  1.                          SECTION 07221
  2.  
  3.                         ROOF INSULATION
  4.  
  5. NOTE ** This section is based on the MI-T-R roof insulation
  6.         system as manufactured by Mizell Bros. Co., located
  7.         at 99 Armour Drive, NE; Atlanta, GA  30324.
  8.         Telephone:  800-328-5401 or 404-875-9361.
  9. NOTE **
  10. NOTE ** The system employs flexible faced glass fiber
  11.         insulation, with a variety of vapor retarders.  The
  12.         patented construction of the MI-T-R high
  13.         performance insulation ensures high thermal
  14.         efficiency in values from R-19 to R-40.  Easily
  15.         installed from the top side, the system is
  16.         especially designed and manufactured to fit the
  17.         spaces in a particular building.  Installation
  18.         requires no special tools or training.  MI-T-R even
  19.         keeps purlins or bar joists exposed for subsequent
  20.         installation of electrical and mechanical systems -
  21.         - without compromising the integrity of the vapor
  22.         retarder.
  23. NOTE **
  24. NOTE ** SECTION 07221 - ROOF INSULATION, Copyright 1996,
  25.         The Architect's Catalog, Inc.
  26.  
  27. PART 1  GENERAL
  28.  
  29. 1.1 SECTION INCLUDES
  30. NOTE ** Delete items below not required for project.
  31.  
  32.     A.  Roof insulation and installation.
  33.  
  34.     B.  Support system and installation.
  35.  
  36. 1.2 RELATED SECTIONS
  37. NOTE ** Delete any sections below not relevant to this
  38.         project; add others as required.
  39.  
  40.     A.  Section 05120 - Structural Steel.
  41.  
  42.     B.  Section 05210 - Steel Joists.
  43.  
  44.     C.  Section 07213 - Batt Insulation.
  45.  
  46.     D.  Section 07421 - Composite Metal Building Panels.
  47.  
  48.     E.  Section 07611 - Custom Sheet Metal Roofing.
  49.  
  50.     F.  Section 13121 - Pre-Engineered Buildings.
  51.  
  52. 1.3 REFERENCES
  53. NOTE ** Delete references from the list below that are not
  54.         actually required by the text of the edited
  55.         section.
  56.  
  57.     A.  ASTM C 236 - Standard Test Method for Steady-State
  58.         Thermal Performance of Building Assemblies by Means of a
  59.         Guarded Hot Box.
  60.  
  61.     B.  ASTM C 518 - Standard Test Method for Steady-State Heat
  62.         Flux Measurements and Thermal Transmission Properties by
  63.         Means of the Heat Flow Meter Apparatus.
  64.  
  65.     C.  ASTM E 84 - Standard Test Method for Surface Burning
  66.         Characteristics of Building Materials.
  67.  
  68.     D.  ASTM E 96 - Standard Test Methods for Water Vapor
  69.         Transmission of Materials.
  70.  
  71.     E.  FS HH-I-558B - Insulation, Blocks, Boards, Blankets,
  72.         Felts, Sleeving, (Pipe and Tube Covering), and Pipe
  73.         Fitting Covering, Thermal (Mineral Fiber, Industrial
  74.         Type).
  75.  
  76. 1.4 SUBMITTALS
  77.  
  78.     A.  Submit under provisions of Section 01300.
  79.  
  80.     B.  Product Data:  Manufacturer's specifications and
  81.         installation instructions.
  82.  
  83.     C.  Shop Drawings:  Include layout and location of structural
  84.         steel roof framing members, details and locations of
  85.         support system components, and specific data about
  86.         insulation, including:
  87.         1.  R value.
  88.         2.  Approximate thickness.
  89.         3.  Facing type.
  90.         4.  Roll widths.
  91.         5.  Lengths and locations.
  92.  
  93. 1.5 REGULATORY REQUIREMENTS
  94. NOTE ** If this article is retained, select one of the two
  95.         following paragraphs.
  96.  
  97.     A.  Conform to requirements of local building code.
  98.  
  99.     B.  Conform to requirements of ___________________.
  100.  
  101. 1.6 DELIVERY, STORAGE, AND HANDLING
  102.  
  103.     A.  Deliver materials in manufacturer's original, unopened
  104.         packaging, with identifying tags or labels intact and
  105.         legible.
  106.  
  107.     B.  Coordinate scheduling for timely deliveries and prompt
  108.         installation of materials.
  109.  
  110.     C.  Store insulation and support system in a dry, protected
  111.         area.  If storage area is outdoors, store material off
  112.         the ground and protected by a suitable waterproof cover.
  113.         If installation is delayed for an extended period, open
  114.         bag ends to allow for ventilation.
  115.  
