home *** CD-ROM | disk | FTP | other *** search
/ Internet Standards / CD2.mdf / ccitt / 1992 / k / k21.asc < prev    next >
Text File  |  1993-06-28  |  14KB  |  557 lines

  1. Recommendation K.21 
  2.  
  3.  
  4.  
  5. RESISTIBILITY OF SUBSCRIBERS TERMINALS 
  6.  
  7. TO OVERVOLTAGES AND OVERCURRENTS
  8.  
  9.  
  10.  
  11.  
  12.  
  13. Introduction
  14.  
  15.  
  16.  
  17.     This Recommendation has been produced by CCITT Study Group V to meet the urgent require-
  18. ments of Administrations and manufacturers who are using or designing subscriber's equipment.  The 
  19. attention of the reader is drawn to the following subjects which CCITT is studying further:
  20.  
  21.  
  22.  
  23.     -     rise of earth potential
  24.  
  25.  
  26.  
  27.     -     electrical fast transients
  28.  
  29.  
  30.  
  31.     -     operational tests for barriers between mains ports and  telecommunication ports
  32.  
  33.  
  34.  
  35.     -    high frequency mains voltage surges
  36.  
  37.  
  38.  
  39.     -     short duration interruptions of mains voltages.
  40.  
  41.  
  42.  
  43.     When these studies have been completed, this Recommendation may be expanded.  
  44.  
  45.  
  46.  
  47. 1.    Purpose of the Recommendation
  48.  
  49.  
  50.  
  51.     When modern telecommunications equipment is connected to local subscribers' lines, the equip-
  52. ment may be damaged as a result of overvoltages or overcurrents which occur on these lines under 
  53. occasional conditions. The probability and magnitude of these conditions vary due to many factors, 
  54. e.g. geography, climate, construction methods, shielding effects.  Overvoltage or overcurrent surges 
  55. arising from electro-static discharges or transients which occur in mains voltages supplies may also 
  56. damage equipment or cause its misoperation. This Recommendation seeks to establish fundamental 
  57. testing methods which may be varied in detail to suit particular local circumstances and which help to 
  58. predict the likelihood of survival when the equipment is exposed to these overvoltages or overcur-
  59. rents.
  60.  
  61.  
  62.  
  63.     In its present form, the Recommendation describes tests that should be applied to equipment 
  64. which is metallically connected directly to balanced pairs.  Further studies relating to equipment con-
  65. nected to coaxial and optical fibre cables are being made.
  66.  
  67.  
  68.  
  69. ûûûûûûûûûûûûûûûûûûûû 
  70.  
  71.  
  72.  
  73. Note - In this document, the expression "Administration" is used for shortness to indicate both a telecom-
  74. munication Administration and a recognized private operating agency.
  75.  
  76.  
  77.  
  78.  
  79.  
  80.     The Recommendation assumes that line protectors are fitted externally to the equipment in exposed 
  81. areas.  Administrations individually will decide their policies for protection. The guidance of Recommenda-
  82. tion K.11 should be followed when making this judgement and should take account of the routing of lines 
  83. to the equipment in addition to its location.
  84.  
  85.  
  86.  
  87. 2.    Scope
  88.  
  89.  
  90.  
  91.     This Recommendation deals principally with desk-borne equipment.     RecommendationK.20 deals 
  92. with switching equipment powered by central-battery.  For the more complex subscriber equipment, 
  93. Administrations should use either K.20 or K.21 as appropriate.
  94.  
  95.  
  96.  
  97.     The Recommendation relates to type tests only.  Recognizing the difficulty in testing a complex item of 
  98. subscribers equipment, the Recommendation concentrates on a series of tests made principally at the line 
  99. and mains input terminals. The tests should be applied at any chosen stage during the normal use of the 
  100. equipment.
  101.  
  102.  
  103.  
  104.     As the equipment may be used in either an exposed or unexposed environment, tests are made with 
  105. and without line protectors fitted.
  106.  
  107.  
  108.  
  109.     The tests for lightning surges assume that electrical connection between the power system earth ter-
  110. minal and the telecommunications equipment earth can be effected.  A study of special test requirements 
  111. for situations where this is not possible is being made.
  112.  
  113.  
  114.  
