home *** CD-ROM | disk | FTP | other *** search
Text File | 2003-06-11 | 59.9 KB | 1,360 lines |
-
- * 2.3 : CLAUSES FOR TRANSMISSION LINE SIGNALLING EQUIPMENT
- ____________________
- Recommendation Q.414
- »»»»»»»»»»»»»»»»»»»»
- 2.3.1 SIGNAL SENDER
- ~~~~~
- 2.3.1.1 Signalling frequency
-
- The nominal value of the signalling frequency is 3825 Hz. Measured at
- the sending point, the frequency variation from thef nominal value must
- not exceed _ | Hz.
-
-
- 2.3.1.2 Send level
-
- The send level of the signalling frequency, measured at the group
- distribution frame or an equivalent point, must be -20 _ dBm0.
-
-
- 2.3.1.3 Leaks
-
- The level of the signal frequency which may be transmitted to line as a
- leak current (e.g. when static modulators are used), must be at least
- 25 dB below the level of the signalling tone.
-
-
- 2.3.1.4 Phase distribution of the signalling frequencies
-
- As the signalling frequency is sent on any circuit in idle state, the
- addition of these tones in moments of low traffic may give rise to the
- following phenomena on certain transmission systems:
-
- o high peak voltage on the line caused by the signalling tones and
- involving the possibility of overloading the system;
-
- o intelligible crosstalk due to third-order intermodulation;
-
- o unwanted tones coming from second-order intermodulation products and
- occurring within sound-programme circuits.
-
- o The following special measures must be taken to avoid these effects:
-
- One method recommended is to inject the signalling frequencies with
- random 0 and ~~ radian phases in the channels. An equivalent method
- is to use carrier frequencies of which the phases are ran- domly
- distributed 0 and ~~ radians. With these methods the probability of
- occurrence of 0 and ~~ radian phases should be 0.5
-
- Other methods may be used provided they give comparable results.
-
-
- 2.3.1.5 Protection of the signalling channel at the sending end
-
- This signalling channel must be protected at the sending end against
- disturbance from the associated and the adjacent speech channel.
-
- When a sinewave at 0 dBm0 level is applied to the audio-frequency input
- of the associated channel, the level measured at the group distribution
- frame or at an equivalent point must not exceed the levels shown in
- Figure 6/Q.414.
-
- When a sinewave of frequency f is applied to the audio-frequency input
- of the adjacent channel it produces two signals that appear on the
- frequency scale of Figure 6/Q.414 as having the frequencies
-
- (4000 + f ) and (4000 - f ). The level of the (4000 + f ) signal,
- measured at the group distribution frame or at an equivalent point,
- shall not be higher than -33 dBm0 when the sinewave with frequency f is
- applied to the audio-frequency input of the adjacent channel at a level
- shown in Figure 6/Q.414 for the frequency of (4000 + f ). The level of
- the (4000 - f ) signal, measured at the group distribution frame or at
- an equivalent point,
-
- [ For further details on the method of random distribution
- [ of the phases of frequency 3825 Hz, see: Ekholm, O. and
- [ Johannesson, N.O.: "Loading Effects with Continuous Tone
- [ Signalling", English edition of TELE , No. 2, 1969. For
- [ further details on a systematic method of phase
- [ distribution, see: Rasch, J. and Kagelmann, H.: "On
- [ Measures for Reducing Voltage Peaks and Distortion Noise
- [ on Carrier Transmission Paths with Single Channel
- [ Supervision", Nachrichtentechnische Zeitschrift (NTZ) , 22
- [ (1969), No. 1, pp. 24-31.
-
- shall not be higher than -33 dBm0 when the sinewave with frequency f is
- applied to the audio-frequency input of the adjacent channel at any
- level below the value shown in Figure 6/Q.414 for the frequency (4000 -
- f).
-
- FIGURE 6/Q.414, p.
-
- When the Go path is looped to the Return path at the group distribution
- frame or an equivalent point, the signal receiver must not change
- condition when:
-
- o the click generator shown in Figure 7/Q.414 is connected to the
- associated speech channel or to the adjacent speech channel at the
- very point where this channel is connected to the switching equipment;
-
- o to take the most difficult circumstances possible, the channel level
- adjusting devices are set to such values encountered in practice which
- give rise to the worst disturbance;
-
- o gain is introduced in the loop at the group distribution frame or at
- the equivalent point, so that the receive level at the point in
- question is +3 dBm0.
-
- FIGURE 7/Q.414, p.
-
- 2.3.1.6 Response time
-
- The response time of the signal sender is defined as the interval
- between the instant when the change signalling condition command is
- applied to the sender and the instant at which the envelope of the
- signalling frequency, measured at the group distribution frame or at an
- equivalent point, reaches half of its value in the steady state. For
- each of the two possible changes of signalling condition the response
- time must be less than 7 ms.
-
-
- ____________________
- Recommendation Q.415
- »»»»»»»»»»»»»»»»»»»»
- 2.3.2 SIGNAL RECEIVER
- ~~~~~
- 2.3.2.1 Recognition of the tone-on condition
-
- The receiver must have assumed or assume the tone-on condition when at
- the group distribution frame or at an equivalent point:
-
- o the level of the received frequency has risen to -27 dBm0 or more;
-
- o its frequency lies between 3825 _ 6 Hz.
-
- The level of -27 dBm0 specified above does not preclude the use of
- individual adjustments in the channel translating equipment to
- compensate for constant level deviations.
-
-
- 2.3.2.2 Recognition of the tone-off condition
-
- The receiver must have assumed or assume the tone-off condition when the
- level of the test frequency, at the group distribution frame or at an
- equivalent point, has dropped to the values shown in Figure 8/Q.415.
-
- FIGURE 8/Q.415, p.
