home *** CD-ROM | disk | FTP | other *** search
/ Explore the World of Soft…e: Engineering & Science / Explore_the_World_of_Software_Engineering_and_Science_HRS_Software_1998.iso / programs / pwrplant / quest150.exe / GALTIN34.QUE < prev    next >
Text File  |  1988-03-21  |  2KB  |  97 lines

  1. TVA's Gallatin Units 3-4 (300 MW nominal)
  2. * this is a QUEST configuration file
  3. 5 one HP, one IP, and one LP turbine, with reheat
  4. * Tb    Pb      Fb     Tr    BP
  5. 1050. 2015.  1954500. 1050. 2.00
  6. *HP turbine stages
  7.  2
  8. *HP turbine type
  9.  3
  10. *HP turbine generator connection
  11.  1
  12. *HP turbine flow factor(s)
  13.  431.2
  14.  264.6
  15. *HPT throttle leak to reheater exit/IPT inlet
  16.       0.
  17. *HPT throttle leak to SSR
  18.    1600.
  19. *HPT HP seal leak to SSR
  20.     700.
  21. *HPT HP seal leak to open feedwater heater
  22.       0.
  23. *HPT HP seal leak to HPT exit/reheater inlet
  24.  -19500.
  25. *HPT LP seal leak to open feedwater heater
  26.       0.
  27. *HPT LP seal leak to SSR
  28.     500.
  29. *IP turbine stages
  30.  3
  31. *IP turbine type
  32.  4
  33. *IP turbine generator connection
  34.  1
  35. *IP turbine flow factor(s)
  36.  116.8
  37.   76.77
  38.   44.60
  39. *IPT LP seal leak to open feedwater heater
  40.       0.
  41. *IPT LP seal leak to SSR
  42.     700.
  43. *cross-over pressure drop factor
  44.    2.00
  45. *LP turbine stages
  46.  4
  47. *LP turbine type
  48.  5
  49. *LP turbine generator connection
  50.  1
  51. *LP turbine flow factor(s)
  52.   26.40
  53.   11.03
  54.    6.634
  55. *LPT LP seal leak to SSR
  56.       0.
  57. *last stage annulus area in square feet (single flow)
  58.   41.1
  59. *number of annuli
  60.  3
  61. *FP turbine stages
  62.  0
  63. *generator 1 type
  64. 3 3600-rpm conductor-cooled
  65. *generator 1 rated KVA
  66.   275000.
  67. *makeup flow
  68.  -39100.
  69. *makeup injection
  70. D=deaerator
  71. *boiler pressure drop and efficiency
  72. 15.0  90.2
  73. *reheater pressure drop and efficiency
  74. 10.0  90.2
  75. *heat exchanger type, TTD, DCA, shell pressure drop
  76. * type 1: no drain inlet, type 2: drain inlet, type 3: open
  77. *type  TTD  DCA   DP
  78.    1    .0 10.0  5.0
  79.    2   5.0 10.0  5.0
  80.    2   5.0 10.0  5.0
  81.    3    .0   .0  5.0
  82.    1   5.0 10.0  7.0
  83.    2   5.0   .0  5.0
  84.    1   5.0   .0  5.0
  85.    2   5.0   .0  5.0
  86. NO, last heat exchanger before GSC does not drain to condenser
  87. *boiler feedpump efficiency
  88.  85.0
  89. *SSR flow to GSC
  90.    2000.
  91. *SSR flow to condenser
  92.       0.
  93. *SSR flow to LP turbine seals
  94.       0.
  95. *service load (+KW or -%)
  96.     -5.00
  97.