  1. [ Ups ]
  2.  SignallingType = Smart
  3.  PortName = COM1
  4.  AutoUpsRebootEnabled = Yes
  5.  AllowedPortNames = COM1,COM2
  6.  BatteryRunTimeEnabled=Yes
  7.  NetViewAlerts = No
  8.  Standalone = No
  9.  
  10. [ EventLogging ]
  11.  EventLogEnabled = Yes
  12.  EventLogName = C:\PWRCHUTE\pwrchute.log
  13.  EventLogName = powerchute.log
  14.  EventLogMaxSize = 50000
  15.  
  16.  
  17. [ DataLogging ]
  18.  DataLogEnabled = Yes
  19.  DataLogName = C:\PWRCHUTE\pwrchute.dat
  20.  DataLogName = powerchute.dat
  21.  DataLogMaxSize = 50000
  22.  DataLogInterval = 600
  23.  
  24. [ ErrorLogging ]
  25.  ErrorLogEnabled = Yes
  26.  ErrorLogName = C:\PWRCHUTE\pwrchute.err
  27.  ErrorLogName = powerchute.err
  28.  ErrorLogMaxSize = 50000
  29.  
  30.  
  31. [ Messaging ]
  32.  MessageDelay = 5
  33.  MessageInterval = 30
  34.  
  35.  
  36. [ SelfTests ]
  37.  EnableSelfTests = Yes
  38.  SelfTestDay = MONDAY
  39.  SelfTestSchedule = At turn on
  40.  SelfTestTime = 12:00 PM
  41.  
  42. [ Shutdown ]
  43.  ShutdownDelay = 30
  44.  AdminShutdownDelay = 900
  45.  DailyShutdownEnabled = No
  46.  DailyShutdownTime = 6:00 PM
  47.  DailyWakeupTime = 7:00 AM
  48.  WeeklyShutdownEnabled = No
  49.  WeeklyShutdownDay = Friday
  50.  WeeklyShutdownTime = 6:00 PM
  51.  WeeklyWakeUpDay = Monday
  52.  WeeklyWakeUpTime = 7:00 AM
  53.  
  54. [ Server ]
  55.  HostName =
  56.  
  57. [ UserInterface ]
  58.  TemperatureUnits = Fahrenheit
  59.  SoundEffects = No
  60.  
  61. [ BatteryCalibration ]
  62.  Enabled = No
  63.  BatteryCalibrationDay = Monday
  64.  BatteryCalibrationTime = 07:00 AM
  65.  
  66. [ Devices ]
  67.  MeasureUps = No
  68.  
  69. [ EventText ]
  70.  100000 = *** PowerChute PLUS Version 4.2.2 Started ***
  71.  100100 = *** PowerChute PLUS Stopped ***
  72.  100200 = Communication established
  73.  100300 = Normal power restored: UPS on line
  74.  100400 = UPS self-test passed
  75.  100401 = Scheduled UPS self-test passed
  76.  100402 = User initiated UPS self-test passed
  77.  100403 = Self-test at UPS passed
  78.  100500 = Administrative shutdown started
  79.  100501 = Administrative shutdown: User initiated
  80.  100502 = Administrative shutdown: Weekly shutdown
  81.  100503 = Administrative shutdown: Daily shutdown
  82.  100600 = Shutdown cancelled
  83.  100601 = User initiated shutdown cancelled
  84.  100602 = Weekly administrative shutdown cancelled
  85.  100603 = Daily administrative shutdown cancelled
  86.  100700 = UPS returned from low battery condition
  87.  100701 = UPS returned from low battery condition: #BATTERY_CAPACITY#
  88.  100900 = UPS batteries no longer need replacing
  89.  101000 = Contact #CONTACT_NUMBER# normal (#NORMAL_POSITION#): #USER_COMMENT#
  90.  101300 = UPS overload condition solved
  91.  101400 = UPS run time calibration initiated
  92.  101500 = UPS run time calibration completed
  93.  101600 = Shutdown started
  94.  101601 = User initiated shutdown started
  95.  101602 = Weekly administrative shutdown  started
  96.  101603 = Daily administrative shutdown  started
  97.  101700 = UPS returned from bypass
  98.  101800 = Smart Cell signal restored
  99.  110000 = Ambient temperature back within thresholds
  100.  110100 = Ambient humidity back within thresholds
  101.  
  102.  
  103.  200000 = UPS on battery
  104.  200001 = UPS on battery: High input line voltage #MAX_VOLTAGE#    V
  105.  200002 = UPS on battery: Brownout #MIN_VOLTAGE# V
  106.  200003 = UPS on battery: Blackout #MIN_VOLTAGE# V
  107.  200004 = UPS on battery: Small momentary sag #MIN_VOLTAGE# V
  108.  200006 = UPS on battery: Deep momentary sag #MIN_VOLTAGE# V
  109.  200005 = UPS on battery: Small momentary spike #MAX_VOLTAGE# V
  110.  200007 = UPS on battery: Large momentary spike #MAX_VOLTAGE# V
  111.  200008 = UPS on battery: Simulated power failure
  112.  200100 = System shutdown
  113.  200101 = System shutdown: #INITIATOR# initiated
  114.  200200 = UPS enabling Smart Boost
  115.  200300 = Low battery condition
  116.  200301 = Low battery condition: #BATTERY_CAPACITY#
  117.  200400 = UPS run time calibration cancelled
  118.  200401 = UPS run time calibration cancelled by user
  119.  200402 = UPS run time calibration cancelled by power failure
  120.  200403 = UPS unable to perform run time calibration: Capacity < 100
  121.  201301 = UPS on bypass: user set via software or panel
  122.  201302 = UPS on bypass: user set via rear switch
  123.  
