- SECTION 09800
-
- ACOUSTICAL TREATMENT
-
- NOTE ** This section is based on Eckoustic(R) Functional
- Panels (EFPs) as manufactured by:
- NOTE ** Eckel Industries, Inc.
- NOTE ** Acoustic Division
- NOTE ** 155 Fawcett Street
- NOTE ** Cambridge, MA 02138-1111
- NOTE ** Tel: (617) 491-3221
- NOTE ** Fax: (617) 547-2171
- NOTE **
- NOTE ** Eckoustic Functional Panels are high performance
- sound-absorbing panels that can be spot located on
- walls or ceilings to achieve effective noise
- control. Because they are independent panels, EFPs
- can be put into place without disturbing existing
- lighting or HVAC diffusers. Attractive, fire
- resistant, durable, and easily cleaned, they are
- ideal for correcting noise problems in gymnasiums,
- swimming pools, auditoriums and theaters, and
- similar facilities. They also are appropriate for
- industrial noise control use in water and waste
- water treatment facilities and power plants as well
- as manufacturing facilities.
- NOTE **
- NOTE ** SECTION 09800 - ACOUSTICAL TREATMENT, Copyright
- 1997, The Architect's Catalog, Inc.
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
-
- A. Sound absorptive ceiling panels.
-
- B. Sound absorptive wall panels.
-
- C. Miscellaneous accessories and trim.
-
- 1.2 RELATED SECTIONS
-
- A. Section 09511 - Suspended Acoustical Ceilings:
- Conventional grid-supported acoustic ceilings.
-
- B. Section 15840 - Air Terminal Units.
-
- C. Section 16510 - Interior Luminaires.
-
- 1.3 REFERENCES
-
- A. ASTM C 423 - Standard Test Method for Sound Absorption
- and Sound Absorption Coefficients by the Reverberation
- Room Method.
-
- B. ASTM E 84 - Standard Test Method for Surface Burning
- Characteristics of Building Materials.
-
- 1.4 SUBMITTALS
-
- A. Submit in accordance with provisions of Section 01300.
-
- B. Product Data: Submit manufacturer's recommended
- installation instructions and documentation certifying
- conformance with specified performance requirements.
-
- C. Shop Drawings: Submit drawings indicating layout for all
- areas to receive work of this section, including
- locations of light fixtures, ceiling diffusers, and
- grilles. Indicate pattern of units, cut units, details,
- and coordination requirements for work of other sections.
-
- D. Samples: Submit for approval two samples of sound
- absorptive panel and suspension systems, not less than 12
- inches by 18 inches in size and demonstrating colors,
- textures, and finishes that will be provided in the
- finished work.
-
- 1.5 QUALITY ASSURANCE
-
- A. Installer Qualifications: Installers shall have
- demonstrated experience in assembly and installation of
- products similar to those specified in this section.
-
- 1.6 DELIVERY, STORAGE, AND HANDLING
-
- A. Deliver materials in manufacturer's original unopened and
- undamaged packages with labels legible and intact.
-
- B. Store materials in unopened packages in a manner that
- will avoid damage from the environment and from
- construction operations.
-
- C. Handle in accordance with manufacturer's instructions.
-
- 1.7 ENVIRONMENTAL REQUIREMENTS
-
- A. Do not begin installation of acoustic panels until
- building has been enclosed and environmental conditions
- approximate interior conditions that will prevail when
- building is occupied.
-
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURERS
-
- A. Provide products as manufactured by Eckel Industries,
- Inc.; 155 Fawcett Street; Cambridge, MA 02138-1111. ASD.
- Tel: (617) 491-3221. Fax: (617) 547-2171.
-
- B. Substitutions are not acceptable.
-
- 2.2 ACOUSTIC PANELS
-
- A. Panels - Performance:
- 1. Sound Absorption: Provide panels that are certified
- to meet the following minimum sound absorption for a
- 30 inch by 120 inch panel when tested in accordance
- with ASTM C 423:
- a. 125 Hz: 6.2 sabins.
