- SECTION 07710
-
- MANUFACTURED ROOF SPECIALTIES
-
- NOTE ** This section is based on products manufactured by
- Marathon Roofing Products Inc., which is located at
- the following address:
- NOTE ** 367 Nagel Drive
- NOTE ** Buffalo NY 14225-4732
- NOTE ** Tel: (716) 685-3340
- NOTE ** Tel: (800) 828-8424
- NOTE ** Fax: (716) 685-1108
- NOTE ** Website: http://www.marathondrains.com
- NOTE ** E-mail: mrp@marathondrains.com
- NOTE **
- NOTE ** Marathon manufactures a complete line of roof
- drains and breather vents for new roofing,
- reroofing, and retrofit applications. Drain
- materials include copper, PVC, ABS, aluminum, and
- epoxy-coated cast iron. Vent materials include
- aluminum, copper, high-density polyethylene, and
- PVC. Custom products may be fabricated to suit
- almost any project condition, with factory
- assistance.
- NOTE **
- NOTE ** The section includes proprietary provisions for all
- types and styles of roof drains and breather vents,
- and must be edited to delete products and related
- provisions not required for a particular project.
- NOTE **
- NOTE ** SECTION 07710 - MANUFACTURED ROOF SPECIALTIES,
- Copyright 1998, The Architect's Catalog, Inc.
-
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
- NOTE ** Delete items below not required for project.
-
- A. Roof drains for new roofing.
-
- B. Roof drains for reroofing.
-
- C. Roof drains for retrofitting into existing roof drains.
-
- D. Roof vents and breathers.
-
- E. Soil vent stack flashings.
-
- 1.2 RELATED SECTIONS
- NOTE ** Delete any sections below not relevant to this
- project; add others as required.
-
- A. Section 07500 - Membrane Roofing.
-
- B. Section 07510 - Built-Up Bituminous Roofing.
-
- C. Section 07530 - Elastomeric Membrane Roofing.
-
- D. Section 07550 - Modified Bituminous Membrane Roofing.
-
- E. Section 07590 - Roof Maintenance and Repairs.
-
- F. Section 15150 - Sanitary Waste and Vent Piping.
-
- G. Section 15160 - Storm Drainage Piping.
-
- 1.3 SUBMITTALS
-
- A. Submit under provisions of Section 01300.
-
- B. Product Data: Provide manufacturer's standard details
- and installation instructions.
-
- 1.4 PROJECT CONDITIONS
-
- A. Obtain Material Safety Data Sheets (MSDS) from
- manufacturer if required.
-
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURER
-
- A. Provide prefabricated roof specialties fabricated by
- Marathon Roofing Products, Inc: 367 Nagel Drive, Buffalo
- NY 14225-4732; ASD. Tel: (716) 685-3340 or (800) 828-
- 8424; Fax: (716) 685-1108.
-
- B. Substitutions: Not permitted.
- NOTE ** Delete the following article if drains for new
- construction are not required.
-
- 2.2 FLANGE/PIPE DRAINS
-
- A. Marathon Premium Century Series Roof Drains:
- NOTE ** Select straight or funnel profile, as desired.
- NOTE **
- NOTE ** Straight profile with clamping ring (optional) is
- used when water cut off mastic is required and a
- greater clamping surface is needed by membrane
- manufacturer.
- NOTE **
- NOTE ** For EPDM or CSPE membranes, straight profile is
- recommended with clamping ring.
- NOTE **
- NOTE ** Delete profiles not required.
- 1. Straight profile, solid copper construction.
- 2. Straight profile, solid copper construction, with
- clamping ring.
- 3. Funnel profile, solid copper construction.
- NOTE ** Select uncoated flange for EPDM and CSPE membranes,
- primed flange for BUR and mod. bit. membranes, PVC-
- coated flange for PVC and CPE membranes. Delete
- two of the three coating options, below.
- 4. 18-inch (457 mm) diameter flange, 20 ounces per
- square foot (61 kg/sq m) copper.
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 5. Perforated copper gravel ring.
- NOTE ** HDPE strainer is standard, aluminum is optional.
- Delete one of the two materials, below.
- 6. Strainer: 10-inch (254 mm) diameter, bolted down.
- a. High density polyethylene.
- b. Cast aluminum alloy.
- NOTE ** Select applicable connection types. Delete those
- not required. All types are available in 2, 3, and
- 4 inch sizes. Plain and Fernco connections are
- also available in 6 inch size.
