  4.  
  5.  
  6.  
  7. Network Working Group                                    J. Case, Editor Request for Comments: 1628                   SNMP Research, Incorporated Category: Standards Track                                       May 1994 
  8.  
  9.                      UPS Management Information Base 
  10.  
  11. Status of this Memo 
  12.  
  13.    This document specifies an Internet standards track protocol for the    Internet community, and requests discussion and suggestions for    improvements.  Please refer to the current edition of the "Internet    Official Protocol Standards" (STD 1) for the standardization state    and status of this protocol.  Distribution of this memo is unlimited. 
  14.  
  15. Table of Contents 
  16.  
  17.    1. Introduction ..............................................    1    2. The SNMPv2 Network Management Framework ...................    2    2.1 Object Definitions .......................................    2    3. Overview ..................................................    2    4. Definitions ...............................................    3    4.1 The Device Identification Group...........................    4    4.2 The Battery Group ........................................    5    4.3 The Input Group ..........................................    7    4.4 The Output Group .........................................    9    4.5 The Bypass Group .........................................   12    4.6 The Alarm Group ..........................................   13    4.7 The Test Group ...........................................   19    4.8 The Control Group ........................................   23    4.9 The Configuration Group ..................................   26    5. Acknowledgements ..........................................   43    6. References ................................................   44    7. Security Considerations ...................................   45    8. Author's Address ..........................................   45 
  18.  
  19. 1.  Introduction 
  20.  
  21.    This memo defines a portion of the Management Information Base (MIB)    for use with network management protocols in the Internet community.    In particular, it defines objects for managing uninterruptible power    supply (UPS) systems. 
  22.  
  23.  
  24.  
  25.  
  26.  
  27.  
  28.  
  29.  
  30.  
  31. Case                                                            [Page 1] 
  32.  RFC 1628                        UPS MIB                         May 1994 
  33.  
  34.  2.  The SNMPv2 Network Management Framework 
  35.  
  36.    The SNMPv2 Network Management Framework consists of four major    components.  They are: 
  37.  
  38.       o    RFC 1442 which defines the SMI, the mechanisms used for            describing and naming objects for the purpose of management. 
  39.  
  40.       o    STD 17, RFC 1213 defines MIB-II, the core set of managed            objects for the Internet suite of protocols. 
  41.  
  42.       o    RFC 1445 which defines the administrative and other            architectural aspects of the framework. 
  43.  
  44.       o    RFC 1448 which defines the protocol used for network access            to managed objects. 
  45.  
  46.    The Framework permits new objects to be defined for the purpose of    experimentation and evaluation. 
  47.  
  48. 2.1.  Object Definitions 
  49.  
  50.    Managed objects are accessed via a virtual information store, termed    the Management Information Base or MIB.  Objects in the MIB are    defined using the subset of Abstract Syntax Notation One (ASN.1)    defined in the SMI.  In particular, each object type is named by an    OBJECT IDENTIFIER, an administratively assigned name.  The object    type together with an object instance serves to uniquely identify a    specific instantiation of the object.  For human convenience, we    often use a textual string, termed the descriptor, to refer to the    object type. 
  51.  
  52. 3.  Overview 
  53.  
  54.    This document defines the managed objects for Uninterruptible Power    Supplies which are to be manageable via the Simple Network Management    Protocol (SNMP). 
  55.  
  56.  
  57.  
  58.  
  59.  
  60.  
  61.  
  62.  
  63.  
  64.  
  65.  
  66.  
  67.  
  68.  Case                                                            [Page 2] 
  69.  RFC 1628                        UPS MIB                         May 1994 
  70.  
  71.  4.  Definitions 
  72.  
  73.    UPS-MIB DEFINITIONS ::= BEGIN 
  74.  
  75.    IMPORTS        MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,        OBJECT-IDENTITY, Counter32, Gauge32, Integer32            FROM SNMPv2-SMI        DisplayString, TimeStamp, TimeInterval, TestAndIncr,          AutonomousType            FROM SNMPv2-TC        MODULE-COMPLIANCE, OBJECT-GROUP            FROM SNMPv2-CONF; 
  76.  
  77.     upsMIB MODULE-IDENTITY        LAST-UPDATED "9402230000Z"        ORGANIZATION "IETF UPS MIB Working Group"        CONTACT-INFO               "        Jeffrey D. Case 
  78.  
  79.                 Postal: SNMP Research, Incorporated                         3001 Kimberlin Heights Road                         Knoxville, TN  37920                         US 
  80.  
  81.                    Tel: +1 615 573 1434                    Fax: +1 615 573 9197 
  82.  
  83.                 E-mail: case@snmp.com"        DESCRIPTION                "The MIB module to describe Uninterruptible Power                Supplies."        ::= { mib-2 33 } 
  84.  
  85.    PositiveInteger ::= TEXTUAL-CONVENTION        DISPLAY-HINT "d"        STATUS       current        DESCRIPTION                "This data type is a non-zero and non-negative value."        SYNTAX       INTEGER (1..2147483647) 
  86.  
  87.    NonNegativeInteger ::= TEXTUAL-CONVENTION        DISPLAY-HINT "d"        STATUS       current        DESCRIPTION                "This data type is a non-negative value."        SYNTAX       INTEGER (0..2147483647) 
  88.  
  89.  
  90.  
  91. Case                                                            [Page 3] 
  92.  RFC 1628                        UPS MIB                         May 1994 
  93.  
  94.     upsObjects            OBJECT IDENTIFIER ::= { upsMIB 1 } 
  95.  
  96.     --    -- The Device Identification group.    --      All objects in this group except for upsIdentName and    --      upsIdentAttachedDevices are set at device initialization    --      and remain static.    -- 
  97.  
  98.    upsIdent              OBJECT IDENTIFIER ::= { upsObjects 1 }     upsIdentManufacturer OBJECT-TYPE        SYNTAX     DisplayString (SIZE (0..31))        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The name of the UPS manufacturer."        ::= { upsIdent 1 } 
  99.  
  100.    upsIdentModel OBJECT-TYPE        SYNTAX     DisplayString (SIZE (0..63))        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The UPS Model designation."        ::= { upsIdent 2 } 
  101.  
  102.    upsIdentUPSSoftwareVersion OBJECT-TYPE        SYNTAX     DisplayString (SIZE (0..63))        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The UPS firmware/software version(s).  This variable                may or may not have the same value as                upsIdentAgentSoftwareVersion in some implementations."        ::= { upsIdent 3 } 
  103.  
  104.    upsIdentAgentSoftwareVersion OBJECT-TYPE        SYNTAX     DisplayString (SIZE (0..63))        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The UPS agent software version.  This variable may or                may not have the same value as                upsIdentUPSSoftwareVersion in some implementations."        ::= { upsIdent 4 } 
  105.  
  106.  
  107.  
  108.  Case                                                            [Page 4] 
  109.  RFC 1628                        UPS MIB                         May 1994 
  110.  
  111.     upsIdentName OBJECT-TYPE        SYNTAX     DisplayString (SIZE(0..63))        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "A string identifying the UPS.  This object should be                set by the administrator."        ::= { upsIdent 5 } 
  112.  
  113.    upsIdentAttachedDevices OBJECT-TYPE        SYNTAX     DisplayString (SIZE(0..63))        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "A string identifying the devices attached to the                output(s) of the UPS.  This object should be set by                the administrator."        ::= { upsIdent 6 } 
  114.  
  115.     --    -- Battery Group    -- 
  116.  
  117.    upsBattery            OBJECT IDENTIFIER ::= { upsObjects 2 } 
  118.  
  119.    upsBatteryStatus OBJECT-TYPE        SYNTAX     INTEGER {            unknown(1),            batteryNormal(2),            batteryLow(3),            batteryDepleted(4)        }        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The indication of the capacity remaining in the UPS                system's batteries.   A value of batteryNormal                indicates that the remaining run-time is greater than                upsConfigLowBattTime.  A value of batteryLow indicates                that the remaining battery run-time is less than or                equal to upsConfigLowBattTime.  A value of                batteryDepleted indicates that the UPS will be unable                to sustain the present load when and if the utility                power is lost (including the possibility that the                utility power is currently absent and the UPS is                unable to sustain the output)."        ::= { upsBattery 1 } 
  120.  
  121.  
  122.  
  123. Case                                                            [Page 5] 
  124.  RFC 1628                        UPS MIB                         May 1994 
  125.  
  126.     upsSecondsOnBattery OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "seconds"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "If the unit is on battery power, the elapsed time                since the UPS last switched to battery power, or the                time since the network management subsystem was last                restarted, whichever is less.  Zero shall be returned                if the unit is not on battery power."        ::= { upsBattery 2 } 
  127.  
  128.    upsEstimatedMinutesRemaining OBJECT-TYPE        SYNTAX     PositiveInteger        UNITS      "minutes"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "An estimate of the time to battery charge depletion                under the present load conditions if the utility power                is off and remains off, or if it were to be lost and                remain off."        ::= { upsBattery 3 } 
  129.  
