21 lines
Sequoyah Nuclear, 2 Units, 2 Ecodyne natural draft crossflow
2 <number of units
2 <number of cooling towers
N <is tower 1 natural draft
1 2 0 0 0 0 <unit(s) is(are) connected to tower
N <is tower 2 natural draft
1 2 0 0 0 0 <unit(s) is(are) connected to tower
1185 1185 0 0 0 0 <design loads [MW]
1218 1218 0 0 0 0 <maximum loads [MW]
2.0 2.0 .0 .0 .0 .0 <design BP(s) [in.Hg]
5.0 5.0 .0 .0 .0 .0 <maximum BP(s) [in.Hg]
9865 9865 0 0 0 0 <design condenser heatrate(s)
.85 .85 .00 .00 .00 .00 <design condenser cleanliness
561000 561000 0 0 0 0 <design condenser flow(s) [gpm]
55.0 55.0 .0 .0 .0 .0 <design condenser inlet temp(s)
560000 560000 0 0 0 0 <design tower flow(s) [gpm]
110.5 110.5 .0 .0 .0 .0 <design tower inlet temp(s)
81.0 81.0 .0 .0 .0 .0 <design tower exit temp(s)
60.4 60.4 .0 .0 .0 .0 <design cooling tower dry-bulb
55.0 55.0 .0 .0 .0 .0 <design cooling tower wet-bulb