- 7. Connections: Pipe size as indicated on the drawings.
- a. Plain, 9-inch (228 mm) depth.
- b. Plain, 15-inch (381 mm) depth.
- c. Expansion coupler (Fernco) with stainless steel
- compression clamps; vertical or 90 degree outlet
- to suit project conditions, or as indicated.
- d. PVC hub (Conectite) fitting, vertical outlet only
- to suit project conditions, or as indicated.
-
- B. Marathon Economy Century Series Roof Drains:
- 1. Straight profile, solid copper construction.
- NOTE ** Select primed flange for BUR and mod. bit.
- membranes, PVC-coated flange for PVC and CPE
- membranes. (For EPDM and CSPE membranes, see
- Century Premium Series drains, below.) Delete one
- of the two coating options, below.
- 2. 14-inch (355 mm) diameter flange, 16 ounces per
- square foot (48.8 kg/sq m) copper.
- a. Primed for adhesion to asphaltic membranes.
- b. PVC-coated, for heat welded membrane attachment.
- 3. Perforated copper gravel ring.
- NOTE ** HDPE strainer is standard, aluminum is optional.
- Delete one of the two materials, below.
- 4. Strainer: 5-inch (127 mm) diameter.
- a. High density polyethylene.
- b. Cast aluminum alloy.
- NOTE ** Select applicable connection types. Delete those
- not required. All types are available in 2, 3, and
- 4 inch sizes.
- 5. Connections: Match pipe size O.D. as indicated on
- the drawings.
- a. Plain, 9-inch (228 mm) depth.
- b. Plain, 15-inch (381 mm) depth.
- c. Expansion coupler (Fernco) with stainless steel
- compression clamps; vertical or 90 degree outlet
- to suit project conditions, or as indicated.
- d. PVC hub (Conectite) fitting, vertical outlet to
- suit project conditions, or as indicated.
- NOTE ** Delete the following article if drains for
- retrofitting into existing drain bodies are not
- required. Diamond Series copper roof drains are
- appropriate to retrofit existing drains without
- removing existing drain or piping. These drains
- are simply and economically installed using rubber
- sealant and O-rings to create a friction fit.
- Where a mechanical seal is required, see
- "PROLINER", a flange/expansion-sleeve or
- flange/mechanical-seal drain, below. See also
- "COPPER-TITE," a sealed in-place retrofit drain.
-
- 2.3 FLANGE/INSERT RETROFIT DRAINS
-
- A. Marathon Diamond (75) Series Roof Drains:
- NOTE ** Select straight or funnel profile, as desired.
- Drain styles older than 1950 typically accept only
- straight profile.
- NOTE **
- NOTE ** Straight profile with clamping ring is used when
- water cut off mastic is required and a greater
- clamping surface is needed by membrane
- manufacturer.
- NOTE **
- NOTE ** For EPDM or CSPE membranes, straight profile is
- recommended with clamping ring.
- NOTE **
- NOTE ** Delete profiles not required.
- 1. Straight profile, solid copper construction. Flange:
- 14-inch (355 mm) diameter flange, 16 ounces per
- square foot (48.8 kg/sq m) copper for 2-inch (50 mm)
- through 4-inch (101 mm) drain sizes; 18-inch (457
- mm) diameter flange, 20 ounces per square foot (61
- kg/sq m) copper for 5-inch (127 mm) and 6-inch drain
- sizes.
- 2. Straight profile, solid copper construction, with
- bolted down clamping ring. Flange: 14-inch (355 mm)
- diameter flange, 16 ounces per square foot (48.8
- kg/sq m) copper for 2-inch (50 mm) through 4-inch
- (101 mm) drain sizes; 18-inch (457 mm) diameter
- flange, 20 ounces per square foot (61 kg/sq m) copper
- for 5-inch (127 mm) and 6-inch (152 mm) drain sizes.
- 3. Straight profile, solid copper construction, with
- clamping ring. Flange: 14-inch (355 mm) diameter
- flange, 16 ounces per square foot (48.8 kg/sq m)
- copper for 2-inch (50 mm) through 4-inch (101 mm)
- drain sizes; 18-inch (457 mm) diameter flange, 20
- ounces per square foot (61 kg/sq m) copper for 5-inch
- (127 mm) and 6-inch (152 mm) drain sizes.