  130.    upsEstimatedChargeRemaining OBJECT-TYPE        SYNTAX     INTEGER (0..100)        UNITS      "percent"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "An estimate of the battery charge remaining expressed                as a percent of full charge."        ::= { upsBattery 4 } 
  131.  
  132.    upsBatteryVoltage OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 Volt DC"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The magnitude of the present battery voltage."        ::= { upsBattery 5 } 
  133.  
  134.    upsBatteryCurrent OBJECT-TYPE        SYNTAX     Integer32        UNITS      "0.1 Amp DC"        MAX-ACCESS read-only 
  135.  
  136.  
  137.  
  138. Case                                                            [Page 6] 
  139.  RFC 1628                        UPS MIB                         May 1994 
  140.  
  141.         STATUS     current        DESCRIPTION                "The present battery current."        ::= { upsBattery 6 } 
  142.  
  143.    upsBatteryTemperature OBJECT-TYPE        SYNTAX     Integer32        UNITS      "degrees Centigrade"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The ambient temperature at or near the UPS Battery                casing."        ::= { upsBattery 7 } 
  144.  
  145.     --    -- Input Group    -- 
  146.  
  147.    upsInput              OBJECT IDENTIFIER ::= { upsObjects 3 } 
  148.  
  149.    upsInputLineBads OBJECT-TYPE        SYNTAX     Counter32        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "A count of the number of times the input entered an                out-of-tolerance condition as defined by the                manufacturer.  This count is incremented by one each                time the input transitions from zero out-of-tolerance                lines to one or more input lines out-of-tolerance."        ::= { upsInput 1 } 
  150.  
  151.     upsInputNumLines OBJECT-TYPE        SYNTAX     NonNegativeInteger        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The number of input lines utilized in this device.                This variable indicates the number of rows in the                input table."        ::= { upsInput 2 } 
  152.  
  153.    upsInputTable OBJECT-TYPE        SYNTAX     SEQUENCE OF UpsInputEntry        MAX-ACCESS not-accessible 
  154.  
  155.  
  156.  
  157. Case                                                            [Page 7] 
  158.  RFC 1628                        UPS MIB                         May 1994 
  159.  
  160.         STATUS     current        DESCRIPTION                "A list of input table entries.  The number of entries                is given by the value of upsInputNumLines."        ::= { upsInput 3 } 
  161.  
  162.    upsInputEntry OBJECT-TYPE        SYNTAX     UpsInputEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "An entry containing information applicable to a                particular input line."        INDEX { upsInputLineIndex }        ::= { upsInputTable 1 } 
  163.  
  164.    UpsInputEntry ::= SEQUENCE {        upsInputLineIndex   PositiveInteger,        upsInputFrequency   NonNegativeInteger,        upsInputVoltage     NonNegativeInteger,        upsInputCurrent     NonNegativeInteger,        upsInputTruePower   NonNegativeInteger    }     upsInputLineIndex OBJECT-TYPE        SYNTAX     PositiveInteger        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "The input line identifier."        ::= { upsInputEntry 1 } 
  165.  
  166.    upsInputFrequency OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 Hertz"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present input frequency."        ::= { upsInputEntry 2 } 
  167.  
  168.    upsInputVoltage OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The magnitude of the present input voltage." 
  169.  
  170.  
  171.  
  172. Case                                                            [Page 8] 
  173.  RFC 1628                        UPS MIB                         May 1994 
  174.  
  175.         ::= { upsInputEntry 3 } 
  176.  
  177.    upsInputCurrent OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 RMS Amp"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The magnitude of the present input current."        ::= { upsInputEntry 4 } 
  178.  
  179.    upsInputTruePower OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "Watts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The magnitude of the present input true power."        ::= { upsInputEntry 5 } 
  180.  
  181.     --    -- The Output group.    -- 
  182.  
  183.    upsOutput             OBJECT IDENTIFIER ::= { upsObjects 4 } 
  184.  
  185.    upsOutputSource OBJECT-TYPE        SYNTAX     INTEGER {            other(1),            none(2),            normal(3),            bypass(4),            battery(5),            booster(6),            reducer(7)        }        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present source of output power.  The enumeration                none(2) indicates that there is no source of output                power (and therefore no output power), for example,                the system has opened the output breaker."        ::= { upsOutput 1 } 
  186.  
  187.    upsOutputFrequency OBJECT-TYPE        SYNTAX     NonNegativeInteger 
  188.  
  189.  
  190.  
  191. Case                                                            [Page 9] 
  192.  RFC 1628                        UPS MIB                         May 1994 
  193.  
  194.         UNITS      "0.1 Hertz"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present output frequency."        ::= { upsOutput 2 } 
  195.  
  196.    upsOutputNumLines OBJECT-TYPE        SYNTAX     NonNegativeInteger        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The number of output lines utilized in this device.                This variable indicates the number of rows in the                output table."        ::= { upsOutput 3 } 
  197.  
  198.    upsOutputTable OBJECT-TYPE        SYNTAX     SEQUENCE OF UpsOutputEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "A list of output table entries.  The number of                entries is given by the value of upsOutputNumLines."        ::= { upsOutput 4 } 
  199.  
  200.    upsOutputEntry OBJECT-TYPE        SYNTAX     UpsOutputEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "An entry containing information applicable to a                particular output line."        INDEX { upsOutputLineIndex }        ::= { upsOutputTable 1 } 
  201.  
  202.    UpsOutputEntry ::= SEQUENCE {        upsOutputLineIndex   PositiveInteger,        upsOutputVoltage     NonNegativeInteger,        upsOutputCurrent     NonNegativeInteger,        upsOutputPower       NonNegativeInteger,        upsOutputPercentLoad INTEGER    } 
  203.  
  204.    upsOutputLineIndex OBJECT-TYPE        SYNTAX     PositiveInteger        MAX-ACCESS not-accessible        STATUS     current 
  205.  
  206.  
  207.  
  208. Case                                                           [Page 10] 
  209.  RFC 1628                        UPS MIB                         May 1994 
  210.  
  211.         DESCRIPTION                "The output line identifier."        ::= { upsOutputEntry 1 } 
  212.  
  213.    upsOutputVoltage OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present output voltage."        ::= { upsOutputEntry 2 } 
  214.  
  215.    upsOutputCurrent OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 RMS Amp"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present output current."        ::= { upsOutputEntry 3 } 
  216.  
  217.    upsOutputPower OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "Watts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present output true power."        ::= { upsOutputEntry 4 } 
  218.  
  219.    upsOutputPercentLoad OBJECT-TYPE        SYNTAX     INTEGER (0..200)        UNITS      "percent"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The percentage of the UPS power capacity presently                being used on this output line, i.e., the greater of                the percent load of true power capacity and the                percent load of VA."        ::= { upsOutputEntry 5 } 
  220.  
  221.  
  222.  
  223.  
  224.  
  225.  
  226.  
  227.  
  228.  
  229. Case                                                           [Page 11] 
  230.  RFC 1628                        UPS MIB                         May 1994 
  231.  
  232.     --    -- The Bypass group.    -- 
  233.  
  234.    upsBypass             OBJECT IDENTIFIER ::= { upsObjects 5 } 
  235.  
  236.    upsBypassFrequency OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 Hertz"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present bypass frequency."        ::= { upsBypass 1 } 
  237.  
  238.    upsBypassNumLines OBJECT-TYPE        SYNTAX     NonNegativeInteger        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The number of bypass lines utilized in this device.                This entry indicates the number of rows in the bypass                table."        ::= { upsBypass 2 } 
  239.  
  240.    upsBypassTable OBJECT-TYPE        SYNTAX     SEQUENCE OF UpsBypassEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "A list of bypass table entries.  The number of                entries is given by the value of upsBypassNumLines."        ::= { upsBypass 3 } 
  241.  
  242.    upsBypassEntry OBJECT-TYPE        SYNTAX     UpsBypassEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "An entry containing information applicable to a                particular bypass input."        INDEX { upsBypassLineIndex }        ::= { upsBypassTable 1 } 
  243.  
  244.    UpsBypassEntry ::= SEQUENCE {        upsBypassLineIndex  PositiveInteger,        upsBypassVoltage    NonNegativeInteger,        upsBypassCurrent    NonNegativeInteger, 
  245.  
  246.  
  247.  
  248. Case                                                           [Page 12] 
  249.  RFC 1628                        UPS MIB                         May 1994 
  250.  
  251.         upsBypassPower      NonNegativeInteger    } 
  252.  
  253.    upsBypassLineIndex OBJECT-TYPE        SYNTAX     PositiveInteger        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "The bypass line identifier."        ::= { upsBypassEntry 1 } 
  254.  
  255.    upsBypassVoltage OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present bypass voltage."        ::= { upsBypassEntry 2 } 
  256.  