  116. 1.7 ENVIRONMENTAL REQUIREMENTS
  117.  
  118.     A.  Handle and install insulation system only under
  119.         conditions and temperatures that allow the facing
  120.         material to remain workable.
  121.  
  122.     B.  Coordinate insulation placement to assure that material
  123.         can be covered promptly with roof panels.  Do not leave
  124.         insulation exposed overnight or to inclement weather.
  125.  
  126. 1.8 WARRANTY
  127.  
  128.     A.  Provide manufacturer's standard warranty, in accordance
  129.         with requirements of Section 01740 - Warranties.
  130.  
  131. PART 2  PRODUCTS
  132.  
  133. 2.1 MANUFACTURER
  134.  
  135.     A.  Products of this section are based on the MI-T-R roof
  136.         insulation system as manufactured by Mizell Bros. Co.,
  137.         located at 99 Armour Drive N.E., Atlanta Georgia  30324.
  138.         Telephone:  404-875-9361.
  139.         1.  Substitutions are not acceptable.
  140.  
  141. 2.2 MATERIALS
  142.  
  143.     A.  Insulation:
  144. 1.      Comply with FS HH-I-558, Form B, Type 1, Class
  145.         6.NOTE ** Select only one of the following seven
  146.         options to specify insulation resistance or
  147.         thickness.
  148.  
  149.         2.  Provide thermal resistance (R) of 19 and a calculated
  150.             transmittance (U Value) of 0.05, as determined by
  151.             ASTM C 518.
  152. 3.      Provide thermal resistance (R) of 26 and a
  153.         calculated transmittance (U Value) of 0.04, as
  154.         determined by ASTM C 518.NOTE ** ASTM C 236 Test
  155.         Results for MI-T-R System
  156. NOTE **
  157. NOTE ** Standing Seam Roof Panels:            6 inch (R19)
  158.         8 inch (R26)
  159. NOTE **   Fasteners @ 24 in, w/thermal blocks      .051
  160.         .044
  161. NOTE **   Fasteners @ 24 in, w/o thermal blocks    .059
  162.         .055
  163. NOTE **
  164. NOTE ** Screw Down Roof Panels:
  165. NOTE **  *Fasteners @ 12 in, w/thermal blocks      .053
  166.         .043
  167. NOTE **   Fasteners @ 12 in, w/o thermal blocks    .082
  168.         .065
  169. NOTE **
  170. NOTE ** * Specify only as approved by building
  171.         manufacturer.
  172.  
  173.         4.  Provide thermal resistance (R) of 30 and a calculated
  174.             transmittance (U Value) of 0.03, as determined by
  175.             ASTM C 518.
  176.         5.  Provide thermal resistance (R) of 31 and a calculated
  177.             transmittance (U Value) of 0.03, as determined by
  178.             ASTM C 518.
  179.         6.  Provide thermal resistance (R) of 36 and a calculated
  180.             transmittance (U Value) of 0.027, as determined by
  181.             ASTM C 518.
  182. 7.      Provide thermal resistance (R) of 38 and a
  183.         calculated transmittance (U Value) of 0.025, as
  184.         determined by ASTM C 518.NOTE ** MI-T-R PROPERTIES
  185. NOTE **
  186. NOTE ** Thickness        R Value        U Value
  187.         (Calculated)
  188. NOTE **              Winter Summer   Non-Reflective
  189.         Reflective
  190. NOTE **                              Winter Summer  Winter
  191.         Summer
  192. NOTE **    6"        20.9    19.03    .047   .050    .046
  193.         .046
  194. NOTE **    8"        27.48   25.03    .036   .039    .035
  195.         .036
  196. NOTE **    9"        31.87   29.06    .031   .034    .031
  197.         .032
  198. NOTE **   10"        32.96   30.03    .030   .033    .030
  199.         .031
  200. NOTE **   11"        38.42   35.09    .026   .028    .026
  201.         .027
  202. NOTE **   12"        39.52   36.06    .025   .027    .025
  203.         .026
  204.  
  205.         8.  Thickness:  Approximately __ inches, providing a
  206.             composite U Value of ____, determined in accordance
  207.             with ASTM C 236, using 8 inch Z purlins 60 inches on
  208.             center, fasteners at ___ inches on center, [with]
  209.             [without] foam blocks, 45 degrees F mean temperature
  210.             corrected to 15 mph wind outside, heat flow up, non-
  211.             reflective facing.
  212. NOTE ** Select one of the following twelve vapor barrier
  213.         options and delete the others.
  214.  