-
- 2.3.2.3 Protection against near-end disturbances
-
- The signal receiver must not change state when any one of the following
- disturbing signals is applied at the 4-wire output of the associated
- speech channel looped at the group distribution frame or at an
- equivalent point:
-
- o A sinusoidal signal whose level as a function of the frequency is
- shown in Figure 9/Q.415,
-
- o A transient signal produced by the click generator (described in S
- 2.3.1.5 above) applied at the point where the channel is connected to
- the switching equipment, all level adjusting devices being set to such
- values encountered in practice which give rise to the worst
- disturbance.
- FIGURE 9/Q.415, p.
-
-
- 2.3.2.4 Overall response time of signal sender and receiver
-
- When the modulation equipment is looped at the group distribution frame
- or at an equivalent point, the overall response time is defined as the
- interval between the instant when a change signalling condition command
- is applied to the sender and the moment when the changed signalling
- condition appears at the receiver output. For each of the two possible
- changes of signalling condition, the overall response time must be less
- than 30 ms.
-
-
- 2.3.2.5 Interference by carrier leaks
-
- The requirements stated in SS 2.3.2.1, 2.3.2.3 and 2.3.2.4 above must be
- fulfilled in the presence of carrier leaks.
-
- It is assumed that:
-
- o when the receive level of the signalling tone is at its nominal value
- at the group distribution frame or an equivalent point, each carrier
- leak is present at a level of - 26 dBm0;
-
- o the level of the carrier leak varies proportionally with any
- variations in the level of the signalling tone.
-
-
- 2.3.2.6 Interference by pilots
-
- The specified signalling system is not intended to work in the presence
- of those pilots specified by CCITT having a frequency differing by 140
- Hz from the nearest multiple of 4 kHz (see Recommendation M.460).
-
- On the other hand, the requirements stated in SS 2.3.2.1, 2.3.2.2,
- 2.3.2.3, 2.3.2.4 and 2.3.2.5 above must be met in the presence of any
- other pilot recommended by the CCITT.
-
- It is assumed that variations in level of the pilot and of the
- signalling tones are correlated.
-
-
-
- ____________________
- Recommendation Q.416
- »»»»»»»»»»»»»»»»»»»»
- * 2.4 : INTERRUPTION CONTROL
-
- 2.4.1 General
- ~~~~~
- In System R2, removal of the tone corresponds to the sending of the seizing
- and answer signals. Steps must be taken, therefore, to guard against unwanted
- interruption of the signalling channels resulting in false signalling.
- Special devices monitor a number of circuits and transmit an indication to
- each individual equipment as soon as an interruption occurs. The whole
- protection system against the effect of interruptions is designated by the
- term interruption control.
-
- In each case, the response time of the interruption control must be based
- on the time required to recognize the signalling condition.
-
- The interruption control systems in the two directions of transmission
- operate independently of each other.
-
- The interruption control specified uses the group pilot to detect
- interruptions.
-
-
- 2.4.2 Mode of operation of interruption control
- ~~~~~
- For each direction of transmission of a carrier circuit connection the
- equipment for interruption control comprises:
-
- o A group pilot generator at the outgoing end;
-
- o A pilot receiver and a wiring system for signalling the interruption at
- the incoming end.
-
- In principle, the existing pilots of the carrier system will be used.
-
- The receiver at one end supervises the pilot transmitted by the other end.
- When a considerable fall in the level of the pilot is detected it is assumed
- that an interruption has occurred on the signalling channels associated with
- the carrier circuits. The interruption control equipment then reacts to
- prevent the unwanted transmission of certain signals on those circuits which
- have already been seized or to ensure that idle circuits are blocked.
-
- Figure 10/Q.416 shows functionally an arrangement where the pilot receiver
- controls the relay sets of interrupted circuits.
-
- To ensure proper interruption control, it is essential that the individual
- transmission or switching equipments should not react to any change of
- signalling state due to a fault. The action initiated by the interruption
- control must therefore be completed in less time than the sum of the response
- time of the signalling receiver and the recognition time for the tone-off
- condition caused by interruption of the signalling channel. Again, to prevent
- the unwanted transfer of certain signals, interruption control, during
- re-establishment of the pilot, must return to alarm off after an interval long
- enough for the signalling equipment to revert to normal.
-
- To operate independently for each direction of transmission the incoming
- end interruption control supervises only the forward direction and, if
- necessary, initiates an operation at the outgoing end via the line signalling
- system. Conversely, interruption control at the outgoing end supervises the
- backward direction of transmission only.
-
- Blocking of a circuit at the outgoing end therefore takes place in two
- different ways:
-
- o Immediate blocking by intervention of interruption control at the
- outgoing end;
-
- o blocking on recognition in the backward direction of the tone-off
- condition caused by interruption control intervention at the incoming
- end.
-
- When the transmission system is re-established, interruption control
- reverts to normal and the signalling equipment must automatically revert to
- normal operating.
-
- Since the action to be taken on the individual circuits differs according
- to their state at the time the fault occurs, the different possibilities are
- dealt with in detail below.
-
- Figure 10/Q.416, p.5
-
- 2.4.2.1 Mode of operation of interruption control at the incoming end
- (transmission interrupted in the forward direction)
-
- a) Circuit in idle state
-
- Transition of interruption control to alarm brings about:
-
- i) removal of the tone in the backward direction by locking
- of the sending unit in the tone-off condition;
-
- ii) locking of the receiving unit in its position, i.e. in
- the tone-on condition.
-
- The effect of operation i) is to block the circuit at the
- outgoing end against possible seizing; operation ii) prevents
- incorrect recognition of seizing of the incoming circuit.
-
- Return of interruption control to normal ensures return to
- the idle state of the circuits affected by the fault, by
- switching sending units at the incoming end to the tone-on
- condition.
-
-
- b) Circuit seized prior to answered state
-
- Transition of interruption control to alarm brings about:
-
- i) locking of the sending unit in its position, i.e. in the
- tone-on condition;
-
- ii) locking of the receiving unit in its position, i.e. in
- the tone-off condition;
-
- iii) start of a time-out device which after a certain interval
- clears the chain beyond the faulty circuit; this timing
- arrangement may be the one specified in Recommendation
- Q.118, S 4.3.3.
