  1. [ Ups ]
  2.  SignallingType = Smart
  3.  PortName = COM1
  4.  AutoUpsRebootEnabled = Yes
  5.  AllowedPortNames = COM1,COM2
  6.  BatteryRunTimeEnabled=Yes
  7.  NetViewAlerts = No
  8.  Standalone = No
  9.  
  10. [ EventLogging ]
  11.  EventLogEnabled = Yes
  12.  EventLogName = C:\pwrchute\pwrchute.log
  13.  EventLogName = powerchute.log
  14.  EventLogMaxSize = 50000
  15.  
  16.  
  17. [ DataLogging ]
  18.  DataLogEnabled = Yes
  19.  DataLogName = C:\pwrchute\pwrchute.dat
  20.  DataLogName = powerchute.dat
  21.  DataLogMaxSize = 50000
  22.  DataLogInterval = 600
  23.  
  24. [ ErrorLogging ]
  25.  ErrorLogEnabled = Yes
  26.  ErrorLogName = C:\pwrchute\pwrchute.err
  27.  ErrorLogName = powerchute.err
  28.  ErrorLogMaxSize = 50000
  29.  
  30.  
  31. [ Messaging ]
  32.  MessageDelay = 5
  33.  MessageInterval = 30
  34.  
  35.  
  36. [ SelfTests ]
  37.  EnableSelfTests = Yes
  38.  SelfTestDay = MONDAY
  39.  SelfTestSchedule = At turn on
  40.  SelfTestTime = 12:00 PM
  41.  
  42. [ Shutdown ]
  43.  ShutdownDelay = 30
  44.  AdminShutdownDelay = 900
  45.  DailyShutdownEnabled = No
  46.  DailyShutdownTime = 6:00 PM
  47.  DailyWakeupTime = 7:00 AM
  48.  WeeklyShutdownEnabled = No
  49.  WeeklyShutdownDay = Friday
  50.  WeeklyShutdownTime = 6:00 PM
  51.  WeeklyWakeUpDay = Monday
  52.  WeeklyWakeUpTime = 7:00 AM
  53.  
  54. [ Server ]
  55.  Security = No
  56.  HostName =
  57.  
  58. [ UserInterface ]
  59.  TemperatureUnits = Fahrenheit
  60.  SoundEffects = No
  61.  
  62. [ BatteryCalibration ]
  63.  Enabled = No
  64.  BatteryCalibrationDay = Monday
  65.  BatteryCalibrationTime = 07:00 AM
  66.  
  67. [ Devices ]
  68.  MeasureUps = No
  69.  
  70. [ EventText ]
  71.  100000 = *** PowerChute PLUS Version 4.2.3 Started ***
  72.  100100 = *** PowerChute PLUS Stopped ***
  73.  100200 = Communication established
  74.  100300 = Normal power restored: UPS on line
  75.  100400 = UPS self-test passed
  76.  100401 = Scheduled UPS self-test passed
  77.  100402 = User initiated UPS self-test passed
  78.  100403 = Self-test at UPS passed
  79.  100500 = Administrative shutdown started
  80.  100501 = Administrative shutdown: User initiated
  81.  100502 = Administrative shutdown: Weekly shutdown
  82.  100503 = Administrative shutdown: Daily shutdown
  83.  100600 = Shutdown cancelled
  84.  100601 = User initiated shutdown cancelled
  85.  100602 = Weekly administrative shutdown cancelled
  86.  100603 = Daily administrative shutdown cancelled
  87.  100700 = UPS returned from low battery condition
  88.  100701 = UPS returned from low battery condition: #BATTERY_CAPACITY#
  89.  100900 = UPS batteries no longer need replacing
  90.  101000 = Contact #CONTACT_NUMBER# normal (#NORMAL_POSITION#): #USER_COMMENT#
  91.  101300 = UPS overload condition solved
  92.  101400 = UPS run time calibration initiated
  93.  101500 = UPS run time calibration completed
  94.  101600 = Shutdown started
  95.  101601 = User initiated shutdown started
  96.  101602 = Weekly administrative shutdown started
  97.  101603 = Daily administrative shutdown started
  98.  101700 = UPS returned from bypass
  99.  101800 = Smart Cell signal restored
  100.  101900 = Immediate shutdown started
  101.  110000 = Ambient temperature back within thresholds
  102.  110100 = Ambient humidity back within thresholds
  103.  110200 = UPS internal temperature in bounds
  104.  
  105.  
  106.  200000 = UPS on battery
  107.  200001 = UPS on battery: High input line voltage #MAX_VOLTAGE# V
  108.  200002 = UPS on battery: Brownout #MIN_VOLTAGE# V
  109.  200003 = UPS on battery: Blackout #MIN_VOLTAGE# V
  110.  200004 = UPS on battery: Small momentary sag #MIN_VOLTAGE# V
  111.  200006 = UPS on battery: Deep momentary sag #MIN_VOLTAGE# V
  112.  200005 = UPS on battery: Small momentary spike #MAX_VOLTAGE# V
  113.  200007 = UPS on battery: Large momentary spike #MAX_VOLTAGE# V
  114.  200008 = UPS on battery: Simulated power failure
  115.  200100 = System shutdown
  116.  200101 = System shutdown: #INITIATOR# initiated
  117.  200200 = UPS enabling Smart Boost
  118.  200300 = Low battery condition
  119.  200301 = Low battery condition: #BATTERY_CAPACITY#
  120.  200400 = UPS run time calibration cancelled
  121.  200401 = UPS run time calibration cancelled by user
  122.  200402 = UPS run time calibration cancelled by power failure
  123.  200403 = UPS unable to perform run time calibration: Capacity < 100
  124.  200700 = UPS enabling SmartTrim
  125.  201301 = UPS on bypass: user set via software or panel
  126.  201302 = UPS on bypass: user set via rear switch
  127.  