  215.         9.  Vapor Barrier:  Face one side of insulation with
  216.             white vinyl reinforced polyester having a maximum
  217.             perm rating of 0.02 as determined in accordance with
  218.             ASTM E 96.
  219.         10. Vapor Barrier:  Face one side of insulation with
  220.             white vinyl scrim polyester, having a maximum perm
  221.             rating of 0.02 as determined in accordance with ASTM
  222.             E 96.
  223.         11. Vapor Barrier:  Face one side of insulation with
  224.             standard duty foil scrim kraft, having a maximum perm
  225.             rating of 0.02 as determined in accordance with ASTM
  226.             E 96.
  227.         12. Vapor Barrier:  Face one side of insulation with UV
  228.             stabilized white polypropylene/scrim/foil, having a
  229.             maximum perm rating of 0.02 as determined in
  230.             accordance with ASTM E 96.
  231.         13. Vapor Barrier:  Face one side of insulation with
  232.             heavy duty vinyl scrim foil, having a maximum perm
  233.             rating of 0.02 as determined in accordance with ASTM
  234.             E 96.
  235.         14. Vapor Barrier:  Face one side of insulation with
  236.             standard duty vinyl scrim foil, having a maximum perm
  237.             rating of 0.02 as determined in accordance with ASTM
  238.             E 96.
  239.         15. Vapor Barrier:  Face one side of insulation with
  240.             heavy duty polypropylene scrim kraft, having a
  241.             maximum perm rating of 0.02 as determined in
  242.             accordance with ASTM E 96.
  243.         16. Vapor Barrier:  Face one side of insulation with
  244.             standard duty polypropylene scrim kraft, having a
  245.             maximum perm rating of 0.02 as determined in
  246.             accordance with ASTM E 96.
  247.         17. Vapor Barrier:  Face one side of insulation with
  248.             light duty foil scrim kraft, having a maximum perm
  249.             rating of 0.03 as determined in accordance with ASTM
  250.             E 96.
  251.         18. Vapor Barrier:  Face one side of insulation with
  252.             white polypropylene scrim kraft, having a maximum
  253.             perm rating of 0.090 as determined in accordance with
  254.             ASTM E 96.
  255.         19. Vapor Barrier:  Face one side of insulation with
  256.             white vinyl reinforced vinyl, having a maximum perm
  257.             rating of 0.90 as determined in accordance with ASTM
  258.             E 96.
  259.         20. Vapor Barrier:  Face one side of insulation with
  260.             white vinyl, having a maximum perm rating of 1.0 as
  261.             determined in accordance with ASTM E 96.
  262.         21. Surface Burning Characteristics:  Provide assembly of
  263.             facing, adhesive, and glass fiber blanket with
  264.             composite flame spread rating of 25 or less and smoke
  265.             developed of 50 or less, as determined in accordance
  266.             with ASTM E 84.
  267.  
  268.     B.  Support System
  269.         1.  Hangers and Stirrups:  Preformed 26 gage galvanized
  270.             steel, 7/8 inches wide, with prepunched holes,
  271.             factory-applied white coating, and pressure-sensitive
  272.             foam tape factory-applied to inside face.
  273.             a.  Depth:  4 inches for R19 insulation.
  274.             b.  Depth:  6 inches for R26 insulation.
  275.             c.  Depth:  7 inches for R30 insulation.
  276.             d.  Depth:  7 inches for R31 insulation.
  277.             e.  Depth:  7 inches for R36 insulation.
  278.             f.  Depth:  7 inches for R38 insulation.
  279.         2.  Channels:  Preformed 26 gage galvanized steel, die
  280.             formed and sheared to length, with slotted hole 1
  281.             inch from each end for attachment to hangers and
  282.             stirrups, and factory-applied white coating.
  283.         3.  Fasteners:  Manufacturer's standard nylon and
  284.             electrostatically galvanized splice fasteners and
  285.             washers.
  286.  
  287. PART 3  EXECUTION
  288.  
  289. 3.1 EXAMINATION
  290.  
  291.     A.  Verify that roof framing system is complete and ready to
  292.         receive insulation system.  Do not proceed with
  293.         installation until unsatisfactory conditions have been
  294.         corrected.
  295.  
  296. 3.2 INSTALLATION
  297.  
  298.     A.  Install roof insulation in strict accordance with
  299.         manufacturer's instructions and approved shop drawings.
  300. NOTE ** The following two paragraphs are optional and
  301.         should be deleted if foam thermal blocks are not
  302.         required for project.  If foam blocks are required,
  303.         select appropriate paragraph and delete the other.
  304.  
  305.     B.  Install one inch thick thermal blocks of extruded
  306.         polystyrene on top of glass fiber tab and between
  307.         standing seam roof panel clips.
  308.  
  309.     C.  Install one inch thick thermal blocks of extruded
  310.         polystyrene in accordance with instructions provided by
  311.         roof panel manufacturer.
  312.  
  313.                          END OF SECTION