  124.  
  125.  300000 = Unable to communicate with UPS
  126.  300100 = UPS output overload
  127.  300200 = UPS self-test failed
  128.  300201 = Scheduled UPS self-test failed: Bad battery
  129.  300202 = Scheduled UPS self-test failed: Invalid test
  130.  300203 = User initiated self-test failed: Bad battery
  131.  300204 = User initiated self-test failed: Invalid test
  132.  300205 = Self-test at UPS failed: Bad battery
  133.  300206 = Self-test at UPS failed: Invalid test
  134.  300300 = UPS battery is discharged
  135.  300301 = UPS battery is discharged: #BATTERY_CAPACITY#
  136.  300400 = Communication lost while on battery
  137.  300600 = Contact #CONTACT_NUMBER# fault (#CONTACT_POSITION#): #USER_COMMENT#
  138.  301000 = Check installation of Smart Cell signal cable
  139.  301300 = UPS on bypass: internal temp over limit
  140.  301301 = UPS on bypass: battery charger failure
  141.  301302 = UPS on bypass: severe DC imbalance overload
  142.  301303 = UPS on bypass: output voltage outside limits
  143.  301304 = UPS on bypass: top module fan needs repair
  144.  301400 = Base module fan needs repair
  145.  301500 = Base module bypass power supply needs repair
  146.  301600 = UPS battery needs replacing
  147.  
  148.  310001 = Below lower ambient temperature threshold of #LOW_THRESHOLD#
  149.  310002 = Exceeded upper ambient temperature threshold of #HIGH_THRESHOLD#
  150.  310101 = Below humidity threshold of #LOW_THRESHOLD#
  151.  310102 = Exceeded upper humidity threshold of #HIGH_THRESHOLD#
  152.  
  153.  
  154. [ PopupText ]
  155.  1003 = Normal utility power at #HOSTNAME# has been restored.
  156.  1006 = Shutdown of #HOSTNAME# has been cancelled.
  157.  1007 = UPS batteries at #HOSTNAME# are no longer discharged.
  158.  1016 = Shutdown process started.
  159.  
  160.  2000 = #HOSTNAME# is running on battery power.
  161.  2001 = #HOSTNAME# has been shutdown.
  162.  2003 = Low battery power at #HOSTNAME#.
  163.  
  164.  3000 = #HOSTNAME# has lost communications with the UPS.
  165.  3003 = UPS batteries at #HOSTNAME# are discharged.
  166.  
  167. [ FlexEventNames ]
  168.  1000 = PowerChute Started
  169.  1001 = PowerChute Stopped
  170.  1002 = Communication Established
  171.  1003 = Power Restored
  172.  1004 = UPS Self-Test Passed
  173.  1005 = Administrative Shutdown
  174.  1006 = Shutdown Cancelled
  175.  1007 = UPS Return From Low Battery
  176.  1009 = Battery No Longer Needs Replacing
  177.  1010 = Contact Normal
  178.  1012 = UPS Returned From Abnormal Condition
  179.  1013 = UPS Overload Condition Solved
  180.  1014 = UPS Run Time Calibration Initiated
  181.  1015 = UPS Run Time Calibration Completed
  182.  1016 = System Shutdown Starting
  183.  1017 = Return From Bypass
  184.  1018 = Smart Cell signal returned
  185.  
  186.  1100 = Ambient Temp In Range
  187.  1101 = Humidity In Range
  188.  
  189.  2000 = UPS On Battery
  190.  2001 = System Shutdown Complete
  191.  2002 = UPS Enabling Smart Boost
  192.  2003 = Low Battery Condition
  193.  2004 = Cancel Battery Calibration
  194.  2013 = UPS On Bypass: Maintenance
  195.  
  196.  
  197.  3000 = Unable To Communicate With UPS
  198.  3001 = UPS Output Overload
  199.  3002 = UPS Self-Test Failed
  200.  3003 = UPS Battery Is Discharged
  201.  3004 = Comm Lost While On Battery
  202.  3006 = Abnormal Contact Position
  203.  3010 = Check Smart Cell Signal
  204.  3012 = UPS In Abnormal Condition
  205.  3013 = UPS On Bypass: Failure
  206.  3014 = Base Module Fan Failure
  207.  3015 = Base Module Power Supply Failure
  208.  3016 = UPS Battery Needs Replacing
  209.  
  210.  3100 = Ambient Temp Out Of Range
  211.  3101 = Humidity Out Of Range
  212.  
  213.  
  214. [ Email ]
  215.  Password = APC
  216.  
  217. [ LineFail ]
  218.  NotifyDelay = 5
  219.  NotifyInterval = 30
  220.  NotifyRepeat = Yes
  221.  ShutdownDelay = 300
  222.  Actions = LUS
  223.  
  224. [ AdminShutdown ]