  115.     The tests for power induction apply only to longitudinal effects and a further study is being made of test 
  116. requirements for transverse surges.
  117.  
  118.  
  119.  
  120.     Some aspects of rise of earth potential, such as may arise from a power line system fault, are not at 
  121. present covered but are being studied.
  122.  
  123.  
  124.  
  125.     Electrical fast transient requirements are not yet included and a study is being made of test require-
  126. ments for both the signal and mains power lines.
  127.  
  128.  
  129.  
  130.     The Recommendation deals primarily with reliability of equipment and although it may provide some 
  131. level of safety, it is not sufficient itself to fully protect the user on its own.  National standards for electrical 
  132. safety should be followed in each country where the equipment is used.  Furthermore, this Recommenda-
  133. tion is not intended to establish whether equipment could produce harmful effects to the network when 
  134. connected.  Interference from low frequency induced voltages or radio frequency interference to the oper-
  135. ation of the equipment is not included.
  136.  
  137.  
  138.  
  139. 3.       Overvoltage and overcurrent conditions
  140.  
  141.  
  142.  
  143.     Aspects of overvoltage or overcurrent covered by this Recommendation are:                                                                             
  144.  
  145.          -     surges due to direct or indirect lightning strokes on or near to               the line plant;
  146.  
  147.  
  148.  
  149.     -    short-term induction of 50/60 Hz voltages from adjacent power lines or railway systems, usually 
  150. when these lines or systems develop faults;
  151.  
  152.  
  153.  
  154.     -    direct contacts between telecommunications lines and power lines, usually of a low voltage 
  155. nature;
  156.  
  157.  
  158.  
  159.          -    electrostatic discharges generated by users touching the equipment or adjacent plant;
  160.  
  161.  
  162.  
  163.     -    transient surges on mains-voltage power supplies to the equipment.
  164.  
  165.        4.    Equipment boundary
  166.  
  167.  
  168.  
  169.     The variations in equipment make it necessary for each unit to be seen as a "black-box" having three 
  170. or more terminals, A, B, ..., etc. and Earth.  Some protective devices may have already been provided 
  171. within the equipment, e.g.,distributed on cards, or connected to internal terminals.  For the purposes of 
  172. these tests manufacturers are expected to define the boundaries of the "black-box"  and any protective 
  173. device which is thereby included must be considered as an immutable part of the equipment.  Where any 
  174. auxillary telecommunications lead is provided, e.g. to an extension, or as a signalling earth, these wires 
  175. should be seen to extend the number of terminals to be tested, e.g.  A, B, C, D, ..., etc. and Earth.
  176.  
  177.  
  178.  
  179. 5.    Test conditions
  180.  
  181.  
  182.  
  183.     The following general conditions apply to all the tests specified in   __7, 8 and 9 except where other-
  184. wise stated.
  185.  
  186.  
  187.  
  188. 5.1    All tests are type tests.
  189.  
  190.  
  191.  
  192. 5.2    The input terminals at which tests on the equipment are to be applied should be identified by the man-
  193. ufacturer and labelled A, B, C, D, ..., etc. and Earth.
  194.  
  195.  
  196.  
  197. 5.3    For the tests specified in _ 7 and _ 9 only, the equipment should be enclosed in a foil shroud over 
  198. areas likely to be contacted during use and the foil connected to the E terminal.
  199.  
  200.  
  201.  
  202. 5.4    The equipment should be tested in any operating state of significant duration.
  203.  
  204.  
  205.  
  206. 5.5    The equipment should pass the tests listed in __ 7 and 9 throughout the ranges of temperature and 
  207. humidity of its intended use.
  208.  
  209.  
  210.  
  211. 5.6    Some of the tests in Table 1 require the addition of agreed primary protection. It is current practice to pro-
  212. tect exposed subscribers' lines with some surge protectors such as gas-discharge tubes.  Recognizing that 
  213. some such device is likely to be needed in most cases to handle high surge currents, and that the operation 
  214. of these protectors exposes subscribers' equipment to other modified conditions, the characteristics of the 
  215. external protectors to be used should be agreed between the equipment supplier and the Administration.  
  216. Administrations applying the tests included in this Recommendation are free to select such protectors with 
  217. any characteristics within the range acceptable for these nominated devices when carrying out tests with 
  218. external protection fitted.
  219.  