- b. 250 Hz: 20.5 sabins.
- c. 500 Hz: 35.2 sabins.
- d. 1000 Hz: 34.5 sabins.
- e. 2000 Hz: 31.5 sabins.
- f. 4000 Hz: 33.1 sabins.
- g. NRC: 0.99, minimum.
- 2. Fire: Provide panels that demonstrate the following
- performance when tested in accordance with ASTM E 84:
- a. Flame spread: 10 maximum.
- b. Smoke density: 5 maximum.
- NOTE ** Edit paragraph below for specific areas, if
- required.
-
- B. Provide Eckoustic Functional Panels with total area not
- less than 50 percent of gross ceiling area.
-
- C. Panel Dimensions: 30 inches wide by 5 foot, 6 foot, 8
- foot, and 10 foot lengths as indicated on the drawings.
- NOTE ** Delete one of the following two paragraphs -- the
- first is for steel panels, the second is for
- aluminum panels.
-
- D. Panel Facings: 22 gage electrogalvanized steel sheet,
- perforated with 3/32 inch holes on 5/32 inch staggered
- centers; vee-ridged on 6-inch centers to a depth of 3/4
- inch.
-
- E. Panel Facings: 0.032 inch thick aluminum sheet,
- perforated with 3/32 inch holes on 5/32 inch staggered
- centers; vee-ridged on 6-inch centers to a depth of 3/4
- inch.
-
- F. Framing: 0.040 inch thick channel shaped steel or
- aluminum transverse framing members. For units 30 inches
- wide to 72 inches in length, provide two stiffening
- channels; for units 96 inches in length, provide three
- channels.
-
- G. Fill: 2 inch thick, fine fibered fibrous glass having a
- density of not less than 1.5 pounds per cubic foot,
- wrapped in a 1.5 mil flame guard polyethylene.
- NOTE ** Select one of three paragraphs below. Enamel
- finish is standard for both steel and aluminum
- panels. Natural aluminum is only for aluminum
- panels.
- NOTE **
-
- H. Finish: White urethane enamel.
-
- I. Finish: Natural aluminum finish.
-
- J. Finish: Painted by manufacturer to match Architect's
- color sample.
-
- K. Color: ______________________.
-
- 2.3 MOUNTING COMPONENTS
- NOTE ** Delete one of the two following paragraphs. Steel
- brackets are for steel panels; stainless steel
- brackets are for aluminum panels.
-
- A. Brackets: Provide four 10 gage steel brackets per unit
- for attachment to walls and ceilings, providing 4 inches
- of clearance between back of panel and mounting surface.
-
- B. Brackets: Provide four 10 gage 316 stainless steel
- brackets per unit for attachment to walls and ceilings,
- providing 4 inches of clearance between back of panel and
- mounting surface.
-
- C. Anchors and Fasteners: Provide aluminum fasteners for
- securing facing to framing members and for securing
- framing members to brackets; provide corrosion-resistant
- anchors for fastening to substrate, as recommended by
- panel manufacturer and approved by Architect.
-
-
- PART 3 EXECUTION
-
- 3.1 EXAMINATION
-
- A. Examine surfaces to receive work of this section. Do not
- begin installation until unsatisfactory conditions have
- been corrected.
-
- 3.2 INSTALLATION
-
- A. Install panels on walls and ceilings in locations and in
- patterns indicated on the drawings.
-
- B. Install each unit as indicated on shop drawings and in
- accordance with manufacturer's printed instructions,
- using approved anchors and fasteners.
-
- 3.3 ADJUST AND CLEAN
-
- A. After installation of acoustic panels, clean all dirty or
- discolored surfaces, using cleaning materials and methods
- acceptable to manufacturer. Replace damaged components
- as directed by the Architect.
-
- B. Remove debris caused by work of this section on a daily
- basis. At completion of acoustic panel installation,
- remove all crates, cartons, packages, and debris from the
- project site.
-
- END OF SECTION
-