  257.    upsBypassCurrent OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 RMS Amp"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present bypass current."        ::= { upsBypassEntry 3 } 
  258.  
  259.    upsBypassPower OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "Watts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The present true power conveyed by the bypass."        ::= { upsBypassEntry 4 } 
  260.  
  261.     --    -- The Alarm group.    -- 
  262.  
  263.    upsAlarm              OBJECT IDENTIFIER ::= { upsObjects 6 } 
  264.  
  265.    upsAlarmsPresent OBJECT-TYPE        SYNTAX     Gauge32        MAX-ACCESS read-only 
  266.  
  267.  
  268.  
  269. Case                                                           [Page 13] 
  270.  RFC 1628                        UPS MIB                         May 1994 
  271.  
  272.         STATUS     current        DESCRIPTION                "The present number of active alarm conditions."        ::= { upsAlarm 1 } 
  273.  
  274.    upsAlarmTable OBJECT-TYPE        SYNTAX     SEQUENCE OF UpsAlarmEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "A list of alarm table entries.  The table contains                zero, one, or many rows at any moment, depending upon                the number of alarm conditions in effect.  The table                is initially empty at agent startup.  The agent                creates a row in the table each time a condition is                detected and deletes that row when that condition no                longer pertains.  The agent creates the first row with                upsAlarmId equal to 1, and increments the value of                upsAlarmId each time a new row is created, wrapping to                the first free value greater than or equal to 1 when                the maximum value of upsAlarmId would otherwise be                exceeded.  Consequently, after multiple operations,                the table may become sparse, e.g., containing entries                for rows 95, 100, 101, and 203 and the entries should                not be assumed to be in chronological order because                upsAlarmId might have wrapped. 
  275.  
  276.                Alarms are named by an AutonomousType (OBJECT                IDENTIFIER), upsAlarmDescr, to allow a single table to                reflect well known alarms plus alarms defined by a                particular implementation, i.e., as documented in the                private enterprise MIB definition for the device.  No                two rows will have the same value of upsAlarmDescr,                since alarms define conditions.  In order to meet this                requirement, care should be taken in the definition of                alarm conditions to insure that a system cannot enter                the same condition multiple times simultaneously. 
  277.  
  278.                The number of rows in the table at any given time is                reflected by the value of upsAlarmsPresent."        ::= { upsAlarm 2 } 
  279.  
  280.    upsAlarmEntry OBJECT-TYPE        SYNTAX     UpsAlarmEntry        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "An entry containing information applicable to a 
  281.  
  282.  
  283.  
  284. Case                                                           [Page 14] 
  285.  RFC 1628                        UPS MIB                         May 1994 
  286.  
  287.                 particular alarm."        INDEX { upsAlarmId }        ::= { upsAlarmTable 1 } 
  288.  
  289.    UpsAlarmEntry ::= SEQUENCE {        upsAlarmId          PositiveInteger,        upsAlarmDescr       AutonomousType,        upsAlarmTime        TimeStamp    } 
  290.  
  291.    upsAlarmId OBJECT-TYPE        SYNTAX     PositiveInteger        MAX-ACCESS not-accessible        STATUS     current        DESCRIPTION                "A unique identifier for an alarm condition.  This                value must remain constant."        ::= { upsAlarmEntry 1 } 
  292.  
  293.    upsAlarmDescr OBJECT-TYPE        SYNTAX     AutonomousType        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "A reference to an alarm description object.  The                object referenced should not be accessible, but rather                be used to provide a unique description of the alarm                condition."        ::= { upsAlarmEntry 2 } 
  294.  
  295.    upsAlarmTime OBJECT-TYPE        SYNTAX     TimeStamp        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The value of sysUpTime when the alarm condition was                detected.  If the alarm condition was detected at the                time of agent startup and presumably existed before                agent startup, the value of upsAlarmTime shall equal                0."        ::= { upsAlarmEntry 3 } 
  296.  
  297.     --    -- Well known alarm conditions.    -- 
  298.  
  299.    upsWellKnownAlarms    OBJECT IDENTIFIER ::= { upsAlarm 3 } 
  300.  
  301.  
  302.  
  303. Case                                                           [Page 15] 
  304.  RFC 1628                        UPS MIB                         May 1994 
  305.  
  306.     upsAlarmBatteryBad OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "One or more batteries have been determined to require                replacement."        ::= { upsWellKnownAlarms  1 } 
  307.  
  308.    upsAlarmOnBattery OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The UPS is drawing power from the batteries."        ::= { upsWellKnownAlarms  2 } 
  309.  
  310.    upsAlarmLowBattery OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The remaining battery run-time is less than or equal                to upsConfigLowBattTime."        ::= { upsWellKnownAlarms  3 } 
  311.  
  312.     upsAlarmDepletedBattery OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The UPS will be unable to sustain the present load                when and if the utility power is lost."        ::= { upsWellKnownAlarms  4 } 
  313.  
  314.    upsAlarmTempBad OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "A temperature is out of tolerance."        ::= { upsWellKnownAlarms  5 } 
  315.  
  316.    upsAlarmInputBad OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "An input condition is out of tolerance."        ::= { upsWellKnownAlarms  6 } 
  317.  
  318.    upsAlarmOutputBad OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "An output condition (other than OutputOverload) is                out of tolerance."        ::= { upsWellKnownAlarms  7 } 
  319.  
  320.    upsAlarmOutputOverload OBJECT-IDENTITY 
  321.  
  322.  
  323.  
  324. Case                                                           [Page 16] 
  325.  RFC 1628                        UPS MIB                         May 1994 
  326.  
  327.         STATUS     current        DESCRIPTION                "The output load exceeds the UPS output capacity."        ::= { upsWellKnownAlarms  8 } 
  328.  
  329.    upsAlarmOnBypass OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The Bypass is presently engaged on the UPS."        ::= { upsWellKnownAlarms  9 } 
  330.  
  331.    upsAlarmBypassBad OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The Bypass is out of tolerance."        ::= { upsWellKnownAlarms 10 } 
  332.  
  333.    upsAlarmOutputOffAsRequested OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The UPS has shutdown as requested, i.e., the output                is off."        ::= { upsWellKnownAlarms 11 } 
  334.  
  335.    upsAlarmUpsOffAsRequested OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The entire UPS has shutdown as commanded."        ::= { upsWellKnownAlarms 12 } 
  336.  
  337.    upsAlarmChargerFailed OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "An uncorrected problem has been detected within the                UPS charger subsystem."        ::= { upsWellKnownAlarms 13 } 
  338.  
  339.    upsAlarmUpsOutputOff OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The output of the UPS is in the off state."        ::= { upsWellKnownAlarms 14 } 
  340.  
  341.    upsAlarmUpsSystemOff OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The UPS system is in the off state."        ::= { upsWellKnownAlarms 15 } 
  342.  
  343.  
  344.  
  345. Case                                                           [Page 17] 
  346.  RFC 1628                        UPS MIB                         May 1994 
  347.  
  348.     upsAlarmFanFailure OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The failure of one or more fans in the UPS has been                detected."        ::= { upsWellKnownAlarms 16 } 
  349.  
  350.    upsAlarmFuseFailure OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The failure of one or more fuses has been detected."        ::= { upsWellKnownAlarms 17 } 
  351.  
  352.    upsAlarmGeneralFault OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "A general fault in the UPS has been detected."        ::= { upsWellKnownAlarms 18 } 
  353.  
  354.    upsAlarmDiagnosticTestFailed OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The result of the last diagnostic test indicates a                failure."        ::= { upsWellKnownAlarms 19 } 
  355.  
  356.    upsAlarmCommunicationsLost OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "A problem has been encountered in the communications                between the agent and the UPS."        ::= { upsWellKnownAlarms 20 } 
  357.  
  358.    upsAlarmAwaitingPower OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The UPS output is off and the UPS is awaiting the                return of input power."        ::= { upsWellKnownAlarms 21 } 
  359.  
  360.    upsAlarmShutdownPending OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "A upsShutdownAfterDelay countdown is underway."        ::= { upsWellKnownAlarms 22 } 
  361.  
  362.    upsAlarmShutdownImminent OBJECT-IDENTITY        STATUS     current 
  363.  
  364.  
  365.  
  366. Case                                                           [Page 18] 
  367.  RFC 1628                        UPS MIB                         May 1994 
  368.  
  369.         DESCRIPTION                "The UPS will turn off power to the load in less than                5 seconds; this may be either a timed shutdown or a                low battery shutdown."        ::= { upsWellKnownAlarms 23 } 
  370.  
  371.    upsAlarmTestInProgress OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "A test is in progress, as initiated and indicated by                the Test Group.  Tests initiated via other                implementation-specific mechanisms can indicate the                presence of the testing in the alarm table, if                desired, via a OBJECT-IDENTITY macro in the MIB                document specific to that implementation and are                outside the scope of this OBJECT-IDENTITY."        ::= { upsWellKnownAlarms 24 } 
  372.  
