home *** CD-ROM | disk | FTP | other *** search
/ Spec Disk 1998 Spring 4.0 / Spec Disk 1998 Spring 4.0.iso / text / 06072hix.txt < prev    next >
Encoding:
Text File  |  1998-06-10  |  12.0 KB  |  304 lines

  1.                          SECTION 06072
  2.  
  3.               FIRE-RETARDANT TREATED WOOD PRODUCTS
  4.  
  5. NOTE ** This section is based on DRICON fire retardant
  6.         treated wood products nationally manufactured under
  7.         license from Hickson Corporation.  For the name and
  8.         location of licensees, contact Hickson at:
  9. NOTE **     Hickson Corporation
  10. NOTE **     3941 Bonsal Road
  11. NOTE **     Conley, GA 30027
  12. NOTE **     Tel:  (404) 362-3970
  13. NOTE **     Fax:  (404) 363-8585
  14. NOTE **
  15. NOTE ** DRICON fire retardant treated wood products are UL
  16.         listed Class A/Class I flame spread, and are
  17.         treated with EPA registered fire, fungus, and
  18.         termite retardant chemicals.
  19. NOTE **
  20. NOTE ** SECTION 06072 - FIRE-RETARDANT TREATED WOOD
  21.         PRODUCTS, Copyright 1997, The Architect's Catalog,
  22.         Inc.
  23.  
  24. PART 1  GENERAL
  25.  
  26. 1.1 SECTION INCLUDES
  27. NOTE ** Delete items below not required for project.
  28.  
  29.     A.  Fire Retardant Treated Dimension Lumber.
  30.  
  31.     B.  Fire Retardant Treated Plywood.
  32.  
  33. 1.2 RELATED SECTIONS
  34. NOTE ** Delete any sections below not relevant to this
  35.         project; add others as required.
  36. NOTE **
  37.     A.  Section 06100 - Rough Carpentry.
  38.  
  39.     B.  Section 06112 - Framing and Sheathing.
  40.  
  41.     C.  Section 06114 - Wood Blocking and Curbing.
  42.  
  43.     D.  Section 06200 - Finish Carpentry.
  44.  
  45.     E.  Section 06075 - Preservative Treatment for Wood.
  46.  
  47. 1.3 REFERENCES
  48. NOTE ** Delete references from the list below that are not
  49.         actually required by the text of the edited
  50.         section.
  51.  
  52.     A.  American Lumber Standard Committee - Softwood Lumber
  53.         Standards.
  54.  
  55.     B.  APA - Design and Construction Guide for Residential and
  56.         Commercial Uses; APA - The Engineered Wood Association.
  57.  
  58.     C.  AWPA C20 - Structural Lumber--Fire Retardant Treatment by
  59.         Pressure Processes; American Wood-Preservers'
  60.         Association.
  61.  
  62.     D.  AWPA C27 - Plywood Fire Retardant Treatment by Pressure
  63.         Process; American Wood-Preservers' Association.
  64.  
  65.     E.  AWPA P17 - Fire Retardant Formulations; American Wood-
  66.         Preservers' Association.
  67.  
  68.     F.  ASTM E 84 - Standard Test Method for Surface Burning
  69.         Characteristics of Building Materials.
  70.  
  71.     G.  MS MIL-L-19140 - Fire Retardant Wood Preservative
  72.         Chemicals.
  73.  
  74.     H.  NFPA 255 - Standard Method of Test for Surface Burning
  75.         Characteristics of Building Materials.
  76.  
  77.     I.  NLGA - Grading Rules; National Lumber Grades Authority.
  78.  
  79.     J.  SPIB - Standard Grading Rules for Southern Pine Lumber;
  80.         Southern Pine Inspection Bureau.
  81.  
  82.     K.  UL 723 - Standard Method of Test for Surface Burning
  83.         Characteristics of Building Materials.
  84.  
  85.     L.  WCLB - Standard Grading and Dressing Rules; West Coast
  86.         Lumber Inspection Bureau.
  87.  
  88.     M.  WWPA - Western Lumber Grading Rules; Western Wood
  89.         Products Association.
  90.  
  91. 1.4 SUBMITTALS
  92.  
  93.     A.  Submit under provisions of Section 01300.
  94.  
  95.     B.  Product Data:
  96.         1.  Manufacturer's printed literature indicating product
  97.             compliance to specified requirements.
  98.         2.  Manufacturer's recommendations for storage and
  99.             protection of product on site.
  100.         3.  Copy of numbered National Evaluation Services Report
  101.             specified in Quality Assurance Article of this
  102.             Section.
  103.  
  104. 1.5 SYSTEM DESCRIPTION
  105.  
