home *** CD-ROM | disk | FTP | other *** search
/ Explore the World of Soft…e: Engineering & Science / Explore_the_World_of_Software_Engineering_and_Science_HRS_Software_1998.iso / programs / pwrplant / mupit250.exe / JSEVIER.MUP < prev    next >
Text File  |  1988-06-24  |  1KB  |  25 lines

  1. John Sevier Steam Plant, 4 Units, 180 MW nominal each
  2. 4 <number of units
  3. 4 <number of cooling towers
  4. M <is tower 1 mechanical draft
  5.  1 2 3 4 0 0 <unit(s) is(are) connected to tower
  6. M <is tower 2 mechanical draft
  7.  1 2 3 4 0 0 <unit(s) is(are) connected to tower
  8. M <is tower 3 mechanical draft
  9.  1 2 3 4 0 0 <unit(s) is(are) connected to tower
  10. M <is tower 4 mechanical draft
  11.  1 2 3 4 0 0 <unit(s) is(are) connected to tower
  12.      191     191     191     191       0       0 <design loads [MW]
  13.      200     200     200     200       0       0 <maximum loads [MW]
  14.      2.0     2.0     2.0     2.0      .0      .0 <design BP(s) [in.Hg]
  15.      5.0     5.0     5.0     5.0      .0      .0 <maximum BP(s) [in.Hg]
  16.     7933    7933    7933    7933       0       0 <design condenser heatrate(s)
  17.      .85     .85     .85     .85     .00     .00 <design condenser cleanliness
  18.   113500  113500  113500  113500       0       0 <design condenser flow(s) [gpm]
  19.     72.0    72.0    72.0    72.0      .0      .0 <design condenser inlet temp(s)
  20.   113500  113500  113500  113500       0       0 <design tower flow(s) [gpm]
  21.   116.95  116.95  116.95  116.95      .0      .0 <design tower inlet temp(s)
  22.    101.0   101.0   101.0   101.0      .0      .0 <design tower exit temp(s)
  23.     92.0    92.0    92.0    92.0      .0      .0 <design cooling tower dry-bulb
  24.     80.0    80.0    80.0    80.0      .0      .0 <design cooling tower wet-bulb
  25.