  373.     --    -- The Test Group    -- 
  374.  
  375.    upsTest               OBJECT IDENTIFIER ::= { upsObjects 7 } 
  376.  
  377.    upsTestId OBJECT-TYPE        SYNTAX     OBJECT IDENTIFIER        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The test is named by an OBJECT IDENTIFIER which                allows a standard mechanism for the initiation of                tests, including the well known tests identified in                this document as well as those introduced by a                particular implementation, i.e., as documented in the                private enterprise MIB definition for the device. 
  378.  
  379.                Setting this variable initiates the named test. Sets                to this variable require the presence of                upsTestSpinLock in the same SNMP message. 
  380.  
  381.                The set request will be rejected with an appropriate                error message if the requested test cannot be                performed, including attempts to start a test when                another test is already in progress.  The status of                the current or last test is maintained in                upsTestResultsSummary. Tests in progress may be                aborted by setting the upsTestId variable to 
  382.  
  383.  
  384.  
  385. Case                                                           [Page 19] 
  386.  RFC 1628                        UPS MIB                         May 1994 
  387.  
  388.                 upsTestAbortTestInProgress. 
  389.  
  390.                Read operations return the value of the name of the                test in progress if a test is in progress or the name                of the last test performed if no test is in progress,                unless no test has been run, in which case the well                known value upsTestNoTestsInitiated is returned."        ::= { upsTest 1 } 
  391.  
  392.    -- see [6] for more information on the semantics of objects with    -- syntax of TestAndIncr 
  393.  
  394.    upsTestSpinLock OBJECT-TYPE        SYNTAX     TestAndIncr        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "A spin lock on the test subsystem.  The spinlock is                used as follows. 
  395.  
  396.                Before starting a test, a manager-station should make                sure that a test is not in progress as follows: 
  397.  
  398.                    try_again:                      get (upsTestSpinLock)                      while (upsTestResultsSummary == inProgress) {                        /* loop while a test is running for another                manager */                        short delay                        get (upsTestSpinLock)                      }                      lock_value = upsTestSpinLock                      /* no test in progress, start the test */                      set (upsTestSpinLock = lock_value, upsTestId =                requested_test)                      if (error_index == 1) { /* (upsTestSpinLock                failed) */                        /* if problem is not access control, then                            some other manager slipped in ahead of us                */                        goto try_again                      }                      if (error_index == 2) { /* (upsTestId) */                        /* cannot perform the test */                        give up                      }                      /* test started ok */                      /* wait for test completion by polling 
  399.  
  400.  
  401.  
  402. Case                                                           [Page 20] 
  403.  RFC 1628                        UPS MIB                         May 1994 
  404.  
  405.                 upsTestResultsSummary */                      get (upsTestSpinLock, upsTestResultsSummary,                upsTestResultsDetail)                      while (upsTestResultsSummary == inProgress) {                        short delay                        get (upsTestSpinLock, upsTestResultsSummary,                upsTestResultsDetail)                      }                      /* when test completes, retrieve any additional                test results */                      /* if upsTestSpinLock == lock_value + 1, then                these are our test */                      /* results (as opposed to another manager's */                      The initial value of upsTestSpinLock at agent                initialization shall                      be 1."        ::= { upsTest 2 } 
  406.  
  407.    upsTestResultsSummary OBJECT-TYPE        SYNTAX     INTEGER {            donePass(1),            doneWarning(2),            doneError(3),            aborted(4),            inProgress(5),            noTestsInitiated(6)        }        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The results of the current or last UPS diagnostics                test performed.  The values for donePass(1),                doneWarning(2), and doneError(3) indicate that the                test completed either successfully, with a warning, or                with an error, respectively.  The value aborted(4) is                returned for tests which are aborted by setting the                value of upsTestId to upsTestAbortTestInProgress.                Tests which have not yet concluded are indicated by                inProgress(5).  The value noTestsInitiated(6)                indicates that no previous test results are available,                such as is the case when no tests have been run since                the last reinitialization of the network management                subsystem and the system has no provision for non-                volatile storage of test results."        ::= { upsTest 3 } 
  408.  
  409.    upsTestResultsDetail OBJECT-TYPE        SYNTAX     DisplayString (SIZE (0..255)) 
  410.  
  411.  
  412.  
  413. Case                                                           [Page 21] 
  414.  RFC 1628                        UPS MIB                         May 1994 
  415.  
  416.         MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "Additional information about upsTestResultsSummary.                If no additional information available, a zero length                string is returned."        ::= { upsTest 4 } 
  417.  
  418.    upsTestStartTime OBJECT-TYPE        SYNTAX     TimeStamp        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The value of sysUpTime at the time the test in                progress was initiated, or, if no test is in progress,                the time the previous test was initiated.  If the                value of upsTestResultsSummary is noTestsInitiated(6),                upsTestStartTime has the value 0."        ::= { upsTest 5 } 
  419.  
  420.    upsTestElapsedTime OBJECT-TYPE        SYNTAX     TimeInterval        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The amount of time, in TimeTicks, since the test in                progress was initiated, or, if no test is in progress,                the previous test took to complete.  If the value of                upsTestResultsSummary is noTestsInitiated(6),                upsTestElapsedTime has the value 0."        ::= { upsTest 6 } 
  421.  
  422.    --    -- Well known tests.    -- 
  423.  
  424.    upsWellKnownTests     OBJECT IDENTIFIER ::= { upsTest 7 } 
  425.  
  426.     upsTestNoTestsInitiated OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "No tests have been initiated and no test is in                progress."        ::= { upsWellKnownTests  1 } 
  427.  
  428.    upsTestAbortTestInProgress OBJECT-IDENTITY        STATUS     current 
  429.  
  430.  
  431.  
  432. Case                                                           [Page 22] 
  433.  RFC 1628                        UPS MIB                         May 1994 
  434.  
  435.         DESCRIPTION                "The test in progress is to be aborted / the test in                progress was aborted."        ::= { upsWellKnownTests  2 } 
  436.  
  437.    upsTestGeneralSystemsTest OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The manufacturer's standard test of UPS device                systems."        ::= { upsWellKnownTests  3 } 
  438.  
  439.    upsTestQuickBatteryTest OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "A test that is sufficient to determine if the battery                needs replacement."        ::= { upsWellKnownTests  4 } 
  440.  
  441.    upsTestDeepBatteryCalibration OBJECT-IDENTITY        STATUS     current        DESCRIPTION                "The system is placed on battery to a discharge level,                set by the manufacturer, sufficient to determine                battery replacement and battery run-time with a high                degree of confidence.  WARNING:  this test will leave                the battery in a low charge state and will require                time for recharging to a level sufficient to provide                normal battery duration for the protected load."        ::= { upsWellKnownTests  5 } 
  442.  
  443.     --    -- The Control group.    -- 
  444.  
  445.    upsControl            OBJECT IDENTIFIER ::= { upsObjects 8 } 
  446.  
  447.    upsShutdownType OBJECT-TYPE        SYNTAX     INTEGER {            output(1),            system(2)        }        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "This object determines the nature of the action to be                taken at the time when the countdown of the 
  448.  
  449.  
  450.  
  451. Case                                                           [Page 23] 
  452.  RFC 1628                        UPS MIB                         May 1994 
  453.  
  454.                 upsShutdownAfterDelay and upsRebootWithDuration                objects reaches zero. 
  455.  
  456.                Setting this object to output(1) indicates that                shutdown requests should cause only the output of the                UPS to turn off.  Setting this object to system(2)                indicates that shutdown requests will cause the entire                UPS system to turn off."        ::= { upsControl 1 } 
  457.  
  458.    upsShutdownAfterDelay OBJECT-TYPE        SYNTAX     INTEGER (-1..2147483648)        UNITS      "seconds"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "Setting this object will shutdown (i.e., turn off)                either the UPS output or the UPS system (as determined                by the value of upsShutdownType at the time of                shutdown) after the indicated number of seconds, or                less if the UPS batteries become depleted. Setting                this object to 0 will cause the shutdown to occur                immediately.  Setting this object to -1 will abort the                countdown.  If the system is already in the desired                state at the time the countdown reaches 0, then                nothing will happen.  That is, there is no additional                action at that time if upsShutdownType = system and                the system is already off.  Similarly, there is no                additional action at that time if upsShutdownType =                output and the output is already off.  When read,                upsShutdownAfterDelay will return the number of                seconds remaining until shutdown, or -1 if no shutdown                countdown is in effect.  On some systems, if the agent                is restarted while a shutdown countdown is in effect,                the countdown may be aborted.  Sets to this object                override any upsShutdownAfterDelay already in effect."        ::= { upsControl 2 } 
  459.  
  460.    upsStartupAfterDelay OBJECT-TYPE        SYNTAX     INTEGER (-1..2147483648)        UNITS      "seconds"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "Setting this object will start the output after the                indicated number of seconds, including starting the                UPS, if necessary.  Setting this object to 0 will                cause the startup to occur immediately.  Setting this 
  461.  