  128.  
  129.  300000 = Unable to communicate with UPS
  130.  300100 = UPS output overload
  131.  300200 = UPS self-test failed
  132.  300201 = Scheduled UPS self-test failed: Bad battery
  133.  300202 = Scheduled UPS self-test failed: Invalid test
  134.  300203 = User initiated self-test failed: Bad battery
  135.  300204 = User initiated self-test failed: Invalid test
  136.  300205 = Self-test at UPS failed: Bad battery
  137.  300206 = Self-test at UPS failed: Invalid test
  138.  300300 = UPS battery is discharged
  139.  300301 = UPS battery is discharged: #BATTERY_CAPACITY#
  140.  300400 = Communication lost while on battery
  141.  300600 = Contact #CONTACT_NUMBER# fault (#CONTACT_POSITION#): #USER_COMMENT#
  142.  301000 = Check installation of Smart Cell signal cable
  143.  301300 = UPS on bypass: internal temp over limit
  144.  301301 = UPS on bypass: battery charger failure
  145.  301302 = UPS on bypass: severe DC imbalance overload
  146.  301303 = UPS on bypass: output voltage outside limits
  147.  301304 = UPS on bypass: top module fan needs repair
  148.  301400 = Base module fan needs repair
  149.  301500 = Base module bypass power supply needs repair
  150.  301600 = UPS battery needs replacing
  151.  
  152.  310001 = Below lower ambient temperature threshold of #LOW_THRESHOLD#
  153.  310002 = Exceeded upper ambient temperature threshold of #HIGH_THRESHOLD#
  154.  310101 = Below humidity threshold of #LOW_THRESHOLD#
  155.  310102 = Exceeded upper humidity threshold of #HIGH_THRESHOLD#
  156.  
  157.  310700 = Maximum UPS internal temperature exceeded
  158.  
  159. [ PopupText ]
  160.  1003 = Normal utility power at #HOSTNAME# has been restored.
  161.  1006 = Shutdown of #HOSTNAME# has been cancelled.
  162.  1007 = UPS batteries at #HOSTNAME# are no longer discharged.
  163.  1016 = Shutdown process started.
  164.  
  165.  2000 = #HOSTNAME# is running on battery power.
  166.  2001 = #HOSTNAME# has been shutdown.
  167.  2003 = Low battery power at #HOSTNAME#.
  168.  
  169.  3000 = #HOSTNAME# has lost communications with the UPS.
  170.  3003 = UPS batteries at #HOSTNAME# are discharged.
  171.  
  172. [ FlexEventNames ]
  173.  1000 = PowerChute Started
  174.  1001 = PowerChute Stopped
  175.  1002 = Communication Established
  176.  1003 = Power Restored
  177.  1004 = UPS Self-Test Passed
  178.  1005 = Administrative Shutdown
  179.  1006 = Shutdown Cancelled
  180.  1007 = UPS Return From Low Battery
  181.  1009 = Battery No Longer Needs Replacing
  182.  1010 = Contact Normal
  183.  1012 = UPS Returned From Abnormal Condition
  184.  1013 = UPS Overload Condition Solved
  185.  1014 = UPS Run Time Calibration Initiated
  186.  1015 = UPS Run Time Calibration Completed
  187.  1016 = System Shutdown Starting
  188.  1017 = Return From Bypass
  189.  1018 = Smart Cell signal returned
  190.  1019 = Immediate Shutdown
  191.  
  192.  1100 = Ambient Temp In Range
  193.  1101 = Humidity In Range
  194.  1102 = UPS Temperature in Bounds
  195.  
  196.  2007 = UPS Enabling SmartTrim
  197.  1102 = UPS Temperature in Bounds
  198.  3107 = Maximum internal UPS temp exceeded
  199.  2000 = UPS On Battery
  200.  2001 = System Shutdown Complete
  201.  2002 = UPS Enabling Smart Boost
  202.  2003 = Low Battery Condition
  203.  2004 = Cancel Battery Calibration
  204.  2013 = UPS On Bypass: Maintenance
  205.  
  206.  
  207.  3000 = Unable To Communicate With UPS
  208.  3001 = UPS Output Overload
  209.  3002 = UPS Self-Test Failed
  210.  3003 = UPS Battery Is Discharged
  211.  3004 = Comm Lost While On Battery
  212.  3006 = Abnormal Contact Position
  213.  3010 = Check Smart Cell Signal
  214.  3012 = UPS In Abnormal Condition
  215.  3013 = UPS On Bypass: Failure
  216.  3014 = Base Module Fan Failure
  217.  3015 = Base Module Power Supply Failure
  218.  3016 = UPS Battery Needs Replacing
  219.  
  220.  3100 = Ambient Temp Out Of Range
  221.  3101 = Humidity Out Of Range
  222.  3107 = Maximum internal UPS temp exceeded
  223.  
  224.  
  225. [ Email ]
  226.  Password = APC
  227.  
  228. [ LineFail ]
  229.  NotifyDelay = 5
  230.  NotifyInterval = 30
  231.  NotifyRepeat = Yes
  232.  ShutdownDelay = 300
  233.  Actions = LUS
  234.  
  235. [ AdminShutdown ]