- 4. Funnel profile, solid copper construction. Flange:
- 18-inch (457 mm) diameter flange, 20 ounces per
- square foot (61 kg/sq m) copper.
- NOTE ** Select uncoated flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated flange for PVC and CPE membranes. Delete
- two of the three coating options, below.
- 5. Flange coating:
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 6. Perforated copper gravel ring.
- 7. Strainer:
- NOTE ** Delete inapplicable strainer sizes, below.
- a. 5-inch (127 mm) diameter for straight profile 2-
- inch (50 mm) through 4-inch (101 mm) drain sizes.
- b. 10-inch (254 mm) diameter for straight profile 5-
- inch (127 mm) and 6-inch (152 mm) drain sizes.
- c. 10-inch (254 mm) diameter for funnel profile
- drains.
- NOTE ** HDPE strainer is standard, aluminum is optional.
- Delete one of the two materials, below.
- d. High density polyethylene.
- e. Cast aluminum alloy.
- NOTE ** Select applicable connection types. Delete those
- not required. Straight profile drains are
- available in 9 and 15-inch depths. Funnel profile
- drains are available in 12 and 18-inch depths. All
- types are available in 2, 3, 4, 5, and 6 inch
- sizes, and larger sizes upon request.
- 8. Connections: Pipe size as indicated on the drawings;
- diameter sized to slip inside of existing drain
- piping.
- a. Plain, 9-inch (228 mm) depth.
- b. Plain, 15-inch (381 mm) depth.
- c. Plain, 12-inch (304 mm) depth.
- d. Plain, 18-inch (457 mm) depth.
- NOTE ** Delete the following article if drains for
- retrofitting into existing drain bodies are not
- required. PROLINER Series roof drains with copper
- flange and malleable metal outlets are appropriate
- to retrofit existing drains without removing
- existing drain or piping, where a permanent
- mechanical seal between the new drain and the
- existing piping is required. The PROLINER tool is
- used to mechanically lock the PROLINER drain in
- place.
-
- 2.4 FLANGE/EXPANSION-SLEEVE RETROFIT DRAINS
-
- A. Marathon PROLINER Series.
- NOTE ** Select straight or funnel profile, as desired.
- Drain styles older than 1950 typically accept only
- straight profile.
- NOTE **
- NOTE ** Straight profile with clamping ring is used when
- water cut off mastic is required and a greater
- clamping surface is needed by membrane
- manufacturer.
- NOTE **
- NOTE ** For EPDM or CSPE membranes, straight profile is
- recommended with clamping ring.
- NOTE **
- NOTE ** Delete profiles not required.
- 1. Straight profile.
- 2. Straight profile, with clamping ring.
- 3. Funnel profile.
- NOTE ** Select uncoated flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated flange for PVC and CPE membranes. Delete
- two of the three coating options, below.
- 4. Flange: 18-inch (457 mm) diameter flange, 20 ounces
- per square foot (61 kg/sq m) copper.
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 5. Perforated copper gravel ring.
- NOTE ** HDPE strainer is standard, aluminum is optional.
- Delete one of the two materials, below.
- 6. Strainer: 10-inch (254 mm) diameter.
- a. High density polyethylene.
- b. Cast aluminum alloy.
- NOTE ** Outlets are available to retrofit standard 3, 4, 5,
- and 6-inch sizes and other non-standard sizes.
- 7. Outlet: Malleable metal alloy. Pipe size as
- indicated on the drawings; diameter sized to slip
- inside of existing drain piping, with 1/4-inch (6 mm)
- maximum difference between existing pipe I.D. and
- outlet O.D.
- NOTE ** Delete the following article if drains for
- retrofitting into existing drain bodies are not
- required. ProSeal Series roof drains with copper
- flange and mechanical compression seal are
- appropriate to retrofit existing drains without
- removing existing drain or piping, where a
- permanent mechanical seal between the new drain and
- the existing piping is required.
-
- 2.5 FLANGE/MECHANICAL-SEAL RETROFIT DRAINS
-
- A. Marathon Copper-Tite Series Roof Drains:
- NOTE ** Select straight or funnel profile, as desired.
- Drain styles older than 1950 typically accept only
- straight profile.
- NOTE **
- NOTE ** Straight profile with clamping ring is used when
- water cut off mastic is required and a greater
- clamping surface is needed by membrane
- manufacturer.