-
-
- Operation i) prevents the transfer of an answer signal while
- interruption control is in action. If the called subscriber
- answers before the time out delay mentioned in iii) above has
- elapsed, then the timer is stopped. For existing equipment
- this requirement may not apply. If the called subscriber
- clears while interruption control is active, the part of the
- connection beyond the faulty circuit must be released
- immediately.
-
- Operation iii) prevents blocking of the called subscriber's
- line if the fault persists; short breaks, on the other hand,
- have no effect.
-
- When the caller clears, operations i) and ii) block the
- faulty circuit against any new seizure even when the backward
- signalling channel is still intact; since the release-guard
- signal has not been sent the outgoing circuit cannot return
- to the idle state.
-
- When interruption control reverts to normal before the called
- subscriber has answered, the call may still mature normally,
- provided the caller is holding.
-
- If the called subscriber has answered during the time-out
- delay and the interruption control reverts to normal with
- both the calling and called subscribers holding, the answer
- signal is sent immediately.
-
- If at the moment when interruption control reverts to normal
- the called subscriber has already cleared, operation ii)
- ensures that in all cases the release-guard sequence takes
- place as in S 2.2.2.6 a) above (either immediately if the
- outgoing exchange has already sent the clear-forward signal
- or when the caller clears). If, on the other hand, the
- called subscriber is still holding and the outgoing exchange
- is already sending the clear-forward signal when interruption
- control reverts to normal the circuit returns to the idle
- state at the outgoing end as described in S 2.2.2.6 b) above.
-
-
- c) Circuit in answered state
-
- Transition of interruption control to alarm brings about:
-
- i) locking of the sending unit in its position, i.e. in the
- tone-off condition;
-
- ii) locking of the receiving unit in its position, i.e. in
- the tone-off condition.
-
- When the caller clears, operation i) blocks the faulty
- circuit against any new seizure, even when the backward
- signalling channel is still intact; since the release-guard
- signal has not been sent, the outgoing circuit cannot return
- to the idle state.
-
- When the called subscriber clears, the part of the connection
- beyond the faulty circuit (including the called subscriber's
- line) must be released immediately.
-
- When interruption control reverts to normal with both
- subscribers still on the line, the connection is maintained.
-
- When the caller has already cleared by the time the
- interruption control reverts to normal, the release-guard
- sequence is carried out as in Recommendation Q.412, S 2.2.2.6
- b) or c).
-
-
- d) Circuit in clear-back state
-
- Transition of interruption control to alarm causes:
-
- i) locking of the sending unit in its position, i.e. in the
- tone-on condition;
-
- ii) locking of the receiving unit in its position, i.e. in
- the tone-off condition;
-
- iii) immediate release of the part of the connection beyond the
- faulty circuit (including the called subscriber's line).
-
- When interruption control reverts to normal, the
- release-guard signal is sent as in Recommendation Q.412, S
- 2.2.2.6 c) as soon as the clear-forward signal is recognized.
-
-
- e) Circuit in release
-
- When interruption control functions after a clear-forward
- signal has been recognized at the incoming end, it causes:
-
- i) locking of the sending unit in the tone-off | ondition; if
- at the instant interruption control operates, the tone-on
- condition exists in the backward direction, it will be
- switched to the tone-off condition following recognition
- of the clear-forward signal and locking in the tone-off
- condition can take place as prescribed;
-
- ii) locking of the receiving unit in its position, i.e. in
- the tone-on condition.
-
-
- The effect of operation i) is to guard the faulty circuit
- from a new seizure at the outgoing exchange.
-
- Operation ii) ensures the release of the part of the
- connection beyond the faulty circuit (including the called
- subscriber's line).
-
- When interruption control reverts to normal the tone-on
- condition is established in the backward direction and causes
- the circuit at the outgoing exchange to return to the idle
- state.
-
-
- 2.4.2.2 Mode of operation of interruption control at the outgoing end |
- transmission in the backward direction interrupted)
-
- a) Circuit in idle state
-
- Transition of interruption control to alarm is immediately
- followed by blocking of the outgoing circuit.
-
- b) Circuit seized but not in answered state (including
- clear-back)
-
- i) Transition of interruption control to alarm causes locking
- of the receiving unit in its position, i.e. the tone-on
- condition. This operation prevents recognition of an
- answer signal or return to the answered state should the
- called subscriber have cleared.
-
- ii) As soon as a clear-forward signal is sent on the part of
- the connection preceding the faulty circuit, it must be
- retransmitted; the tone must therefore be established in
- the forward direction to ensure, assuming that the forward
- signalling channel is left intact, that the part of the
- connection beyond the faulty circuit is released.
-
- iii) When interruption control reverts to normal, the tone may
- already have been sent in the forward direction as a
- clear-forward signal. If the forward signalling channel
- has remained intact, recognition at the incoming end of
- the tone-on condition will have caused generation of the
- release-guard sequence which, because of the fault, will
- not have been received at the outgoing end.
- Exceptionally, therefore, return of the outgoing circuit
- to the idle state must take place simply on recognition of
- tone-on in the backward direction without necessarily
- taking into account time-out T1.
-
- c) Circuit in answered state
-
- In this case transition of interruption control to alarm does
- not cause immediate action. A clear-forward signal sent on
- the part of the connection preceding the faulty circuit must
- be repeated forward to ensure that, if the forward signalling
- channel is left intact, the part beyond the faulty circuit is
- cleared.
-
- Once the interruption control reverts to normal the
- connection is maintained provided the caller and the called
- subscriber are still holding. On the other hand, by the time
- the interruption con- trol reverts to normal the
- clear-forward signal may already have been sent and the
- situation will be the one described in S 2.4.2.2 b), iii).