  462.  
  463.  
  464. Case                                                           [Page 24] 
  465.  RFC 1628                        UPS MIB                         May 1994 
  466.  
  467.                 object to -1 will abort the countdown.  If the output                is already on at the time the countdown reaches 0,                then nothing will happen.  Sets to this object                override the effect of any upsStartupAfterDelay                countdown or upsRebootWithDuration countdown in                progress.  When read, upsStartupAfterDelay will return                the number of seconds until startup, or -1 if no                startup countdown is in effect.  If the countdown                expires during a utility failure, the startup shall                not occur until the utility power is restored.  On                some systems, if the agent is restarted while a                startup countdown is in effect, the countdown is                aborted."        ::= { upsControl 3 } 
  468.  
  469.    upsRebootWithDuration OBJECT-TYPE        SYNTAX     INTEGER (-1..300)        UNITS      "seconds"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "Setting this object will immediately shutdown (i.e.,                turn off) either the UPS output or the UPS system (as                determined by the value of upsShutdownType at the time                of shutdown) for a period equal to the indicated                number of seconds, after which time the output will be                started, including starting the UPS, if necessary.  If                the number of seconds required to perform the request                is greater than the requested duration, then the                requested shutdown and startup cycle shall be                performed in the minimum time possible, but in no case                shall this require more than the requested duration                plus 60 seconds.  When read, upsRebootWithDuration                shall return the number of seconds remaining in the                countdown, or -1 if no countdown is in progress.  If                the startup should occur during a utility failure, the                startup shall not occur until the utility power is                restored."        ::= { upsControl 4 } 
  470.  
  471.    upsAutoRestart OBJECT-TYPE        SYNTAX     INTEGER {            on(1),            off(2)        }        MAX-ACCESS read-write        STATUS     current        DESCRIPTION 
  472.  
  473.  
  474.  
  475. Case                                                           [Page 25] 
  476.  RFC 1628                        UPS MIB                         May 1994 
  477.  
  478.                 "Setting this object to 'on' will cause the UPS system                to restart after a shutdown if the shutdown occurred                during a power loss as a result of either a                upsShutdownAfterDelay or an internal battery depleted                condition.  Setting this object to 'off' will prevent                the UPS system from restarting after a shutdown until                an operator manually or remotely explicitly restarts                it.  If the UPS is in a startup or reboot countdown,                then the UPS will not restart until that delay has                been satisfied."        ::= { upsControl 5 } 
  479.  
  480.     --    -- The Configuration group.    -- 
  481.  
  482.    upsConfig             OBJECT IDENTIFIER ::= { upsObjects 9 } 
  483.  
  484.    upsConfigInputVoltage OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The magnitude of the nominal input voltage.  On those                systems which support read-write access to this                object, if there is an attempt to set this variable to                a value that is not supported, the request must be                rejected and the agent shall respond with an                appropriate error message, i.e., badValue for SNMPv1,                or inconsistentValue for SNMPv2."        ::= { upsConfig 1 } 
  485.  
  486.    upsConfigInputFreq OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 Hertz"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The nominal input frequency.  On those systems which                support read-write access to this object, if there is                an attempt to set this variable to a value that is not                supported, the request must be rejected and the agent                shall respond with an appropriate error message, i.e.,                badValue for SNMPv1, or inconsistentValue for SNMPv2."        ::= { upsConfig 2 } 
  487.  
  488.  
  489.  
  490.  Case                                                           [Page 26] 
  491.  RFC 1628                        UPS MIB                         May 1994 
  492.  
  493.     upsConfigOutputVoltage OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The magnitude of the nominal output voltage.  On                those systems which support read-write access to this                object, if there is an attempt to set this variable to                a value that is not supported, the request must be                rejected and the agent shall respond with an                appropriate error message, i.e., badValue for SNMPv1,                or inconsistentValue for SNMPv2."        ::= { upsConfig 3 } 
  494.  
  495.    upsConfigOutputFreq OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "0.1 Hertz"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The nominal output frequency.  On those systems which                support read-write access to this object, if there is                an attempt to set this variable to a value that is not                supported, the request must be rejected and the agent                shall respond with an appropriate error message, i.e.,                badValue for SNMPv1, or inconsistentValue for SNMPv2."        ::= { upsConfig 4 } 
  496.  
  497.    upsConfigOutputVA OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "Volt-Amps"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The magnitude of the nominal Volt-Amp rating."        ::= { upsConfig 5 } 
  498.  
  499.    upsConfigOutputPower OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "Watts"        MAX-ACCESS read-only        STATUS     current        DESCRIPTION                "The magnitude of the nominal true power rating."        ::= { upsConfig 6 } 
  500.  
  501.    upsConfigLowBattTime OBJECT-TYPE 
  502.  
  503.  
  504.  
  505. Case                                                           [Page 27] 
  506.  RFC 1628                        UPS MIB                         May 1994 
  507.  
  508.         SYNTAX     NonNegativeInteger        UNITS      "minutes"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The value of upsEstimatedMinutesRemaining at which a                lowBattery condition is declared.  For agents which                support only discrete (discontinuous) values, then the                agent shall round up to the next supported value.  If                the requested value is larger than the largest                supported value, then the largest supported value                shall be selected."        ::= { upsConfig 7 } 
  509.  
  510.    upsConfigAudibleStatus OBJECT-TYPE        SYNTAX     INTEGER {            disabled(1),            enabled(2),            muted(3)        }        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The requested state of the audible alarm.  When in                the disabled state, the audible alarm should never                sound.  The enabled state is self-describing.  Setting                this object to muted(3) when the audible alarm is                sounding shall temporarily silence the alarm.  It will                remain muted until it would normally stop sounding and                the value returned for read operations during this                period shall equal muted(3).  At the end of this                period, the value shall revert to enabled(2).  Writes                of the value muted(3) when the audible alarm is not                sounding shall be accepted but otherwise shall have no                effect."        ::= { upsConfig 8 } 
  511.  
  512.    upsConfigLowVoltageTransferPoint OBJECT-TYPE        SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The minimum input line voltage allowed before the UPS                system transfers to battery backup."        ::= { upsConfig 9 } 
  513.  
  514.    upsConfigHighVoltageTransferPoint OBJECT-TYPE 
  515.  
  516.  
  517.  
  518. Case                                                           [Page 28] 
  519.  RFC 1628                        UPS MIB                         May 1994 
  520.  
  521.         SYNTAX     NonNegativeInteger        UNITS      "RMS Volts"        MAX-ACCESS read-write        STATUS     current        DESCRIPTION                "The maximum line voltage allowed before the UPS                system transfers to battery backup."        ::= { upsConfig 10 } 
  522.  
  523.     --    -- notifications, i.e., traps    --    upsTraps              OBJECT IDENTIFIER ::= { upsMIB 2 } 
  524.  
  525.    -- This section defines the well-known notifications sent by    -- UPS agents.    -- Care must be taken to insure that no particular notification    -- is sent to a single receiving entity more often than once    -- every five seconds. 
  526.  
  527.    upsTrapOnBattery NOTIFICATION-TYPE        OBJECTS { upsEstimatedMinutesRemaining, upsSecondsOnBattery,                  upsConfigLowBattTime }        STATUS  current        DESCRIPTION                "The UPS is operating on battery power.  This trap is                persistent and is resent at one minute intervals until                the UPS either turns off or is no longer running on                battery."      ::= { upsTraps 1 } 
  528.  
  529.    upsTrapTestCompleted NOTIFICATION-TYPE        OBJECTS { upsTestId, upsTestSpinLock,                  upsTestResultsSummary, upsTestResultsDetail,                  upsTestStartTime, upsTestElapsedTime }        STATUS  current        DESCRIPTION                "This trap is sent upon completion of a UPS diagnostic                test."      ::= { upsTraps 2 } 
  530.  
  531.    upsTrapAlarmEntryAdded NOTIFICATION-TYPE        OBJECTS { upsAlarmId, upsAlarmDescr }        STATUS  current        DESCRIPTION                "This trap is sent each time an alarm is inserted into                to the alarm table.  It is sent on the insertion of 
  532.  
  533.  
  534.  
  535. Case                                                           [Page 29] 
  536.  RFC 1628                        UPS MIB                         May 1994 
  537.  
  538.                 all alarms except for upsAlarmOnBattery and                upsAlarmTestInProgress."      ::= { upsTraps 3 } 
  539.  
  540.    upsTrapAlarmEntryRemoved NOTIFICATION-TYPE        OBJECTS { upsAlarmId, upsAlarmDescr }        STATUS  current        DESCRIPTION                "This trap is sent each time an alarm is removed from                the alarm table.  It is sent on the removal of all                alarms except for upsAlarmTestInProgress."      ::= { upsTraps 4 } 
  541.  