- NOTE **
- NOTE ** For EPDM or CSPE membranes, straight profile is
- recommended with clamping ring.
- NOTE **
- NOTE ** Delete profiles not required.
- 1. Straight (CTS) profile.
- 2. Straight profile with clamping ring.
- 3. Funnel (CTF) profile.
- NOTE ** Select plain flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated flange for PVC and CPE membranes. Delete
- two of the three finish options, below.
- 4. Flange: 20 ounces per square foot (61 kg/sq m)
- copper.
- a. Plain finish
- b. Asphalt primed finish.
- c. PVC-coated finish.
- NOTE ** Flange size is 14 inches (356 mm) in diameter for
- 2, 3, and 4-inch (51, 76, and 102 mm) straight
- (CTS) drains, 18 inches (457 mm) in diameter for
- all others. Delete one of the two sizes, below.
- 5. Flange size: 14 inches (356 mm).
- 6. Flange size: 18 inches (457 mm).
- NOTE ** Plastic strainer is standard, aluminum is optional.
- Delete one of the two materials, below.
- 7. Strainer: Plastic.
- 8. Strainer: Aluminum.
- NOTE ** For straight (CTS) drains, 9-inch (229 mm) long
- outlets are available to retrofit standard 2, 3, 4,
- 5, 6, and 8-inch (51, 76, 102, 127, 152, and 203
- mm) drain pipes; drain outlets may be ordered
- extended by 6 inches (152 mm).
- NOTE **
- NOTE ** For straight drains with clamping ring, 9-inch (229
- mm) long outlets are available to retrofit standard
- 2, 3, 4, 5, and 6-inch (51, 76, 102, 127, and 152
- mm) drain pipes; drain outlets may be ordered
- extended by 6 inches (152 mm).
- NOTE **
- NOTE ** For funnel (CTF) drains, 12-inch (305 mm) long
- outlets are available to retrofit standard 2, 3, 4,
- 5, and 6-inch (51, 76, 102, 127, and 152 mm) drain
- pipes; drain outlets may be ordered extended by 6
- inches (152 mm).
- 9. Outlet: Copper outlet with 2-inch (51 mm) wide
- asphalt-impregnated high density expanding foam
- compression seal. Pipe size as indicated on the
- drawings; diameter sized to slip inside of existing
- drain piping, with 1/4-inch (6 mm) maximum difference
- between existing pipe I.D. and outlet O.D.
-
- B. Marathon ProSeal Series Roof Drains:
- NOTE ** Select straight or funnel profile, as desired.
- Drain styles older than 1950 typically accept only
- straight profile.
- NOTE **
- NOTE ** Straight profile with clamping ring is used when
- water cut off mastic is required and a greater
- clamping surface is needed by membrane
- manufacturer.
- NOTE **
- NOTE ** For EPDM or CSPE membranes, straight profile is
- recommended with clamping ring.
- NOTE **
- NOTE ** Delete profiles not required.
- 1. Straight profile.
- 2. Straight profile, with clamping ring.
- 3. Funnel profile.
- NOTE ** Select uncoated flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated flange for PVC and CPE membranes. Delete
- two of the three coating options, below.
- 4. Flange: 18-inch (457 mm) diameter flange, 20 ounces
- per square foot (61 kg/sq m) copper.
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 5. Perforated copper gravel ring.
- NOTE ** HDPE strainer is standard, aluminum is optional.
- Delete one of the two materials, below.
- 6. Strainer: 10-inch (254 mm) diameter.
- a. High density polyethylene.
- b. Cast aluminum alloy.
- NOTE ** Outlets are available to retrofit standard 3, 4, 5,
- and 6-inch sizes.
- 7. Outlet: Copper outlet with elastomeric mechanical
- compression seal. Pipe size as indicated on the
- drawings; diameter sized to slip inside of existing
- drain piping, with 1/4-inch (6 mm) maximum difference
- between existing pipe I.D. and outlet O.D.
- NOTE ** Delete the following article if mechanical drains
- are not required.
- NOTE ** ULRD drains (PVC or ABS body), RD-1 and RD-10
- drains (epoxy-coated cast iron body) are suitable
- for most single ply and conventional built-up
- roofing membranes and with roof decks of steel,
- wood, precast concrete, and gypsum.
- 2.6 MECHANICAL DRAINS
- NOTE ** Select either PVC, ABS, or epoxy-coated cast iron
- drain body. Delete inapplicable paragraphs, below.
