVALVES BECOME TESTABLE AFTER 8 ITERATIONS
PRV IN PIPE 10 IS BEING TURNED ON AT ITER NO. 8
NUMBER OF ITERATIONS= 10
MAX UNBALANCED HEAD IN A PSEUDO-LOOP IS .0000
ASSOCIATED WITH RESERVOIR AT NODE T-1
MAXIMUM UNBALANCED HEAD IN ANY LOOP .0000 IN LOOP NO 1
FLOW ANALYSIS SUCCESSFUL. USE LIST OR BATCH COMMANDS TO INSPECT RESULTS.
Figure 5e. Sample ALLWET Terminal Session
ENTER NEXT MAIN COMMAND.
I>LIST
ENTER IN, INPUT OR OUTPUT
I>OUTPUT
INDICATE TYPE OF ELEMENT TO BE LISTED-- NODE, PIPE, CHECK, RESE, PRV,
BOOS, OR ALL (TO GET ALL OF THE LAST THREE).
I>NODES
INDICATE WHICH NODES SHOULD BE LISTED.
TYPE HELP IF MORE INFORMATION NEEDED.
I>ALL
NODE ELEVATION FLOW HGL PRESSURE
1 385.0 100.0 484.51 43.08
2 450.0 115.0 487.63 16.29
3 350.0 130.0 419.30 30.00
4 475.0 60.0 537.93 27.24
AA 410.0 150.0 484.13 32.09
BB 410.0 175.0 484.23 32.13
CC 415.0 836.2 472.75 25.00
T-1 400.0 -447.6 485.00 36.80
T-2 375.0 -1118.7 494.59 51.77
ENTER NEXT MAIN COMMAND.
I>STORE
INDICATE DISK AREA NAME ON WHICH TO STORE.
I>FIRETEST.DAT
UPDATED VERSION OF DATA TO BE WRITTEN ON FILE NAMED
FIRETEST.DAT
INDICATE YES TO CONFIRM, NO TO CANCEL STORE COMMAND.
I>YES
ENTER NEXT MAIN COMMAND.
I>HALT
HALT HAS BEEN INDICATED. TYPE YES TO CONFIRM, NO TO CANCEL.
I>YES
Stop - Program terminated.
Figure 5f. Sample ALLWET Terminal Session