-
- d) Circuit in release
-
- [See S 2.4.2.2 b), iii).]
-
-
- 2.4.3 Clauses on interruption control equipment
- ~~~~~
- Adoption of thresholds with widely differing levels makes for economy in
- the design of interruption control equipment. Against this must be set the
- fact that the device cannot cope with the effects of certain slow drops in
- level. However, the probability of these occurring in practice is very small.
-
-
- 2.4.3.1 Pilots
-
- Interruption control uses the 84.08 kHz group pilot or by bilateral
- agreement and, at the request of the receiving end country, the 104.08
- kHz group pilot.
-
- However, if the ends of the supergroup link coincide with the end of the
- five group links it is carrying, the supergroup pilot may also be used.
-
-
- 2.4.3.2 Alarm-on threshold
-
- Interruption control must pass to alarm-on | hen the pilot level,
- measured at the group distribution frame or at an equivalent point,
- drops to -29 dBm0.
-
-
- 2.4.3.3 Alarm-off threshold
-
- Interruption control must revert to alarm-off | i.e. normal when the
- pilot level, measured at the group distribution frame or at an
- equivalent point, rises to -24 dBm0.
-
-
- 2.4.3.4 Response time for a drop in level
-
- Interruption control must pass from normal to alarm-on within an
- interval t v such that:
-
- 5 ms t v tr\ds m\di\dn
- + 13 ms
-
-
- when the pilot level, measured at the group distribution frame or at an
- equivalent point, suddenly drops from its nominal level to -33 dBm0.
-
- In the above formula, tr\dsm\di\dnis the minimum response time of the
- signalling receiver for a drop in level, taking into account a possible
- variation of _ | dB in the signalling tone level from its nominal value,
- the level being measured on the receiving side of the group distribution
- frame or at an equivalent point.
-
- If the value (40 _ 10) ms is exclusively applied, it is possible to use
- the minimum value of 30 ms instead of 13 ms for the interruption control
- device. The figure of 13 ms in the above formula is derived on the
- assumption that the output of the interruption control equipment acts
- upon the input of the device which regulates the recognition time for
- the tone-on and tone-off conditions (20 _ 7 ms) , i.e. absence of a
- direct current signal at this input for a period of up to 13 ms has no
- relevance.
-
-
- 2.4.3.5 Response time for rise in level
-
- Interruption control must revert from the alarm-on to normal in an
- interval t ^ such that:
-
- tr\ds m\da\dx - 13 ms t
- ^ 500 ms
-
- when the pilot level, measured at the group distribution frame or at an
- equivalent point, suddenly rises from its nominal level to -33 dBm0.
-
- In the above formula, tr\dsm\da\dxis the maximum response time of the
- signalling receiver for a rise in level, taking into account a possible
- variation of _ | dB in the signalling tone level from its nominal value,
- the level being measured on the receiving side of the group distribution
- frame or at an equivalent point.
-
- The figure of 13 ms in the above formula is derived on the assumption
- that the output of the interruption control equipment acts upon the
- input of the device which regulates the recognition time for tone-on and
- tone-off condition (20 _ 7 ms) i.e. absence of a direct current signal
- at this input for a period of up to 13 ms has no relevance.
-
-
- 2.4.3.6 Precautions against noise
-
- An interruption may produce increased noise on the group link.
- Interruption control must be capable of distinguishing between the pilot
- itself and a high level noise simulating the pilot.
-
- Interruption control must not revert to normal in the presence of white
- noise having a spectral power density of not more than -47 dBm0 per Hz.
-
- To facilitate the design of interruption control equipment operating
- satisfactorily at high noise levels, the upper limit of 500 ms for t ^
- has been specified.
-
-
-
-
- SECTION 3
-
- LINE SIGNALLING, DIGITAL VERSION
- ____________________
- Recommendation Q.421
- »»»»»»»»»»»»»»»»»»»»
- * 3.1 : DIGITAL LINE SIGNALLING CODE
-
- 3.1.1 General
- ~~~~~
- Primary PCM multiplexes (see Recommendations G.732 and G.734) economically
- provide more than one signalling channel per speech circuit in each direction
- of transmission. By making use of the increased signalling capacity,
- simplification of the outgoing and incoming switching equipment can be
- achieved since the timing conditions necessary for the System R2 line
- signalling, analogue version, are not required. For this reason the digital
- version of System R2 line signalling is recommended for use on PCM systems in
- national and international public switched networks and is specified below.
-
- Note - The continuous line signalling scheme specified for FDM systems may
- also be used on PCM systems by utilizing one signalling channel only in
- each direction. In this case relay sets designed for the continuous
- line signalling system on FDM channels can be used provided that the
- functions specified for the interruption control on FDM circuits (see
- Recommendation Q.416) are performed by use of the local alarm facility
- provided by PCM equipment. This method of line signalling on PCM
- systems is not recommended for use on international circuits.
-
- The digital version of System R2 line signalling uses two signalling
- channels in each direction of transmission per speech circuit. These
- signalling channels are referred to as afand bffor the forward direction (i.e.
- the direction of call set-up) and aband bbfor the backward direction.
-
- Under normal conditions:
-
- o The afchannel identifies the operating condition of the outgoing
- switching equipment and reflects the condition of the calling
- subscriber's line.
-
- o The bfchannel provides a means for indicating a failure in the forward
- direction to the incoming switching equipment.
-
- o The abchannel reflects the condition of the called subscriber's line (on
- hook or off hook).
-
- o The bbchannel indicates the idle or seized state of the incoming
- switching equipment.
-
- The line signals are transmitted link-by-link.
-
- The digital version of System R2 line signalling also specifies a means for
- appropriate action in the case of faulty transmission conditions on the PCM
- multiplex, see Recommendation Q.424.
-
- The signalling system is specified for one-way operation, but both-way
- operation is also possible (see S 3.2.7 below).
-
-
- 3.1.2 Signalling code
- ~~~~~
- Table 2/Q.421, shows the signalling code on the PCM line under normal
- conditions.