  542.     --    -- conformance information    --    upsConformance        OBJECT IDENTIFIER ::= { upsMIB 3 } 
  543.  
  544.    upsCompliances        OBJECT IDENTIFIER ::= { upsConformance 1 } 
  545.  
  546.     --    -- compliance statements    -- 
  547.  
  548.    upsSubsetCompliance MODULE-COMPLIANCE        STATUS     current        DESCRIPTION 
  549.  
  550.                "The compliance statement for UPSs that only support                the two-contact communication protocol."        MODULE -- this module            MANDATORY-GROUPS  { upsSubsetIdentGroup,                      upsSubsetBatteryGroup, upsSubsetInputGroup,                      upsSubsetOutputGroup, upsSubsetAlarmGroup,                      upsSubsetControlGroup, upsSubsetConfigGroup } 
  551.  
  552.        OBJECT     upsBatteryStatus        SYNTAX     INTEGER {            batteryNormal(2),            batteryLow(3)        }        DESCRIPTION                "Support of the values unknown(1) and                batteryDepleted(4) is not required." 
  553.  
  554.        OBJECT     upsAlarmDescr 
  555.  
  556.  
  557.  
  558. Case                                                           [Page 30] 
  559.  RFC 1628                        UPS MIB                         May 1994 
  560.  
  561.         DESCRIPTION                "Support of all `well known' alarm types is not                required.  The well known alarm types which must be                supported are: upsAlarmOnBattery, upsAlarmLowBattery,                upsAlarmInputBad, upsAlarmUpsOutputOff,                upsAlarmUpsSystemOff, and upsAlarmTestInProgress." 
  562.  
  563.        OBJECT     upsOutputSource        SYNTAX     INTEGER {            normal(2),            battery(4)        }        DESCRIPTION                "Support of the values other(1), none(2), bypass(4),                booster(6) and reducer(7) is not required." 
  564.  
  565.        OBJECT     upsShutdownType        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required, i.e., compliant                systems need not support more than one shutdown type." 
  566.  
  567.        OBJECT     upsAutoRestart        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required, i.e., compliant                systems need not support more than one restart type." 
  568.  
  569.        OBJECT     upsConfigInputVoltage        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  570.  
  571.        OBJECT     upsConfigInputFreq        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  572.  
  573.        OBJECT     upsConfigOutputVoltage        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  574.  
  575.        OBJECT     upsConfigOutputFreq        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  576.  
  577.  
  578.  
  579.  Case                                                           [Page 31] 
  580.  RFC 1628                        UPS MIB                         May 1994 
  581.  
  582.         ::= { upsCompliances 1 } 
  583.  
  584.    upsBasicCompliance MODULE-COMPLIANCE        STATUS     current        DESCRIPTION 
  585.  
  586.                "The compliance statement for UPSs that support                full-featured functions, such as control."        MODULE -- this module            MANDATORY-GROUPS { upsBasicIdentGroup,                      upsBasicBatteryGroup, upsBasicInputGroup,                      upsBasicOutputGroup, upsBasicAlarmGroup,                      upsBasicTestGroup, upsBasicControlGroup,                      upsBasicConfigGroup } 
  587.  
  588.         OBJECT     upsAlarmDescr        DESCRIPTION                "Support of all `well known' alarm types is not                required.  The well known alarm types which must be                supported are: upsAlarmOnBattery, upsAlarmLowBattery,                upsAlarmDepletedBattery, upsAlarmTempBad,                upsAlarmInputBad, upsAlarmOutputOverload,                upsAlarmOnBypass, upsAlarmBypassBad,                upsAlarmOutputOffAsRequested,                upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,                upsAlarmUpsSystemOff, upsAlarmGeneralFault,                upsAlarmDiagnosticTestFailed,                upsAlarmCommunicationsLost, upsAlarmShutdownPending,                and upsAlarmTestInProgress." 
  589.  
  590.        OBJECT     upsTestId        DESCRIPTION                "Support of all `well known' test types is not                required.  If no tests are supported, then the only                well known test type which must be supported is                upsTestNoTestsInitiated." 
  591.  
  592.        OBJECT     upsOutputSource        SYNTAX     INTEGER {            normal(2),            battery(4)        }        DESCRIPTION                "Support of the values other(1), none(2), bypass(4),                booster(6) and reducer(7) is not required." 
  593.  
  594.            GROUP upsBasicBypassGroup 
  595.  
  596.  
  597.  
  598. Case                                                           [Page 32] 
  599.  RFC 1628                        UPS MIB                         May 1994 
  600.  
  601.             DESCRIPTION                "The upsBasicBypassGroup is only required for UPSs                that have a Bypass present."        OBJECT     upsShutdownType        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required, i.e., compliant                systems need not support more than one shutdown type." 
  602.  
  603.        OBJECT     upsAutoRestart        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required, i.e., compliant                systems need not support more than one restart type." 
  604.  
  605.        OBJECT     upsConfigInputVoltage        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  606.  
  607.        OBJECT     upsConfigInputFreq        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  608.  
  609.        OBJECT     upsConfigOutputVoltage        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  610.  
  611.        OBJECT     upsConfigOutputFreq        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  612.  
  613.        OBJECT     upsConfigLowBattTime        DESCRIPTION                "Implementation of all possible values may be onerous                for some systems.  Consequently, not all possible                values must be supported.  However, at least two                different manufacturer-selected values must be                supported." 
  614.  
  615.        ::= { upsCompliances 2 } 
  616.  
  617.    upsFullCompliance MODULE-COMPLIANCE        STATUS     current        DESCRIPTION 
  618.  
  619.  
  620.  
  621. Case                                                           [Page 33] 
  622.  RFC 1628                        UPS MIB                         May 1994 
  623.  
  624.                 "The compliance statement for UPSs that support                advanced full-featured functions."        MODULE -- this module            MANDATORY-GROUPS { upsFullIdentGroup, upsFullBatteryGroup,                      upsFullInputGroup, upsFullOutputGroup,                      upsFullAlarmGroup, upsFullTestGroup,                      upsFullControlGroup, upsFullConfigGroup } 
  625.  
  626.        OBJECT     upsAlarmDescr        DESCRIPTION                "Support of all `well known' alarm types is not                required.  The well known alarm types which must be                supported are: upsAlarmBatteryBad, upsAlarmOnBattery,                upsAlarmLowBattery, upsAlarmDepletedBattery,                upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass,                upsAlarmBypassBad, upsAlarmOutputOffAsRequested,                upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,                upsAlarmUpsSystemOff, upsAlarmGeneralFault,                upsAlarmDiagnosticTestFailed,                upsAlarmCommunicationsLost, upsAlarmShutdownPending,                and upsAlarmTestInProgress." 
  627.  
  628.        OBJECT     upsTestId        DESCRIPTION                "Support of all `well known' test types is not                required.  The well known test types which must be                supported are: upsTestNoTestsInitiated,                upsTestGeneralSystemsTest, and                upsTestQuickBatteryTest." 
  629.  
  630.        OBJECT     upsOutputSource        SYNTAX     INTEGER {            normal(2),            battery(4)        }        DESCRIPTION                "Support of the values other(1), none(2), bypass(4),                booster(6) and reducer(7) is not required." 
  631.  
  632.            GROUP upsFullBypassGroup            DESCRIPTION                "The upsFullBypassGroup is only required for UPSs that                have a Bypass present." 
  633.  
  634.        OBJECT     upsShutdownType        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required, i.e., compliant 
  635.  
  636.  
  637.  
  638. Case                                                           [Page 34] 
  639.  RFC 1628                        UPS MIB                         May 1994 
  640.  
  641.                 systems need not support more than one shutdown type." 
  642.  
  643.        OBJECT     upsAutoRestart        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required, i.e., compliant                systems need not support more than one restart type." 
  644.  
  645.        OBJECT     upsConfigInputVoltage        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  646.  
  647.        OBJECT     upsConfigInputFreq        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  648.  
  649.        OBJECT     upsConfigOutputVoltage        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  650.  
  651.        OBJECT     upsConfigOutputFreq        MIN-ACCESS read-only        DESCRIPTION                "Read-write access is not required." 
  652.  
  653.        OBJECT     upsConfigLowBattTime        DESCRIPTION                "Implementation of all possible values may be onerous                for some systems.  Consequently, not all possible                values must be supported.  However, at least two                different manufacturer-selected values must be                supported." 
  654.  
  655.        ::= { upsCompliances 3 } 
  656.  
  657.     --    -- units of conformance    -- 
  658.  
  659.    -- summary at a glance: 
  660.  
  661.    --                                      subset  basic   adv    --upsIdentManufacturer                  x       x       x    --upsIdentModel                         x       x       x 
  662.  
  663.  
  664.  
  665. Case                                                           [Page 35] 
  666.  RFC 1628                        UPS MIB                         May 1994 
  667.  