  220.  
  221.  
  222.     Protectors having characteristics within the agreed range should be used where specified in Table 1. A 
  223. new set of protectors may be used after the completion of each test sequence. Alternatively, some Adminis-
  224. trations may choose to omit the external protectors but to modify the applied voltages and durations so that 
  225. the conditions applied to the equipment are the same as could reasonably be expected to occur under the 
  226. conditions of Table 1.
  227.  
  228.  
  229.  
  230. 5.7        In all cases where a maximum voltage is specified, tests should also be made at lower voltages if this is 
  231. necessary to confirm that the equipment will resist any voltage up to the maximum value specified.
  232.  
  233.  
  234.  
  235. 5.8    Each test should be applied the number of times indicated in the relative Table.  The time interval between 
  236. applications should be one minute and, in the case of pulse tests, the polarity should be reversed between 
  237. consecutive pulses.
  238.  
  239.  
  240.  
  241. 5.9    Power induction and power contact tests should be made at the frequencies of the ac mains or electric 
  242. railways used in the country of application.
  243.  
  244.  
  245.  
  246. 6.    Permitted malfunction or damage
  247.  
  248.  
  249.  
  250.     Two levels of malfunction or damage are recognized:
  251.  
  252.  
  253.  
  254.     Criterion A - Equipment shall withstand the test without damage or other disturbance (such as corruption 
  255. of software or misoperation of fault- protection facilities) and shall operate properly within the specified limits 
  256. after the test.  (It is not required to operate correctly while the test condition is present). If specifically permit-
  257. ted by the Administration, the test may cause the operation of fuses or other devices which have to be 
  258. replaced or reset before normal operation is restored.
  259.  
  260.  
  261.  
  262.     Criterion B - A fire hazard should not arise in the equipment as a result of the tests. Any damage or per-
  263. manent malfunction occuring should be confined to a small number of external line interface circuits.
  264.  
  265.  
  266.  
  267.     The conditions likely to give rise to criterion B are considered to be so rare that complete protection 
  268. against them is not economical.
  269.  
  270.  
  271.  
  272. 7.    Tests related to lightning surges, power induction and contacts
  273.  
  274.  
  275.  
  276.     The test circuits used for the three overvoltage or overcurrent conditions are as follows:
  277.  
  278.  
  279.  
  280.     Figure 1 - Lightning surges,
  281.  
  282.  
  283.  
  284.     Figure 2 - Power induction,
  285.  
  286.  
  287.  
  288.     Figure 3 - Power contacts.
  289.  
  290.  
  291.  
  292.     The equipment should be tested according to Table 1.
  293.  
  294.  
  295.  
  296.  
  297.  
  298.  
  299.  
  300.  
  301.  
  302.  
  303.  
  304.  
  305.  
  306.  
  307.  
  308.  
  309.  
  310.  
  311.  
  312.  
  313.  
  314.  
  315.  
  316.  
  317.  
  318.  
  319.  
  320.  
  321.  
  322.  
  323.  
  324.  
  325.  
  326.  
  327.  
  328.  
  329.  
  330.  
  331.  
  332.  
  333.  
  334.  
  335.  
  336.  
  337.  
  338.  
  339.  
  340.  
  341.  
  342.  
  343.  
  344.  
  345.  
  346.  
  347.  
  348.  
  349.  
  350.  
  351.  
  352.  
  353.  
  354.  
  355.  
  356.  
  357.  
  358.  
  359.  
  360.  
  361.  
  362.  
  363.  
  364.  
  365.  
  366.  
  367.  
  368.  
  369.  
  370.  
  371.  
  372.  
  373.  
  374.  
  375.  
  376.  
  377.  
  378.  
  379.  
  380.  
  381.  
  382.  
  383.  
  384.  
  385.  
  386.  
  387.  
  388.  
  389.  
  390.  
  391.  
  392.  
  393.  
  394.  
  395.  
  396.  
  397.  
  398.  
  399.  
  400.  
  401.  
  402.  
  403.  
  404.  
  405.  
  406.  
  407.  
  408.  
  409.  
  410.  
  411.  
  412.  
  413.  
  414.  
  415.  
  416.  
  417.  
  418.  
  419.  
  420.  
  421.  
  422.  
  423.  
  424.  
  425.  