-
- H.T. [2/Q.421]
- TABLE 2/Q.421
-
- __________________________________________________
- Signalling code
- State of the circuit Forward Backward a f
- __________________________________________________
- Idle/Released 1 0 1 0
- Seized 0 0 1 0
- Seizure acknowledged 0 0 1 1
- Answered 0 0 0 1
- Clear-back 0 0 1 1
- Clear-forward |
- |
- |
- |
- |
- |
- |
- |
- |
-
-
-
-
-
-
-
- 1 |
- |
- |
- |
- |
- |
- |
-
-
-
-
-
- 0 |
- |
- |
- |
- |
- |
- |
- |
-
-
-
-
-
-
- 0 |
- |
- |
- |
- |
- |
- |
-
-
-
-
-
- 1
-
-
- or
- 1 1
- Blocked 1 0 1 1
- __________________________________________________
-
- Table [2/Q.421], p.
-
-
-
-
-
-
-
-
-
-
-
- ____________________
- Recommendation Q.422
- »»»»»»»»»»»»»»»»»»»»
- * 3.2 : CLAUSES FOR EXCHANGE LINE SIGNALLING EQUIPMENT
-
- 3.2.1 Recognition of a change of signalling code
- ~~~~
- 3.2.1.1 Signalling channel transitions
-
- The recognition time for a transition from 0 to 1 or vice versa on a
- signalling channel is 20 _ 10 ms. This value presupposes the existence
- of protection against the effects of faulty transmission conditions on
- the PCM multiplex.
-
- The recognition time is defined as the duration that the signals
- representing 0 or 1 must have at the output of the terminal equipment of
- a signalling channel in order to be recognized by the exchange
- equipment.
-
-
- 3.2.1.2 Change of signalling code
-
- Recognition of a change of signalling code is thus defined as either of
- the following:
-
- a) Recognition of a transition detected on one signalling channel with
- no transition detected on the second signalling channel during the
- recognition period.
-
- b) Recognition of a transition detected on the second signalling channel
- during the recognition period already being applied to the first
- signalling channel. In this case, a change of signalling code is
- recognized only when both recognition timing periods have elapsed.
-
-
- 3.2.2 Sent signal time tolerance
- ~~~~~
- The time difference between application of transitions intended to be
- simultaneous on two signalling channels in the same direction of transmission
- must not exceed 2 ms.
-
-
- 3.2.3 States and procedures under normal conditions | see Table 2/Q.421)
- ~~~~~
- In the forward direction bf= 0 is established permanently.
-
- 3.2.3.1 Idle state
-
- In the idle state the outgoing end sends af= 1, bf= 0. At the incoming
- end this results in sending ab = 1, bb= 0 in the backward direction,
- provided that the switching equipment at the incoming end of the circuit
- is idle.
-
-
- 3.2.3.2 Seizing procedure
-
- i) Seizure
-
- Seizing should occur only if ab = 1, bb = 0 is recognized.
- The outgoing end changes af = 1 into af = 0. The code af =
- 0, bf = 0 must be maintained until the seizing
- acknowledgement signal is recognized. In this way the
- outgoing switching equipment will only be able to send the
- clear-forward signal after recognition off the seizing
- acknowledgement signal.
-
- ii) Seizure acknowledgement
-
- After having recognized the seizing signal, the incoming end
- sends ab = 1, bb = 1 as an acknowledgement.
-
- 3.2.3.3 Answering
-
- The off-hook condition of the called subscriber's line provokes the
- incoming switching equipment to send ab = 0, bb = 1.
-
- The answered state must be established on the preceding link immediately
- after it is recognized: see also S 3.2.3.6 below.
-
-
- 3.2.3.4 Clear-back
-
- The on-hook condition of the called subscriber's line provokes the
- incoming switching equipment to send ab = 1, bb = 1. The clear-back
- state must be established on the preceding link immediately after it is
- recognized: see also S 3.2.3.6 below.
-
-
- 3.2.3.5 Clear-forward procedure
-
- The cleared condition of the calling subscriber's line or the release of
- the outgoing switching equipment will normally result in sending af = 1,
- bf = 0. The outgoing switching equipment will not be restored to the
- idle state until recognition of the code ab = 1, bb = 0: see also SS
- 3.2.3.2, 3.2.3.6 and Table 3/Q.422.
-
-
- 3.2.3.6 Release procedure
-
- Recognition of the clear-forward signal in the incoming switching
- equipment initiates the release of the succeeding link even though
- answering or clearing by the called party has occurred. Upon complete
- release of the incoming switching equipment, the code ab = 1, bb = 0 is
- established on the circuit. This will cause the circuit to be restored
- to the idle state and the outgoing switching equipment to become
- available for another call.
-
-
- 3.2.3.7 Blocking and unblocking procedure
-
- Blocking of an idle circuit to new calls at the outgoing end must occur
- as soon as ab = 1 and bb = 1 is recognized: see also Tables 3/Q.422 and
- 4/Q.422.
-
- The recognition of ab = 1, bb = 0 restores the circuit to the idle
- state.
-
-
- 3.2.4 Actions appropriate to various signalling conditions
- ~~~~~
- In addition to normal conditions described in Table 2/Q.421 other
- conditions due to faults may be encountered. Tables 3/Q.422 and 4/Q.422
- indicate the states appropriate to each signalling code recognized and the
- actions to be taken at the outgoing and incoming end respectively of a circuit
- operated with the digital version of System R2 line signalling.