  106.     A.  Performance Requirements:
  107.         1.  Fire Rating:  Provide UL listed Class A/Class I fire
  108.             retardant treated wood products exhibiting maximum
  109.             flame spread of 25, when tested in accordance with
  110.             ASTM E 84, NFPA 255, or UL 723, and no evidence of
  111.             significant combustion when test is extended for and
  112.             additional 20 minutes.
  113.         2.  Corrosive Properties:  Carbon steel, galvanized
  114.             steel, aluminum, copper, and red brass in contact
  115.             with fire retardant treated wood products to exhibit
  116.             maximum corrosion rates of one (1) mil (0.025 mm) per
  117.             year when tested in accordance with MIL-L-19140.
  118.  
  119. 1.6 QUALITY ASSURANCE
  120.  
  121.     A.  Regulatory Requirements:  Fire retardant chemicals
  122.         registered for use as wood preservative by U. S.
  123.         Environmental Protection Agency.
  124.  
  125.     B.  Certifications:  Test results of fire performance,
  126.         strength, and corrosive properties of fire retardant
  127.         treated wood products issued in numbered National
  128.         Evaluation Services Report.
  129.  
  130. 1.7 DELIVERY, STORAGE, AND HANDLING
  131.  
  132.     A.  Storage and Protection:  Store fire retardant treated
  133.         wood products on site in accordance with manufacturer's
  134.         recommendations.
  135.  
  136. PART 2  PRODUCTS
  137.  
  138. 2.1 MANUFACTURERS
  139.  
  140.     A.  Acceptable Manufacturer:  Licensed producer of Hickson
  141.         Corporation DRICON Fire Retardant Treated Wood Products.
  142.         ASD.
  143. NOTE ** Delete one of the two paragraphs below; coordinate
  144.         with Division 1 requirements.
  145.  
  146.     B.  Requests for substitutions will be considered in
  147.         accordance with provisions of Section 01600.
  148.  
  149.     C.  Substitutions:  Not permitted.
  150.  
  151. 2.2 MATERIALS
  152.  
  153.     A.  Fire Retardant Treated Dimension Lumber:
  154.         1.  Acceptable Product:  DRICON Fire Retardant Treated
  155.             Wood.
  156. NOTE ** Use the following set of paragraphs to specify by
  157.         grading agency, commercial species group, and
  158.         grade.  Indicate grade and size classifications if
  159.         required; refer to grading agency publications.
  160.         Ensure that grades entered provide strength
  161.         required.
  162.         2.  Grading Agency:  ALSC.
  163.         3.  Grading Agency:  WWPA.
  164.         4.  Grading Agency:  SPIB.
  165.         5.  Grading Agency:  WCLB.
  166.         6.  Grading Agency:  _______.
  167.         7.  Studs:  ________ grade; ________ species group.
  168.         8.  Miscellaneous Framing:  ________ grade; ________
  169.             species group.
  170. NOTE ** Delete one of the following two paragraphs.
  171.         9.  Structural Framing:  ________ grade; ________ species
  172.             group.
  173.         10. Structural Framing:  Any species and grade which
  174.             meets or exceeds the following values:
  175.             a.  Fb (Extreme Fiber Stress in Bending):  ____
  176.                 pounds per square inch (____ Mpa).
  177.             b.  E (Modulus of Elasticity):  __________ pounds per
  178.                 square inch (____ Mpa).
  179. NOTE ** Use the following set of paragraphs to specify by
  180.         Stress Groups defined by NLGA (Canadian lumber).
  181.         Be sure that the stress groups entered provide the
  182.         required strength.
  183.         11. Grading agency:  NLGA.
  184.         12. Studs:  Stress Group ____.
  185.         13. Miscellaneous Framing:  Stress Group ____.
  186. NOTE ** Delete one of the following two paragaphs.
  187.         14. Structural Framing:  Stress Group ____.
  188.         15. Structural Framing:  Any species and grade which
  189.             meets or exceeds the following values:
  190.             a.  Fb (Extreme Fiber Stress in Bending):  ____
  191.                 pounds per square inch (____ Mpa).
  192.             b.  E (Modulus of Elasticity):  __________ pounds per
  193.                 square inch (____ Mpa).
  194.         16. Sizes:  Indicated on Drawings.
  195.  
  196.     B.  Fire Retardant Treated Plywood:
  197.         1.  Acceptable Product:  DRICON Fire Retardant Treated
  198.             Plywood.
  199.         2.  Plywood Grading Agency:  Certified by APA, TECO, or
  200.             PTL.
  201. NOTE ** Delete one of two paragraphs below; delete both
  202.         paragraphs if not required.
  203.         3.  Floor Sheathing:  ________ grade, ________ species;
  204.             panel size __ feet (___ m) by __ feet (___ m), ___
  205.             inch (__ mm) thickness.
  206.         4.  Floor Sheathing:  APA Rated Sheathing Structural
  207.             Grade __, Span Rating ____, Exposure Durability __,
  208.             sanded; panel size __ feet (___ m) by __ feet (___
  209.             m), ___ inch (__ mm) thickness.