-
- A. Marathon ULRD (Utility Large Roof Drain): Injection
- molded PVC drain body with solvent-weld style outlet.
-
- B. Marathon ULRD (Utility Large Roof Drain): Injection
- molded ABS drain body with solvent-weld style outlet.
-
- C. Marathon RD-1: Epoxy-coated standard size cast iron
- drain body with no-hub style outlet.
-
- D. Marathon RD-10: Epoxy-coated large size cast iron drain
- body with no-hub style outlet.
- E. Construction:
- NOTE ** Select either polyethylene or metal strainer,
- below. Delete any other construction features that
- are not required.
- 1. Strainer: Molded polyethylene dome.
- 2. Strainer: Epoxy-coated metal dome.
- 3. Clamping ring: Epoxy-coated aluminum.
- 4. Underdeck clamp: Aluminum
- 5. Adjustable insulation extension flange: Match
- insulation thickness.
- 6. Bearing pan.
- 7. Waterproofing flange.
- 8. Flow-control device.
- 9. Flexible expansion coupling with stainless steel band
- clamps.
- NOTE ** PVC and ABS drains are available in 3, 4, and 6-
- inch sizes. Cast iron drains are available in 3,
- 4, 6, and 8-inch sizes.
-
- F. Pipe size as indicated on the drawings.
- NOTE ** Delete the following article if parapet/scupper
- drains are not required.
-
- 2.7 PARAPET SCUPPER DRAINS
-
- A. Marathon RD-27.
-
- B. Construction:
- 1. Cast aluminum grate, body, and outlet.
- 2. Reversible hub connection for 45 or 90-degree outlet.
- NOTE ** Select either angled grate (standard) or flat grate
- (optional).
- 3. Angled grate.
- 4. Flat grate.
- NOTE ** Select either red epoxy paint finish (standard) or
- nickel bronze finish.
- 5. Red epoxy finish.
- 6. Nickel bronze finish.
- NOTE ** Delete the following article if roof vents are not
- required.
-
- 2.8 ROOF VENTS AND BREATHERS
- NOTE ** Select type of vents desired from paragraphs below.
- Delete those that are not required.
- NOTE **
- NOTE ** Vents are designed to assist in relieving pressure
- created by moisture in lightweight insulating
- concrete materials, and for venting conventional
- roofing insulation.
-
- A. Solar Powered Roof Vent: Marathon Sol-A-Vent; continuous-
- operation exhaust fan powered by 4 inch (100 mm) diameter
- photoelectric cell and battery.
- 1. Battery: Rechargeable NiCad battery charged by cell
- capable of powering fan for 3 overcast days and
- nights.
- 2. Minimum capacity: 900 cubic feet (25 cu m) per hour.
- 3. Housing: Aluminum; flanged for flashing into
- roofing, adjustable pitch to adapt to sloped roofs.
- NOTE ** Delete one of the following two paragraphs. Chrome
- plated cap is an option at extra cost.
- 4. Cap: Same as housing.
- 5. Cap: Chrome plated.
- 6. Housing diameter: 8-3/4 inches (222 mm).
- 7. Height: 8 inches (203 mm).
- NOTE ** Delete the following if not applicable -- applies
- to aluminum only.
- 8. Flange: Asphalt-coated.
-
- B. Marathon Aluminum Insulvent:
- 1. Heavy gage spun aluminum.
- 2. Secured cap to prevent entry of wind-blown rain or
- snow.
- 3. 4-inch (101 mm) diameter base opening.
- 4. 10-3/4 inch (273 mm) diameter flange.
- NOTE ** Select uncoated flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated for PVC membranes. Delete all but one of
- the coating options, below.
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 5. 8-1/2 inches overall height.
- NOTE ** Select either one or two-way design. Delete
- optional insulation if not required.
- 6. One-way valve to prevent moisture re-entry.
- 7. Two-way design to allow both exhaust and convective
- air movement to create equalized pressure.
- 8. Expanded polystyrene foam insulation, to prevent
- condensation.
- NOTE ** In the following paragraph, select either Medium
- Capacity or Large Capacity.
-
- C. Marathon Aluminum MC (Medium Capacity) and LC (Large
- Capacity) Vent:
- 1. Heavy gage spun aluminum.
- 2. Secured cap to prevent entry of wind-blown rain or
- snow.