-
- 3.2.4.1 Outgoing end
-
- H.T. [3/Q.422]
- TABLE 3/Q.422
-
- _____________________________________________________________________________________________________________________________________
-
-
- Received code
-
- {
- a b = 0, b b = 0 a b = 0, b b = 1 = 1, b b = 0 a b = 1, b b = 1
- _____________________________________________________________________________________________________________________________________
- Idle/Released a f = 1, b f = 0 Abnormal, see Note 1 Abnormal, see Note 1 Idle Blocked
- _____________________________________________________________________________________________________________________________________
- Seized a f = 0, b f = 0 Abnormal, see Note 2 Abnormal, see Note 2 Sed see Note 2 Seizure acknowledged
- _____________________________________________________________________________________________________________________________________
- Seizure acknowledged a f = 0, b f = 0 Abnormal, see Note 3 Answered Abmal, see Note 3 Seizure acknowledged
- _____________________________________________________________________________________________________________________________________
- Answered a f = 0, b f = 0 Abnormal, see Note 4 Answered Abmal, see Note 4 Clear-back
- _____________________________________________________________________________________________________________________________________
- Clear-back a f = 0, b f = 0 Abnormal, see Note 4 Answered Abmal, see Note 4 Clear-back
- _____________________________________________________________________________________________________________________________________
-
-
-
-
-
-
-
-
-
- Clear-forward a f = 1, b f = 0 Abnormal, see Note 1 Clear-forward leased = Idle Clear-forward
- _____________________________________________________________________________________________________________________________________
- Blocked a f = 1, b f = 0 Abnormal, see Note 1 Abnormal, see Note 1 Idle Blocked
- _____________________________________________________________________________________________________________________________________
-
-
- Note 1 - In these abnormal conditions the outgoing end must prevent a new
- seizure of the circuit. A delayed alarm should also be given (see S
- 3.2.6).
-
- Note 2 - Non-recognition of the seizing acknowledgement signal 100 ms-200 ms
- after sending the seizing signal on a terrestrial link or 1-2 seconds
- after sending the seizing signal on a satellite link results in an
- alarm and either congestion information being sent backward or a
- repeat attempt being made to set up the call. The outgoing end must
- prevent a new seizure of the circuit. When the seizing
- acknowledgement signal is recognized after the time-out period has
- elapsed, the clear-forward signal must be sent.
-
- Note 3 - Receipt of b b = 0 by the outgoing switching equipment for 1-2
- seconds after recognition of the seizing acknowledgement signal and
- prior to recognition of the answer signal, results in an alarm and
- either congestion information being sent backward or a repeat attempt
- being made to set up the call. The outgoing end must prevent new
- seizures of the circuit. When b b reverts to 1 after the 1-2 seconds
- timeout period has elapsed, the clear-forward signal must be sent.
-
- Note 4 - In the case of recognition of b b = 0 whilst in the answered or
- clear-back state, immediate action is not necessary. On receipt of
- clearing from the preceding link, the clear-forward signal (a f = 1,
- b f = 0) must not be sent until b b is restored to 1. A delayed
- alarm should also be given. Tableau [3/Q.422] + Remarques, p.7
-
-
- 3.2.4.2 Incoming end
-
- H.T. [4/Q.422]
- TABLE 4/Q.422
-
- _____________________________________________________________________________________________________________________________________________________
-
-
- Received code
-
- {
- a f = 0, b f = 0 a f0, b f = 1 a f = 1, b f = 0 a f = 1, b f = 1
- _____________________________________________________________________________________________________________________________________________________
- Idle/Released a b = 1, b b = 0 Seized Faulsee Note 1 Idle Fault see Note 1
- _____________________________________________________________________________________________________________________________________________________
- Seizure acknowledged a b = 1, b b = 1 Seizure acknowledged FaulSee Note 2 Clear- forward Fault See Note 2
- _____________________________________________________________________________________________________________________________________________________
- Answered a b = 0, b b = 1 Answered Faulsee Note 3 Clear- forward Fault see Note 3
- _____________________________________________________________________________________________________________________________________________________
- Clear-back a b = 1, b b = 1 Clear-back Faulsee Note 4 Clear- forward Fault see Note 4
- _____________________________________________________________________________________________________________________________________________________
- Clear-forward {
- a
- b = 0, b
- b = 1
- or
- a
- b = 1, b
- b = 1
- } Abnormal seized see Note 7 Fault see Note 7 Clear- ward see Note 7 Fault see Note 7
- _____________________________________________________________________________________________________________________________________________________
- Blocked a b = 1, b b = 1 Abnormal seized see Note 5 Faulsee Note 6 Blocked Fault see Note 6
- _____________________________________________________________________________________________________________________________________________________
-
-
- Note 1 - When in the idle/released state b f changes to 1, b b must be changed
- to 1.
-
- Note 2 - In these cases a time-out device is started, which after a certain
- interval clears the connection beyond the faulty circuit: this
- timing arrangement may be the one specified in Recommendation Q.118,
- Section 4.3.3. If the answer signal is recognized during the
- time-out delay, the timer is stopped but the answer signal is not
- sent on the preceding link until recognition of a f = 0, b f = 0. If
- the clear-back signal is recognized while the fault persists, the
- connection beyond the faulty circuit must be released immediately.
- Additionally, when the incoming register has not started to send the
- last backward signal, the rapid release procedure described in Note 5
- may be used.
-
- Note 3 - In these cases no action is taken until the clear-back signal is
- recognized, at which stage the connection beyond the faulty circuit
- is immediately released.
-
- Note 4 - Under these conditions the succeeding link must be released
- immediately.
-
- Note 5 - In this case immediate action is not necessary. However, rapid
- release of the circuit should occur if the incoming end simulates
- answer by sending a b = 0, b b = 1.
-
- Note 6 - Under these conditions no action is taken.
-
- Note 7 - After clear-forward signal is recognized and until the code a b = 1,
- b b = 0 is sent, all transitions in the forward direction shall be
- ignored.
-
- Tableau [4/Q.422] + Remarques, p.8
-
- 3.2.5 Abnormal conditions
- ~~~~~
- 3.2.5.1 Special release arrangements
-
- a) If an exchange where an outgoing R2 register is situated recognizes
- ab = 0, bb = 1 (premature answer) before an address-complete signal
- A-6 or a Group B signal is received, the connection must be released.