  210. NOTE ** Delete one of two paragraphs below; delete both
  211.         paragraphs if not required.
  212.         5.  Floor Underlayment:  ________ grade, ________
  213.             species; panel size __ feet (___ m) by __ feet (___
  214.             m), ___ inch (__ mm) thickness.
  215.         6.  Floor Underlayment:  APA Rated Sheathing Structural
  216.             Grade __, Span Rating ____, Exposure Durability __,
  217.             sanded; panel size __ feet (___ m) by __ feet (___
  218.             m), ___ inch (__ mm) thickness.
  219. NOTE ** Delete one of two paragraphs below; delete both
  220.         paragraphs if not required.
  221.         7.  Wall Sheathing:  ________ grade, ________ species;
  222.             panel size __ feet (___ m) by __ feet (___ m), ___
  223.             inch (__ mm) thickness.
  224.         8.  Wall Sheathing:  APA Rated Sheathing Structural Grade
  225.             __, Span Rating ____, Exposure Durability __, sanded;
  226.             panel size __ feet (___ m) by __ feet (___ m), ___
  227.             inch (__ mm) thickness.
  228. NOTE ** Delete one of two paragraphs below; delete both
  229.         paragraphs if not required.
  230.         9.  Roof Sheathing:  ________ grade, ________ species;
  231.             panel size __ feet (___ m) by __ feet (___ m), ___
  232.             inch (__ mm) thickness.
  233.         10. Roof Sheathing:  APA Rated Sheathing Structural Grade
  234.             __, Span Rating ____, Exposure Durability __, sanded;
  235.             panel size __ feet (___ m) by __ feet (___ m), ___
  236.             inch (__ mm) thickness.
  237.         11. Telephone and Electrical Backboards:  ________ grade,
  238.             ________ species; panel size __ feet (___ m) by __
  239.             feet (___ m), ___ inch (__ mm) thickness.
  240.         12. Miscellaneous Plywood:  ________ grade, ________
  241.             species; thicknesses indicated on drawings.
  242.  
  243. 2.3 FABRICATION
  244.  
  245.     A.  Fire Retardant Chemicals:  Formulated free of halogens,
  246.         sulfates, and ammonium phosphate, and for fungal and
  247.         termite inhibitive properties; conforming to AWPA P17.
  248.  
  249.     B.  Fire Retardant Treated Dimension Lumber:  Kiln-dried to
  250.         maximum moisture content 19 percent after pressure
  251.         impregnation with fire retardant chemicals; conforming to
  252.         AWPA C20.
  253.  
  254.     C.  Fire Retardant Treated Plywood:  Kiln-dried to maximum
  255.         moisture content 15 percent after pressure impregnation
  256.         with fire retardant chemicals; conforming to AWPA C27.
  257.  
  258. 2.4 SOURCE QUALITY CONTROL
  259.  
  260.     A.  Tests, inspections:  Fire retardant chemicals UL listed;
  261.         follow-up inspections conducted by UL.
  262.  
  263.     B.  Verification of performance:  Factory-mark each piece of
  264.         fire retardant treated wood products with the following:
  265.         1.  UL imprint certifying Class A/Class I flame spread
  266.             rating.
  267.         2.  Imprint certifying Interior Type A product
  268.             classification.
  269.         3.  Imprint certifying kiln-drying after treatment
  270.             (KDAT).
  271.         4.  Imprint of number of National Evaluation Services
  272.             Report specified in Quality Assurance Article of this
  273.             section.
  274.  
  275. PART 3  EXECUTION
  276.  
  277. 3.1 INSTALLATION
  278.  
  279.     A.  Fire Retardant Treated Dimension Lumber:
  280. NOTE ** Verify Section Numbers and Titles in paragraph
  281.         below.
  282.         1.  Install in accordance with Section 06100 and Section
  283.             06200.
  284.         2.  Field-cut lumber for required lengths, drilled holes,
  285.             or joining cuts only; ripping or milling of lumber is
  286.             prohibited.
  287.         3.  Secure lumber with fasteners of galvanized steel or
  288.             other corrosion resistant material.
  289.  
  290.     B.  Fire Retardant Treated Plywood:
  291. NOTE ** Verify Section Numbers and Titles in paragraph
  292.         below.
  293.         1.  Install in accordance with Section 06100 and Section
  294.             06200.
  295.         2.  Comply with nailing schedules and panel spacings
  296.             specified in APA "Design and Construction Guide for
  297.             Residential and Commercial Uses", including use of
  298.             plyclips where required, unless otherwise indicated.
  299.         3.  Secure plywood panels with fasteners of galvanized
  300.             steel or other corrosion resistant material; use of
  301.             staples is prohibited.
  302.  
  303.                          END OF SECTION
  304.