home
***
CD-ROM
|
disk
|
FTP
|
other
***
search
/
Internet Standards
/
CD2.mdf
/
ccitt
/
1992
/
k
/
k17a.asc
< prev
next >
Wrap
Text File
|
1993-06-28
|
4KB
|
247 lines
Recommendation K.17
1. Amend Figure 1:
2. Point 2.1, after the description of Test 3, insert the following:
"- Test 1a between input terminals of the repeater and conductive housing normally connected to earth
in the case of symmetric pair repeaters;
- Test 2a between output terminals of the repeater and conductive housing normally connected to
earth in the case of symmetric pair repeaters.
Equipments protected with arresters and installed on symmetrical pair cables, which are induced by a.c.
power or traction lines, can be tested with an alternating current, applied for 0.5 second. Current intensity
and frequency are comparable to the alternating currents that are likely to be met with in practice, but
should not exceed 10 A r.m.s."
3. Amend Figure 3 and Table 1:
4. Add new point 3.3:
"3.3 Test conditions for regenerators and power feeding sources used on optical fibre transmission systems
The following tests are applicable for all types of regenerators:
In principle two types of regenerators exist:
Regenerators with housings on floating potential and regenerators with housings connected to local
earth. The regenerators may also be power-fed via separate d.c.-converters. Both alone standing units may
be also considered as one "regenerator" with respect to this Recommendation."
3.3.1 Prototype tests
3.3.1.1 Impulse tests
These tests will be carried out under conditions listed in column 1 of Table 2/K.17.
Tests should be applied to equipment as indicated in Figure 5/K.17.
- Test 1 - Between terminals a and b of the power feeding path.
- Test 2 - Between terminal a of power feeding path and reference earth.
- Test 3 - Between terminal b of power feeding path and reference earth.
- Test 4 - Between both terminals a and b of power feeding path and reference earth.
Earth connections of housings with reference earth should be the same as used in practice.
3.3.1.2 A.C. Tests
3.3.1.2.1 Short-term a.c. induction
These tests are carried out under conditions listed in Table 3/K.17.
Tests 1, 2, 3 and 4 should be applied to equipment as indicated in Figure5/K.17 and explained in _
3.3.1.1.
3.3.1.2.2 Steady state a.c. induction
These tests should be carried out in accordance with _ 2.3 b and equipment should operate during tests
without significant increase of bit error rate.
3.3.1.3 Immunity test against fast transients induced in the power feeding path
These tests may be carried out to ensure that the regenerator is sufficiently protected against transients
occurring in the power feeding path.
These tests should be applied to equipment as indicated in Figure6/K.17.
For testing a generator, according to IEC, Publication 801-4 should be used. At test voltages up to 1 kV
the simulated signal transmission should not be disturbed severely. It is recommended to carry out this test,
if the power feeding path is not sufficiently shielded and interferences due to switching in electric power
systems may be expected.
3.3.2 Acceptance tests
Only impulse tests will be carried out under conditions listed in column 2 of Table 2/K.17.
Tests 1 and 4 have to be performed taking into account the remarks given in _ 1.4.