- 3. MC: 8-inch (203 mm) diameter base opening and 10-inch
- (254 mm) diameter flange.
- 4. LC: 10-inch (254 mm) diameter base opening and 12-
- inch (304 mm) diameter flange.
- NOTE ** Select uncoated flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated for PVC membranes. Delete all but one of
- the coating options, below.
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 5. MC: 6-1/2 inches (165 mm) overall height.
- 6. LC: 8 inches (203 mm) overall height.
- NOTE ** Select either one or two-way design. Delete
- optional insulation if not required.
- 7. One-way valve to prevent moisture re-entry.
- 8. Two-way design to allow both exhaust and convective
- air movement to create equalized pressure.
- 9. Expanded polystyrene foam insulation.
-
- D. Marathon Aluminum SC Vent (Small Capacity):
- 1. Heavy gage spun aluminum.
- 2. Secured cap to resist vandals.
- 3. 2-7/8-inch (73 mm) diameter base opening.
- 4. 6-inch (152 mm) diameter flange.
- NOTE ** Select uncoated flange for EPDM membranes, primed
- flange for BUR and modified bitumen membranes, PVC-
- coated for PVC membranes. Delete all but one of
- the coating options, below.
- a. Uncoated.
- b. Primed for adhesion to asphaltic membranes.
- c. PVC-coated, for heat welded membrane attachment.
- 5. 4-1/4 inches (108 mm) overall height.
- NOTE ** Select either one or two-way design.
- 6. One-way valve to prevent moisture re-entry.
- 7. Two-way design to allow both exhaust and convective
- air movement to create equalized pressure.
-
- E. Marathon Ex-Flow Insulation Vent:
- NOTE ** Select either HDPE for bituminous membranes, or PVC
- for PVC and urethane foam membranes.
- 1. High density polyethylene construction.
- 2. PVC construction.
- 3. Secured cap to prevent entry of wind-blown rain or
- snow.
- 4. 5-1/4-inch (133 mm) diameter base opening.
- 5. 10-1/2-inch (266 mm) diameter flange.
- 6. 8 inches (203 mm) overall height.
- 7. One-way valve to prevent moisture re-entry.
-
- 2.9 SOIL VENT STACK FLASHINGS
-
- A. Marathon High Security Vent Stack Flashing:
- 1. Lead-free, tamper-resistant construction.
- 2. Heavy gage spun aluminum.
- 3. 7-inch (177 mm) diameter base opening; 4-inch (101
- mm) DWV pipe capacity with hub.
- 4. 15-1/4-inch (387 mm) diameter flange.
- 5. 15-1/4 inches (387 mm) overall height.
-
-
- PART 3 EXECUTION
-
- 3.1 EXAMINATION
-
- A. Verify that dimensions are correct and substrate is in
- proper condition for installation. Correct
- unsatisfactory conditions before proceeding with
- installation.
-
- B. Verify elevation of drain to provide positive drainage.
- NOTE ** Delete the following article if no retrofit drains
- are required.
-
- 3.2 PREPARATION
-
- A. Remove bitumen, gravel, debris, adhesives, etc., from
- existing drain and pipe inlet. Ensure that surface of
- drain and pipe inlet is clean and dry; employ hot air
- gun if necessary to remove moisture. Verify that I.D. of
- existing drain does not exceed O.D. of new outlet by more
- than 1/4 inch (6 mm).
-
- B. Verify that deck opening is sufficient to accommodate the
- O.D. of connector. Where large existing drain bowl is
- encountered use funnel profile. If using new straight
- profile drain, provide support for the flange by
- installing 1/2 inch (12 mm) pressure-preservative-treated
- plywood, rigid high compressive strength insulation, or
- by filling bowl with spray polyurethane foam.
-
- 3.3 ROOF DRAIN INSTALLATION
- NOTE ** Retain installation paragraphs below of products
- specified in Part 2. Delete inapplicable
- paragraphs.
-
- A. Flange Drains:
- 1. Set flange in a full bed of mastic or adhesive, and
- mechanically fasten flange through roofing assembly
- to the deck.
- 2. Strip in drain flange in accordance with membrane
- manufacturer's instructions.
- NOTE ** Delete one or both the following paragraphs if
- inapplicable.
- 3. Do not allow flame of torch used to apply modified
- bitumen to come in contact with flange.
- 4. Hand tighten clamping ring with 7/16-inch (11 mm)
- hand wrench.