  426.  
  427.  
  428.  
  429.  
  430.  
  431.  
  432.  
  433.  
  434.  
  435.  
  436.  
  437.  
  438.  
  439.  
  440.  
  441.  
  442.  
  443.  
  444.  
  445.  
  446. Note 1 - An earthed connection may prevent the establishment of normal operation conditions when the test 
  447. is made.  In these cases, alternative testing procedures should be followed to meet the requirements of this 
  448. test (e.g. a low voltage spark gap or other variation in the earth connection should be used).
  449.  
  450.  
  451.  
  452. Note 2 - Administrations may choose other values of Uc(max) to suit local circumstances, e.g. to avoid the 
  453. use of protectors or to align with the impulse spark-over voltage of protectors that are normally used.
  454.  
  455.  
  456.  
  457. Note 3 - Administrations may vary Uc(max) to meet their local requirements.
  458.  
  459.  
  460.  
  461. Note 4 - Administrations may specify lower values of Uac (max) and may vary the duration of the test to meet 
  462. their local requirements (e.g. local mains voltages).  
  463.  
  464. Note 5 - Voltages and durations should be in accordance with CCITT Directives or such other limits as Admin-
  465. istrations may set.
  466.  
  467.  
  468.  
  469. Note 6 - Fuses, fuse cables, etc, may be left in circuit during these tests. The current conducted by wiring 
  470. shall not constitute a fire hazard within the premises where the equipment is located.
  471.  
  472.  
  473.  
  474. 8.    Tests related to electrostatic discharges
  475.  
  476.  
  477.  
  478.     The requirements of IEC Publication 801-2 should be followed. The equipment should meet criterion A of 
  479. this Recommendation when tested to both severity levels 2 and 4 of IEC Publication 801-2 .These two sever-
  480. ity levels have been chosen because at severity level 2, the rise time is much faster than that at severity level 
  481. 4.  This fast rise time may cause coupling into sensitive circuits to take place and will require an assessment 
  482. for misoperation due to software corruption rather than just for energy dissipation.
  483.  
  484.  
  485.  
  486.     However, when deemed appropriate by an Administration, alternative severity levels of testing may be 
  487. used.  In addition, an Administration may choose to relax the conditions of criterion A to a limited extent.
  488.  
  489.  
  490.  
  491. 9.    Tests related to mains voltage powered equipment
  492.  
  493.  
  494.  
  495.     The following tests are made on mains-powered equipment to ensure that the equipment can adequately 
  496. resist high voltage surges which may arise on power conductors from lightning or other causes such as load 
  497. switching.
  498.  
  499.  
  500.  
  501.     The equipment under test should be tested with normal operating power applied and with the telecommu-
  502. nication line parts terminated in such a manner as to simulate the conditions in each state of operation of sig-
  503. nificant duration.
  504.  
  505.  
  506.  
  507.     Equipment not complying with a) below should meet Criterion A of this Recommendation when tested with 
  508. surge tests applied between phase, neutral and protective earth terminals of the equipment in accordance 
  509. with b) below.
  510.  
  511.  
  512.  
  513.     a)      Insulation coordination
  514.  
  515.  
  516.  
  517.     IEC Publication 664 (Insulation coordination within low-voltage systems, including clearances and creep-
  518. age distances for equipment) describes over-voltage categories for mains-powered equipment including tele-
  519. communications equipment, in respect of over-voltages arising in the supply network. Most subscribers 
  520. equipment is expected to be installed in over-voltage category 11 in which the maximum surge voltage arriv-
  521. ing at its mains terminals is 2.5 kV peak. Given this and certain other assumptions about atmospheric pollu-
  522. tion (e.g. dust)  and the quality of insulation, IEC 664 gives guidance to IEC standards committees on 
  523. coordinated creepage distances and clearances that can be expected to give adequate performance during 
  524. the lifetime of the equipment.
  525.  
  526.  
  527.  
  528.  
  529.  
  530.  
  531.  
  532.  
  533.  
  534.  
  535.  
  536.  
  537.  
  538.  
  539.  
  540.  
  541.  
  542.  
  543.  
  544.  
  545.  
  546.  
  547.  
  548.  
  549.  
  550.  
  551.  
  552.  
  553.  
  554.  
  555.  
  556.  
  557.