  668.     --upsIdentUPSSoftwareVersion                    x       x    --upsIdentAgentSoftwareVersion          x       x       x    --upsIdentName                          x       x       x    --upsIdentAttachedDevices               x               x    --    --upsBatteryStatus                      x       x       x  notes    --upsSecondsOnBattery                   x       x       x    --upsEstimatedMinutesRemaining                          x    --upsEstimatedChargeRemaining                           x    --upsBatteryVoltage    --upsBatteryCurrent    --upsBatteryTemperature    --    --upsInputLineBads                      x       x       x    --upsInputNumLines                              x       x    --upsInputFrequency                             x       x    --upsInputVoltage                               x       x    --upsInputCurrent    --upsInputTruePower    --    --upsOutputSource                       x       x       x  notes    --upsOutputFrequency                            x       x    --upsOutputNumLines                             x       x    --upsOutputVoltage                              x       x    --upsOutputCurrent                                      x    --upsOutputPower                                        x    --upsOutputPercentLoad                                  x    --    --    --upsBypassFrequency                            x       x  notes    --upsBypassNumLines                             x       x    --upsBypassVoltage                              x       x    --upsBypassCurrent    --upsBypassPower    --    --    --upsAlarmsPresent                      x       x       x    --upsAlarmDescr                         x       x       x  notes    --upsAlarmTime                          x       x       x    --    --upsTestId                                     x       x  notes    --upsTestSpinLock                               x       x    --upsTestResultsSummary                         x       x    --upsTestResultsDetail                          x       x    --upsTestStartTime                              x       x    --upsTestElapsedTime                            x       x    --    --upsShutdownType                       x       x       x  notes 
  669.  
  670.  
  671.  
  672. Case                                                           [Page 36] 
  673.  RFC 1628                        UPS MIB                         May 1994 
  674.  
  675.     --upsShutdownAfterDelay                 x       x       x    --upsStartupAfterDelay                          x       x    --upsRebootWithDuration                         x       x    --upsAutoRestart                        x       x       x  notes    --    --upsConfigInputVoltage                 x       x       x  notes    --upsConfigInputFreq                    x       x       x  notes    --upsConfigOutputVoltage                x       x       x  notes    --upsConfigOutputFreq                   x       x       x  notes    --upsConfigOutputVA                     x       x       x    --upsConfigOutputPower                  x       x       x    --upsConfigLowBattTime                          x       x  notes    --upsConfigAudibleStatus                        x       x    --upsConfigLowVoltageTransferPoint    --upsConfigHighVoltageTransferPoint 
  676.  
  677.     -- units of conformance    upsGroups             OBJECT IDENTIFIER ::= { upsConformance 2 } 
  678.  
  679.    upsSubsetGroups       OBJECT IDENTIFIER ::= { upsGroups 1 } 
  680.  
  681.    upsSubsetIdentGroup OBJECT-GROUP        OBJECTS { upsIdentManufacturer, upsIdentModel,                  upsIdentAgentSoftwareVersion, upsIdentName,                  upsIdentAttachedDevices }        STATUS  current        DESCRIPTION                "The upsSubsetIdentGroup defines objects which are                common across all UPSs which meet subset compliance.                Most devices which conform to the upsSubsetIdentGroup                will provide access to these objects via a proxy                agent.  If the proxy agent is compatible with multiple                UPS types, configuration of the proxy agent will                require specifying some of these values, either                individually, or as a group (perhaps through a table                lookup mechanism based on the UPS model number)."        ::= { upsSubsetGroups 1 } 
  682.  
  683.    upsSubsetBatteryGroup OBJECT-GROUP        OBJECTS { upsBatteryStatus, upsSecondsOnBattery }        STATUS  current        DESCRIPTION                "The upsSubsetBatteryGroup defines the objects that                are common to battery groups of two-contact UPSs."        ::= { upsSubsetGroups 2 } 
  684.  
  685.    upsSubsetInputGroup OBJECT-GROUP 
  686.  
  687.  
  688.  
  689. Case                                                           [Page 37] 
  690.  RFC 1628                        UPS MIB                         May 1994 
  691.  
  692.         OBJECTS { upsInputLineBads }        STATUS  current        DESCRIPTION                "The upsSubsetInputGroup defines the objects that are                common to the Input groups of two-contact UPSs."        ::= { upsSubsetGroups 3 } 
  693.  
  694.    upsSubsetOutputGroup OBJECT-GROUP        OBJECTS { upsOutputSource }        STATUS  current        DESCRIPTION                "The upsSubsetOutputGroup defines the objects that are                common to the Output groups of two-contact UPSs."        ::= { upsSubsetGroups 4 } 
  695.  
  696.     -- { upsSubsetGroups 5 } is reserved for    -- future use (upsSubsetBypassGroup) 
  697.  
  698.    upsSubsetAlarmGroup OBJECT-GROUP        OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }        STATUS  current        DESCRIPTION                "The upsSubsetAlarmGroup defines the objects that are                common to the Alarm groups of two-contact UPSs."        ::= { upsSubsetGroups 6 }     -- { upsSubsetGroups 7 } is reserved for    -- future use (upsSubsetTestGroup) 
  699.  
  700.    upsSubsetControlGroup OBJECT-GROUP        OBJECTS { upsShutdownType, upsShutdownAfterDelay,                      upsAutoRestart }        STATUS  current        DESCRIPTION                "The upsSubsetControlGroup defines the objects that                are common to the Control groups of two-contact UPSs."        ::= { upsSubsetGroups 8 } 
  701.  
  702.    upsSubsetConfigGroup OBJECT-GROUP        OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,                  upsConfigOutputVoltage, upsConfigOutputFreq,                  upsConfigOutputVA, upsConfigOutputPower }        STATUS  current        DESCRIPTION                "The upsSubsetConfigGroup defines the objects that are                common to the Config groups of two-contact UPSs."        ::= { upsSubsetGroups 9 } 
  703.  
  704.  
  705.  
  706. Case                                                           [Page 38] 
  707.  RFC 1628                        UPS MIB                         May 1994 
  708.  
  709.     upsBasicGroups        OBJECT IDENTIFIER ::= { upsGroups 2 } 
  710.  
  711.    upsBasicIdentGroup OBJECT-GROUP        OBJECTS { upsIdentManufacturer, upsIdentModel,                  upsIdentUPSSoftwareVersion,                  upsIdentAgentSoftwareVersion, upsIdentName }        STATUS  current        DESCRIPTION                "The upsBasicIdentGroup defines objects which are                common to the Ident group of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 1 } 
  712.  
  713.    upsBasicBatteryGroup OBJECT-GROUP        OBJECTS { upsBatteryStatus, upsSecondsOnBattery }        STATUS  current        DESCRIPTION                "The upsBasicBatteryGroup defines the objects that are                common to the battery groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 2 } 
  714.  
  715.    upsBasicInputGroup OBJECT-GROUP        OBJECTS { upsInputLineBads, upsInputNumLines,                  upsInputFrequency, upsInputVoltage }        STATUS  current        DESCRIPTION                "The upsBasicInputGroup defines the objects that are                common to the Input groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 3 } 
  716.  
  717.    upsBasicOutputGroup OBJECT-GROUP        OBJECTS { upsOutputSource, upsOutputFrequency,                  upsOutputNumLines, upsOutputVoltage }        STATUS  current        DESCRIPTION                "The upsBasicOutputGroup defines the objects that are                common to the Output groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 4 } 
  718.  
  719.    upsBasicBypassGroup OBJECT-GROUP        OBJECTS { upsBypassFrequency, upsBypassNumLines,                  upsBypassVoltage }        STATUS  current        DESCRIPTION                "The upsBasicBypassGroup defines the objects that are 
  720.  
  721.  
  722.  
  723. Case                                                           [Page 39] 
  724.  RFC 1628                        UPS MIB                         May 1994 
  725.  
  726.                 common to the Bypass groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 5 } 
  727.  
  728.    upsBasicAlarmGroup OBJECT-GROUP        OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }        STATUS  current        DESCRIPTION 
  729.  
  730.                "The upsBasicAlarmGroup defines the objects that are                common to the Alarm  groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 6 } 
  731.  
  732.    upsBasicTestGroup OBJECT-GROUP        OBJECTS { upsTestId, upsTestSpinLock,                  upsTestResultsSummary, upsTestResultsDetail,                  upsTestStartTime, upsTestElapsedTime }        STATUS  current        DESCRIPTION                "The upsBasicTestGroup defines the objects that are                common to the Test groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 7 } 
  733.  
  734.    upsBasicControlGroup OBJECT-GROUP        OBJECTS { upsShutdownType, upsShutdownAfterDelay,                  upsStartupAfterDelay, upsRebootWithDuration,                  upsAutoRestart }        STATUS  current        DESCRIPTION                "The upsBasicControlGroup defines the objects that are                common to the Control groups of compliant UPSs which                support basic functions."        ::= { upsBasicGroups 8 } 
  735.  
