home *** CD-ROM | disk | FTP | other *** search
/ Internet Standards / CD2.mdf / ccitt / 1992 / k / k17a.asc < prev    next >
Text File  |  1993-06-28  |  4KB  |  247 lines

  1. Recommendation K.17
  2.  
  3.  
  4.  
  5. 1.    Amend Figure 1:
  6.  
  7.  
  8.  
  9.  
  10.  
  11.  
  12.  
  13.  
  14.  
  15.  
  16.  
  17.  
  18.  
  19.  
  20.  
  21.  
  22.  
  23.  
  24.  
  25.  
  26.  
  27.  
  28.  
  29.  
  30.  
  31.  
  32.  
  33. 2.    Point 2.1, after the description of Test 3, insert the following:
  34.  
  35.  
  36.  
  37.         "-     Test 1a between input terminals of the repeater and conductive housing normally connected to earth 
  38. in the case of symmetric pair repeaters;
  39.  
  40.  
  41.  
  42.     -    Test 2a between output terminals of the repeater and conductive housing normally connected to 
  43. earth in the case of symmetric pair repeaters.
  44.  
  45.     Equipments protected with arresters and installed on symmetrical pair cables, which are induced by a.c. 
  46. power or traction lines, can be tested with an alternating current, applied for 0.5 second. Current intensity 
  47. and frequency are comparable to the alternating currents that are likely to be met with in practice, but 
  48. should not exceed 10 A r.m.s."
  49.  
  50.  
  51.  
  52. 3.    Amend Figure 3 and Table 1:  
  53.  
  54.  
  55.  
  56.  
  57.  
  58.  
  59.  
  60.  
  61.  
  62.  
  63.  
  64.  
  65.  
  66.  
  67.  
  68.  
  69.  
  70.  
  71.  
  72.  
  73.  
  74.  
  75.  
  76.  
  77.  
  78.  
  79.  
  80.  
  81.  
  82.  
  83.  
  84.  
  85.  
  86.  
  87.  
  88.  
  89.  
  90.  
  91.  
  92. 4.    Add new point 3.3:
  93.  
  94.  
  95.  
  96. "3.3    Test conditions for regenerators and power feeding sources used on optical fibre transmission systems 
  97.  
  98.     The following tests are applicable for all types of regenerators:
  99.  
  100.  
  101.  
  102.     In principle two types of regenerators exist:
  103.  
  104.  
  105.  
  106.     Regenerators with housings on floating potential and regenerators with housings connected to local 
  107. earth. The regenerators may also be power-fed via separate d.c.-converters. Both alone standing units may 
  108. be also considered as one "regenerator" with respect to this Recommendation." 
  109.  
  110.  
  111.  
  112. 3.3.1    Prototype tests
  113.  
  114.  
  115.  
  116. 3.3.1.1    Impulse tests
  117.  
  118.  
  119.  
  120.     These tests will be carried out under conditions listed in column 1 of Table 2/K.17.
  121.  
  122.  
  123.  
  124.     Tests should be applied to equipment as indicated in Figure 5/K.17.
  125.  
  126.  
  127.  
  128.     -    Test 1 - Between terminals a and b of the power feeding                                 path.
  129.  
  130.  
  131.  
  132.     -    Test 2 - Between terminal a of power feeding path and reference         earth.  
  133.  
  134.  
  135.  
  136.  
  137.  
  138.  
  139.  
  140.  
  141.  
  142.  
  143.  
  144.     -    Test 3 - Between terminal b of power feeding path and reference                        earth.
  145.  
  146.                  
  147.  
  148.     -    Test 4 - Between both terminals a and b of power feeding path and                        reference earth.  
  149.  
  150.  
  151.  
  152.     Earth connections of housings with reference earth should be the same as used in practice.
  153.  
  154.  
  155.  
  156. 3.3.1.2    A.C. Tests
  157.  
  158.  
  159.  
  160. 3.3.1.2.1  Short-term a.c. induction 
  161.  
  162.  
  163.  
  164.     These tests are carried out under conditions listed in Table 3/K.17.
  165.  
  166.  
  167.  
  168.     Tests 1, 2, 3 and 4 should be applied to equipment as indicated in Figure5/K.17 and explained in _ 
  169. 3.3.1.1.
  170.  
  171.  
  172.  
  173. 3.3.1.2.2  Steady state a.c. induction
  174.  
  175.  
  176.  
  177.     These tests should be carried out in accordance with _ 2.3 b and equipment should operate during tests 
  178. without significant increase of bit error rate.
  179.  
  180.  
  181.  
  182. 3.3.1.3    Immunity test against fast transients induced in the power feeding path
  183.  
  184.  
  185.  
  186.     These tests may be carried out to ensure that the regenerator is sufficiently protected against transients 
  187. occurring in the power feeding path.
  188.  
  189.  
  190.  
  191.     These tests should be applied to equipment as indicated in            Figure6/K.17.
  192.  
  193.  
  194.  
  195.     For testing a generator, according to IEC, Publication 801-4 should be used.  At test voltages up to 1 kV 
  196. the simulated signal transmission should not be disturbed severely. It is recommended to carry out this test, 
  197. if the power feeding path is not sufficiently shielded and interferences due to switching in electric power 
  198. systems may be expected.
  199.  
  200.  
  201.  
  202. 3.3.2    Acceptance tests
  203.  
  204.  
  205.  
  206.     Only impulse tests will be carried out under conditions listed in column 2 of Table 2/K.17.
  207.  
  208.  
  209.  
  210.     Tests 1 and 4 have to be performed taking into account the remarks given in _ 1.4.
  211.  
  212.  
  213.  
  214.  
  215.  
  216.  
  217.  
  218.  
  219.  
  220.  
  221.  
  222.  
  223.  
  224.  
  225.  
  226.  
  227.  
  228.  
  229.  
  230.  
  231.  
  232.  
  233.  
  234.  
  235.  
  236.  
  237.  
  238.  
  239.  
  240.  
  241.  
  242.  
  243.  
  244.  
  245.  
  246.  
  247.