- Congestion information is then sent backward or a repeat attempt is
- made to set up the call.
-
- b) In the cases of non-receipt of the answer signal, of delay in
- clearing by the calling subscriber in automatic working and of
- non-receipt of the clear-forward signal by the incoming exchange
- after the clear-back signal has been sent, the provisions of
- Recommendation Q.118 apply.
-
-
- 3.2.5.2 Safeguard against failures
-
- The PCM equipment and the exchange line signalling equipment should be
- designed in such a way that at least those faults which are most likely
- to occur in this equipment or in the interconnecting cables, result in
- blocking of the circuit at the outgoing end and in the ultimate clearing
- of the connection beyond the incoming switching equipment. This can be
- achieved, as far as possible, by ensuring that a = 1, b = 1 is sent on
- line upon:
-
- o removal of PCM or switching equipment by maintenance personnel;
-
- o occurrences of abnormal conditions (e.g. open wire, low voltage) in
- switching equipment.
-
-
- 3.2.6 Alarms for technical staff
- ~~~~~
- According to Recommendation Q.117, an alarm must in principle be given to
- the technical staff upon recognition of abnormal conditions.
-
- Arrangements for these alarms are to be specified by the Administrations.
-
- It is recommended that a delayed alarm be given at the outgoing end for the
- procedure described under S 3.2.3.7 above (blocking) and for the following
- reasons:
-
- o when the abnormal conditions covered by Note 1 to Table 3/Q.422 are
- applicable;
-
- o when the seizing acknowledgement signal is not recognized within the time
- specified in Note 2 to Table 3/Q.422 after sending the seizing signal;
-
- o when, after recognition of the seizing acknowledgement signal and prior
- to recognition of the answer signal, bb = 0 is received for 1-2 seconds;
-
- o when the abnormal conditions covered by Note 4 to Table 3/Q.422 are
- applicable.
-
- It is also recommended that a delayed alarm be given under PCM failure
- conditions specified in Recommendations G.732 and G.734.
-
-
- 3.2.7 Both-way working
- ~~~~~
- System R2 is specified for one-way working, but in principle the line
- signalling code detailed in Recommendation Q.421 is also suitable for use on
- both-way circuits. Where Administrations have undertaken, by bilateral
- agreement, to use both-way working, the clauses and additional specifications
- for exchange signalling equipment detailed in SS 3.2.7.1 and 3.2.7.2 below,
- must be observed.
-
- 3.2.7.1 Procedures under normal conditions
-
- a) Double seizure
-
- Double seizure is assumed if the outgoing equipment is in a seized
- state and the signalling code ab = 0, bb = 0 is recognized instead of
- ab = 1, bb = 1 (seizure acknowledgement). In such a situation the
- connection must be released at both ends and congestion information
- sent to the calling subscriber or a repeat attempt must be made. On
- recognition of double seizure the line signalling equipment at both
- ends must maintain the seized state for a minimum of 100 ms after
- which the clear-forward signal af = 1, bf = 0 must be sent.
-
- 100 ms after sending the clear-forward signal and on recognition of
- ab = 1, bb = 0 each end may assume the idle state.
-
- The clear-forward state af = 1, bf = 0 must be maintained for at
- least 100 ms to ensure that it is recognized at the other end.
-
- In the sense of preventive action it is recommended that an opposite
- order of circuit selection be used by each exchange of a both-way
- circuit group to minimize double seizure.
-
-
- b) Requirements for circuit release
-
- When a both-way circuit is released, the end which acted as the
- incoming end must maintain the signalling code ab = 1, bb = 0 for at
- least 100 ms to ensure that the signal is recognized at the other end
- after which the circuit becomes idle.
-
-
- c) Blocking and unblocking procedure
-
- When a both-way circuit is blocked manually in its idle state at one
- end (e.g. end B) the blocking signal must be sent to the other end
- (A). The circuit must then be kept blocked locally (at end A)
- against all calls in the A to B traffic direction as long as the
- blocked state persists in the B to A direction.
-
- In order to avoid permanent blocking, end A should maintain the
- signalling code a = 1, b = 0 in the direction A to B.
-
- When the blocked state is removed, end B must send the clear-forward
- signal and must maintain that state for at least 100 ms, before
- assuming the idle state.
-
-
- 3.2.7.2 Special arrangement
-
- The physical realization of signalling equipment terminating a bothway
- circuit may allow that part of the equipment concerned with outgoing
- calls to be removed without preventing the remaining equipment from
- being used for incoming calls. In this case it is only necessary to
- block the circuit locally against outgoing calls and a blocking signal
- need not be sent to the other end.
-
-
-
-
- ____________________
- Recommendation Q.424
- »»»»»»»»»»»»»»»»»»»»
- * 3.3 : PROTECTION AGAINST THE EFFECTS OF FAULTY TRANSMISSION
-
- Faulty transmission conditions in PCM systems can lead to degradation of
- the speech channels and erroneous signalling. In the case of primary PCM
- multiplex equipment operating at 2048 kbit/s failures due to loss of frame or
- multi-frame alignment and/or failure of any other important function results
- in both PCM terminals going into alarm condition in accordance with
-
-
- ________________________________
- Recommendations G.732 and G.734.
- »»»»»»»»»»»»»»»»»»»»»»»»»»»»»»»»
- Thus both PCM terminals apply the state corresponding to state 1 on the PCM
- line on each "receive" signalling channel at the interfaces with the switching
- equipment, as indicated in Table 4 of Recommendation G.732. In this way, the
- incoming switching equipment receives the equivalent of af = 1, bf = 1 on the
- PCM line and the outgoing switching equipment receives the equivalent of ab =
- 1, bb = 1.