  736.    upsBasicConfigGroup OBJECT-GROUP        OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,                  upsConfigOutputVoltage, upsConfigOutputFreq,                  upsConfigOutputVA, upsConfigOutputPower,                  upsConfigLowBattTime, upsConfigAudibleStatus }        STATUS  current        DESCRIPTION                "The upsBasicConfigGroup defines the objects that are                common to the Config groups of UPSs which support                basic functions."        ::= { upsBasicGroups 9 } 
  737.  
  738.  
  739.  
  740.  Case                                                           [Page 40] 
  741.  RFC 1628                        UPS MIB                         May 1994 
  742.  
  743.     upsFullGroups         OBJECT IDENTIFIER ::= { upsGroups 3 } 
  744.  
  745.    upsFullIdentGroup OBJECT-GROUP        OBJECTS { upsIdentManufacturer, upsIdentModel,                  upsIdentUPSSoftwareVersion,                  upsIdentAgentSoftwareVersion, upsIdentName,                  upsIdentAttachedDevices }        STATUS  current        DESCRIPTION                "The upsFullIdentGroup defines objects which are                common to the Ident group of fully compliant UPSs."        ::= { upsFullGroups 1 } 
  746.  
  747.    upsFullBatteryGroup OBJECT-GROUP        OBJECTS { upsBatteryStatus, upsSecondsOnBattery,                  upsEstimatedMinutesRemaining,                  upsEstimatedChargeRemaining }        STATUS  current        DESCRIPTION                "The upsFullBatteryGroup defines the objects that are                common to the battery groups of fully compliant UPSs."        ::= { upsFullGroups 2 } 
  748.  
  749.    upsFullInputGroup OBJECT-GROUP        OBJECTS { upsInputLineBads, upsInputNumLines,                  upsInputFrequency, upsInputVoltage }        STATUS  current        DESCRIPTION                "The upsFullInputGroup defines the objects that are                common to the Input groups of fully compliant UPSs."        ::= { upsFullGroups 3 } 
  750.  
  751.    upsFullOutputGroup OBJECT-GROUP        OBJECTS { upsOutputSource, upsOutputFrequency,                  upsOutputNumLines, upsOutputVoltage,                  upsOutputCurrent, upsOutputPower,                  upsOutputPercentLoad }        STATUS  current        DESCRIPTION                "The upsFullOutputGroup defines the objects that are                common to the Output groups of fully compliant UPSs."        ::= { upsFullGroups 4 } 
  752.  
  753.    upsFullBypassGroup OBJECT-GROUP        OBJECTS { upsBypassFrequency, upsBypassNumLines,                  upsBypassVoltage }        STATUS  current        DESCRIPTION 
  754.  
  755.  
  756.  
  757. Case                                                           [Page 41] 
  758.  RFC 1628                        UPS MIB                         May 1994 
  759.  
  760.                 "The upsFullBypassGroup defines the objects that are                common to the Bypass groups of fully compliant UPSs."        ::= { upsFullGroups 5 } 
  761.  
  762.    upsFullAlarmGroup OBJECT-GROUP        OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }        STATUS  current        DESCRIPTION 
  763.  
  764.                "The upsFullAlarmGroup defines the objects that are                common to the Alarm  groups of fully compliant UPSs."        ::= { upsFullGroups 6 } 
  765.  
  766.    upsFullTestGroup OBJECT-GROUP        OBJECTS { upsTestId, upsTestSpinLock,                  upsTestResultsSummary, upsTestResultsDetail,                  upsTestStartTime, upsTestElapsedTime }        STATUS  current        DESCRIPTION                "The upsFullTestGroup defines the objects that are                common to the Test groups of fully compliant UPSs."        ::= { upsFullGroups 7 } 
  767.  
  768.    upsFullControlGroup OBJECT-GROUP        OBJECTS { upsShutdownType, upsShutdownAfterDelay,                  upsStartupAfterDelay, upsRebootWithDuration,                  upsAutoRestart }        STATUS  current        DESCRIPTION    "The upsFullControlGroup defines the objects that are    common to the Control groups of fully compliant UPSs."        ::= { upsFullGroups 8 } 
  769.  
  770.    upsFullConfigGroup OBJECT-GROUP        OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,                  upsConfigOutputVoltage, upsConfigOutputFreq,                  upsConfigOutputVA, upsConfigOutputPower,                  upsConfigLowBattTime, upsConfigAudibleStatus }        STATUS  current        DESCRIPTION                "The upsFullConfigGroup defines the objects that are                common to the Config groups of fully compliant UPSs."        ::= { upsFullGroups 9 } 
  771.  
  772.    END 
  773.  
  774.  
  775.  
  776.  
  777.  
  778.  Case                                                           [Page 42] 
  779.  RFC 1628                        UPS MIB                         May 1994 
  780.  
  781.  5.  Acknowledgements 
  782.  
  783.    The UPS MIB represents the combined work of the IETF UPS MIB Working    Group, with particular, substantial authorship contributions from: 
  784.  
  785.            Mike Davison            Fibercom, Inc. 
  786.  
  787.            Ray Wasson            Consultant 
  788.  
  789.            Roger Draper            Liebert Corporation 
  790.  
  791.            Ken Key            SNMP Research, Incorporated 
  792.  
  793.            Pete Yoest            American Power Conversion 
  794.  
  795.            Doug Rademacher            American Power Conversion 
  796.  
  797.            Ron Pitt            Network Security Systems, Inc 
  798.  
  799.            Terry Zumwalt            International Power Machines 
  800.  
  801.            Lawren Markle            Tripp Lite 
  802.  
  803.            Bill Elliot            ONEAC 
  804.  
  805.            Tom Brennan            Exide Electronics 
  806.  
  807.            Brian Young            Best Power Technology 
  808.  
  809.  
  810.  
  811.  
  812.  
  813.  
  814.  
  815.  
  816.  
  817.  
  818.  
  819. Case                                                           [Page 43] 
  820.  RFC 1628                        UPS MIB                         May 1994 
  821.  
  822.  6.  References 
  823.  
  824.    [1] Case, J., Fedor, M., Schoffstall, M., and J. Davin, "Simple        Network Management Protocol", STD 15, RFC 1157, SNMP Research,        Inc., Performance Systems International, Performance Systems        International, MIT Laboratory for Computer Science, May 1990. 
  825.  
  826.    [2] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Protocol        Operations for Version 2 of the Simple Network Management        Protocol (SNMPv2)", RFC 1448, SNMP Research, Inc., Hughes LAN        Systems, Dover Beach Consulting, Inc., Carnegie Mellon        University, April 1993. 
  827.  
  828.    [3] McCloghrie, K., and M. Rose, Editors, "Management Information        Base for Network Management of TCP/IP-based internets: MIB-II",        STD 17, RFC 1213, Hughes LAN Systems, Performance Systems        International, March 1991. 
  829.  
  830.    [4] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Structure        of Management Information for Version 2 of the Simple Network        Management Protocol (SNMPv2)", RFC 1442, SNMP Research, Inc.,        Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon        University, April 1993. 
  831.  
  832.    [5] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser,        "Conformance Statements for Version 2 of the Simple Network        Management Protocol (SNMPv2)", RFC 1444, SNMP Research, Inc.,        Hughes LAN Systems, Dover Beach Consulting, Inc., Carnegie Mellon        University, April, 1993. 
  833.  
  834.    [6] Case, J., McCloghrie, K., Rose, M., and S. Waldbusser, "Textual        Conventions for Version 2 of the Simple Network Management        Protocol (SNMPv2)", RFC 1443, SNMP Research, Inc., Hughes LAN        Systems, Dover Beach Consulting, Inc., Carnegie Mellon        University, April 1993. 
  835.  
  836.  
  837.  
  838.  
  839.  
  840.  
  841.  
  842.  
  843.  
  844.  
  845.  
  846.  
  847.  
  848.  
  849.  
  850.  Case                                                           [Page 44] 
  851.  RFC 1628                        UPS MIB                         May 1994 
  852.  
  853.  7.  Security Considerations 
  854.  
  855.    Security issues are not discussed in this memo. 
  856.  
  857. 8.  Author's Address 
  858.  
  859.    Jeffrey D. Case, Ph.D.    SNMP Research, Incorporated    3001 Kimberlin Heights Road    Knoxville, Tennessee 37920 
  860.  
  861.    Phone:  (615) 573-1434    EMail:  case@SNMP.COM 
  862.  
  863.  
  864.  
  865.  
  866.  
  867.  
  868.  
  869.  
  870.  
  871.  
  872.  
  873.  
  874.  
  875.  
  876.  
  877.  
  878.  
  879.  
  880.  
  881.  
  882.  
  883.  
  884.  
  885.  
  886.  
  887.  
  888.  
  889.  
  890.  
  891.  
  892.  
  893.  
  894.  
  895.  
  896.  
  897.  
  898.  
  899.  Case                                                           [Page 45] 
  900.  
  901.