  1.                          SECTION 13980
  2.  
  3.              RETROFIT-SPRINKLER PIPING COVER SYSTEM
  4.  
  5. NOTE ** This section is based on DecoShield piping cover
  6.         systems manufactured by Creative Systems, Inc.,
  7.         headquartered at the following address:
  8. NOTE **      One Parker Place
  9. NOTE **      P.O. Box 957
  10. NOTE **      Janesville, WI  53547
  11. NOTE **      Telephone:  (608) 757-0717
  12. NOTE **      Fax:  (608) 757-0721
  13. NOTE **
  14. NOTE ** This section includes piping anchors and covers for
  15.         retrofitted sprinkler systems installed in existing
  16.         construction.  The covers and anchors are designed
  17.         to be mounted against walls and ceilings; the
  18.         covers are of L-shaped and U-shaped cross-section.
  19.         The entire system is UL listed and can be painted.
  20. NOTE **
  21. NOTE ** SECTION 13980 - RETROFIT-SPRINKLER PIPING COVER
  22.         SYSTEM, Copyright 1996, The Architect's Catalog,
  23.         Inc.
  24.  
  25. PART 1  GENERAL
  26.  
  27. 1.1 SECTION INCLUDES
  28. NOTE ** Delete items below not required for project.
  29.  
  30.     A.  Modular piping cover system for installation of metal
  31.         piping system in existing construction.
  32.  
  33.     B.  Modular combination pipe hanger and cover system for
  34.         installation of CPVC piping system in existing
  35.         construction.
  36.  
  37. 1.2 RELATED SECTIONS
  38. NOTE ** Delete any sections below not relevant to this
  39.         project; add others as required.  If piping is to
  40.         be installed in this project, this section MUST be
  41.         accompanied by a section that specifies the piping
  42.         installation.  The only part of the piping
  43.         installation that is included in this section is
  44.         the actual hanger fitting that encircles the pipe
  45.         and is attached to the wall or ceiling --
  46.         coordinate the piping specification.
  47.  
  48.     A.  Section 13915 - Fire Protection Piping.
  49.  
  50. 1.3 REFERENCES
  51. NOTE ** Delete references from the list below that are not
  52.         actually required by the text of the edited
  53.         section.
  54.  
  55.     A.  ASTM E 84 - Standard Test Method for Surface Burning
  56.         Characteristics of Building Materials.
  57.  
  58.     B.  NFPA 13 - Installation of Sprinkler Systems.
  59.  
  60.     C.  "Building Materials Directory"; Underwriters Laboratories
  61.         Inc.
  62.  
  63.     D.  "Fire Protection Equipment Directory"; Underwriters
  64.         Laboratories Inc.
  65.  
  66. 1.4 SUBMITTALS
  67.  
  68.     A.  Submit under provisions of Section 01300.
  69.  
  70.     B.  Product Data:  Include manufacturer's installation
  71.         instructions.
  72.  
  73.     C.  Certification of UL listings.
  74.  
  75. 1.5 DELIVERY, STORAGE, AND HANDLING
  76.  
  77.     A.  Store materials in areas where temperature will be
  78.         maintained above 35 degrees F.
  79.  
  80.     B.  Protect from exposure to direct sunlight.
  81.  
  82.     C.  Stack or store in such a manner to prevent distortion of
  83.         shape.
  84.  
  85. 1.6 WARRANTY
  86.  
  87.     A.  Provide manufacturer's 10 year material warranty.
  88.  
  89.  
  90. PART 2  PRODUCTS
  91.  
  92. 2.1 MANUFACTURERS
  93.  
  94.     A.  Provide "DecoShield" piping cover system manufactured by
  95.         Creative Systems, Inc., One Parker Place, P.O. Box 957,
  96.         Janesville, WI 53547.  Telephone: (608) 757-0717.
  97.         Fax: (608) 757-0721.
  98.  
  99. 2.2 MATERIALS
  100.  
  101.     A.  Piping Cover System:  Modular, snap-fit cover units,
  102.         clips, and anchors, which once assembled, render the
  103.         cover essentially irremovable with the use of ordinary
  104.         tools; UL listed for use with CPVC piping systems.
  105.  
  106.     B.  Cover Units:  L-shaped and U-shaped cross-section units
  107.         of flame retardant resin material, paintable finish.
  108.         1.  Resin:  B.F. Goodrich Co. "TempRite."
  109.         2.  Surface burning characteristics when tested in
  110.             accordance with ASTM E 84:
  111.             a.  Flame spread:  20.
  112.             b.  Smoke developed:  250.
  113.         3.  Unit length:  7.5 feet.
  114.         4.  Provide coupling fittings for joining units end to
  115.             end and prefabricated inside and outside corner
  116.             fittings and end caps.
  117. NOTE ** Delete the following paragraph if no sidewall
  118.         sprinkler installations are included.
  119.         5.  Provide sidewall sprinkler head housing accommodating
  120.             NFPA 13 4-inch drop assembly requirements.
  121.         6.  Provide mounting clips to secure covers to
  122.             wall/ceiling.
  123.  
  124.     C.  Pipe Hangers for CPVC Piping:  Manufactured by cover
  125.         system manufacturer; UL listed; requiring no special
  126.         tools for installation.
  127.         1.  For supporting piping only:  "Snap-2" hangers.
  128.         2.  For supporting both piping and covers:  "Combo"
  129.             hangers that automatically position pipe in cover.
  130.  
  131.     D.  Pipe Hangers for Copper and Steel Piping:  Design and
  132.         dimensions compatible with cover system; UL listed.
  133. NOTE ** Delete the following paragraph if the covers are to
  134.         be left unpainted or if painting is to be done by
  135.         some entity other than the installer of the covers.
  136.         In the latter case, specify painting in Division 9.
  137.  
  138.     E.  Paint:  Acrylic latex; color to match adjoining surfaces.
  139.  
  140.  
  141. PART 3  EXECUTION
  142.  
  143. 3.1 INSTALLATION
  144.  
  145.     A.  Install in accordance with the manufacturer's
  146.         instructions and recommendations.
  147. NOTE ** Delete the following paragraph if the covers are
  148.         being installed on existing piping.  Otherwise,
  149.         coordinate the section number and title with the
  150.         actual section where the piping installation is
  151.         specified.
  152.  
  153.     B.  See Section 13980 - Fire Protection Piping for
  154.         requirements for installation of piping.  Space hangers
  155.         supporting piping in accordance with applicable
  156.         requirements.
  157.  
  158.     C.  Space hangers and mounting clips supporting covers to
  159.         hold the covers and fittings firmly against the mounting
  160.         surface without gaps or unpleasant appearance.
  161.  
  162.     D.  Install cover units using coupling fittings and corner
  163.         units as required.
  164. NOTE ** Delete the following paragraph if the covers are to
  165.         be left unpainted or if painting is to be done by
  166.         some entity other than the installer of the covers.
  167.         In the latter case, specify painting in Division 9.
  168.  
  169.     E.  Paint entire cover assembly.  Cover sprinkler heads
  170.         carefully during painting and remove covering completely