-
- These characteristics are taken into account in the present specifications
- (see S 3.2.4) so that:
-
- o at the outgoing end (see Table 3/Q.422) a PCM fault results in a blocked
- state, seizure acknowledged state or clear-back state. This means that
- all circuits in the idle state of a faulty PCM multiplex will be blocked
- against seizure and that seized circuits will go to or remain in the
- seizure acknowledged or clear-back state;
-
- o at the incoming end (see Table 4/Q.422) a PCM fault can be identified and
- appropriate actions can be taken.
-
- When the signalling equipment is a part of a digital exchange, it may
- receive alarm indications in a form other than both signalling bits in state
- one. The failure may be detected by the signalling equipment or an indication
- be received from the PCM terminal according to Recommendation G.734.
-
- When the signalling equipment recognizes a failure it must:
-
- o block the detection of signalling transitions to avoid recognition of
- erroneous signalling codes caused by the failure. This action must be
- taken as soon as possible and at least within 3 ms as specified in
- Recommendation G.734 for a PCM termi nal,
-
- o react as specified in Tables 3/Q.422 and 4/Q.422 when a signalling code a
- = 1, b = 1 is detected at the input of signalling equipment situated at
- the analogue access of a PCM terminal equipment complying with
- Recommendation G.732.
-
-
-
- ____________________
- Recommendation Q.430
- »»»»»»»»»»»»»»»»»»»»
- * 3.5 : CONVERSION BETWEEN ANALOGUE AND DIGITAL VERSIONS OF SYSTEM R2 LINE
- SIGNALLING
-
- This Recommendation is applicable to a conversion equipment placed on the
- circuit between two switching exchanges each using one of the two versions
- specified for System R2 line signalling. Owing to this particular use, all
- the specifications for the two versions of the line signalling may not be
- fully observed. Nevertheless, the diagrams which follow are based on the
- principles of CCITT Recommendations Q.411, Q.412 and Q.416 for the analogue
- version and on Recommendations Q.421, Q.422 and Q.424, for the digital
- version. The only time conditions taken into account in this Recommendation
- are those set out in the aforementioned Recommendations. The operation of the
- interruption control device is also, wherever possible, that specified in
- Recommendation Q.416. As stated in that Recommendation, the receiver is
- blocked immediately whenever pilot tone off is detected: since this is a
- routine operation, it has not been represented explicitly in the diagrams.
-
- The conversion diagrams have been divided into four parts:
-
- o for conversion between the analogue version at the incoming end and the
- digital version at the outgoing end, into:
-
- o incoming analogue,
-
- o outgoing digital;
-
- o for conversion between the digital version at the incoming end and the
- analogue version at the outgoing end, into:
-
- o incoming digital,
-
- o outgoing analogue.
-
- It should be noted, however, that this Recommendation can be simplified
- with respect to alarm processing when the conversion equipment is connected
- directly at the input or output of a switch- ing exchange; the processes
- necessary for this application are shown on the diagrams with thickened lines.
-
-
- 1. Drawing conventions
- ~~~~~~~~~~~~~~~~~~~~~~~
-
- - tone
-
- tf = 1 tone on forward
-
- tf = 0 tone off forward
-
- tb = 1 tone on backward
-
- tb = 0 tone off backward
-
-
- When recognized
-
-
- p = 1 pilot tone on
-
- p = 0 pilot tone off
-
- - signalling bits
-
- The conventions are those of Recommendation Q.421.
-
-
- 2. Conversion incoming analogue version to outgoing digital version
- ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
-
- * 2.1 : Incoming analogue
-
- Figure CCITT-55980, p.
-
- List of timers:
-
- T2: Recommendation Q.412 (S 2.2.2.7)
-
- T3: 2 to 3 mn Recommendation Q.118 (S 4.3.3)
-
- In sheets 2 and 4 the diagram for group pilot supervision is given.
-
- In sheets 3 and 5 the diagram for supergroup pilot supervision is given.
-
- Sheet 1 is for group and supergroup pilot supervision.
-
-
- FIGURE CCITT-60881 (feuillet 1), p.10
-
- FIGURE CCITT-60891 (feuillet 2), p.11
-
- FIGURE T1115760-88 (feuillet 3), p.
-
- FIGURE CCITT-60901 (feuillet 4), p.12
-
- FIGURE T1115770-88 (feuillet 5), p.
-
-
- * 2.2 : Outgoing digital
-
- Figure CCITT-55990, p.
-
- List of timers:
-
- T6: Recommendation Q.422 (S 3.2.4.1, Note 2 to Table 3)
-
- Figure CCITT-60911 (Sheet 1 of 3), p.
-
- Figure CCITT-60920 (Sheet 2 of 3), p.
-
- Figure CCITT-60930 (Sheet 3 of 3), p.
-
-
- 3. Conversion incoming digital version to outgoing analogue version
- ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
- * 3.1 : Incoming digital
-
- Figure CCITT-56000, p.
- List of timers:
-
- T3: 2 to 3 mn Recommendation Q.118 (S 4.3.3)
-
-
- Figure CCITT-60940 (Sheet 1 of 3), p.
-
- Figure CCITT-60950 (Sheet 2 of 3), p.
-
- Figure CCITT-60960 (Sheet 3 of 3), p.
-
-
- * 3.2 : Outgoing analogue
-
- Figure CCITT-50610, p.
-
-
- List of timers:
-
- T1: Recommendation Q.412 (S 2.2.2.7)
-
- T5: 100 ms Recommendation Q.412 (S 2.2.2.1)
-
- Automatic restoration of an abnormally blocked circuit
- Recommendation Q.490 (S 6.6)
-
- n: number of attempts made
-
- T4: 30 s to 2 mn
-
- T7: 2 to 3 s
-
-
-
-
- Figure CCITT-60971 (Sheet 1 of 5), p.
-
- Figure CCITT-60981 (Sheet 2 of 5), p.
-
- Figure CCITT-60991 (Sheet 3 of 5), p.
-
- Figure CCITT-70001 (Sheet 4 of 5), p.
-
- Figure, p.
-
-
-