-
- 3.4 ROOF DRAIN OUTLET CONNECTIONS
- NOTE ** Retain connection instructions, below, applicable
- to roof drains specified in Part 2. Delete
- inapplicable paragraphs.
- NOTE **
- NOTE ** Connection of drain outlets to new or existing
- piping must be specified either in this section, or
- in Division 15. Mechanical drains are commonly
- installed by plumbing trades. Retrofit-style
- drains are commonly installed by roofing trades.
-
- A. Flange/Pipe Roof Drains:
- NOTE ** Of the three paragraphs, below, retain only those
- outlet styles that have been retained in Part 2,
- above.
- 1. Connect to piping in accordance with provisions
- specified in Division 15.
- 2. Expansion connections: Hand tighten compression
- bands with torque wrench calibrated to 60 inch-pounds
- (759,600 N m). Adjust if required to make water
- tight.
- 3. PVC hub fittings: Solvent weld using compatible
- solvent cement in accordance with manufacturer's
- instructions to achieve a water tight connection.
-
- B. Flange/Sleeve Drains:
- 1. Set drain outlet inside of existing drain, using
- rubber type sealant and O-rings to ensure a water-
- tight connection between drain and existing pipe.
-
- C. Flange/Expansion-Sleeve Drains:
- 1. Apply sealant to outlet and existing drain leader.
- Apply an additional amount to top inside of existing
- drain pipe. Spread sealant evenly around whole
- outlet, extending at least 5 inches (127 mm) up lower
- portion.
- 2. Set drain outlet inside of existing drain.
- 3. Expand malleable metal outlet at beginning at top of
- drain pipe and leaving 1 inch (25 mm) distance
- between expansions. Use Proliner Expander Tool Kit
- with properly sized accessories. Use 12 half-turns
- for 3-inch (76 mm) and 4-inch (101 mm) diameter
- drains, and 9 half-turns for 5-inch (127 mm) and 6-
- inch (152 mm) diameter drains. Verify that outlet
- has been sufficiently expanded to ensure a water-
- tight connection between drain and existing pipe.
- Adjust if necessary.
-
- D. Flange/Mechanical-Seal Retrofit Drains:
- 1. Set drain outlet inside of existing drain.
- 2. Uniformly tighten the 3 seal screws until quite snug
- to ensure a water-tight connection between drain and
- existing pipe.
-
- E. Mechanical Drains:
- NOTE ** Of the three paragraphs, below, retain only those
- outlet styles that have been retained in Part 2,
- above.
- 1. Connect to piping in accordance with provisions
- specified in Division 15.
- 2. Expansion connections: Hand tighten compression
- bands with torque wrench calibrated to 60 inch-pounds
- (759,600 N m). Adjust if required to make water
- tight.
- 3. PVC hub fittings: Solvent weld using compatible
- solvent cement in accordance with manufacturer's
- instructions to achieve a water tight connection.
-
- F. Parapet/Scupper Drains: Connect to piping in accordance
- with provisions specified in Division 15.
-
- G. Install strainer domes.
- NOTE ** Delete the following article if roof vents are not
- required.
-
- 3.5 ROOF VENT INSTALLATION
- NOTE ** Delete the following paragraph if vents are
- installed in new membranes only.
-
- A. Existing Membranes: Remove bitumen, gravel, debris,
- adhesives, etc., from area to receive vent.
-
- B. Core through membrane and insulation to deck.
- 1. Do not disturb vapor barrier, if any.
- 2. Set flange in a full bed of mastic or adhesive.
- 3. Strip in vent flange in accordance with membrane
- manufacturer's instructions.
- NOTE ** Delete the following paragraph if inapplicable.
- 4. Do not allow flame of torch used to apply modified
- bitumen to come in contact with flange.
- NOTE ** Delete the following article if soil vent stack
- flashings are not required.
-
- 3.6 SOIL VENT STACK FLASHING INSTALLATION
-
- A. Set flange in a full bed of mastic or adhesive.
- 1. Strip in stack flange in accordance with membrane
- manufacturer's instructions.
- NOTE ** Delete the following paragraph if inapplicable.
- 2. Do not allow flame of torch used to apply modified
- bitumen to come in contact with flange.
-
- 3.7 CLEANING AND PROTECTION
-
- A. Clean work area of debris associated with roofing
- specialties.
-
- B. Protect finished work.
-
-
- END OF SECTION
-