-------------------------------------------------------------------------- |CMP|FPLP|CL3P|CL2P|CMR|FPLR|CL3R|CL2R|CM|FPL|CL3|PLTC|CL2|CMX|CL3X|CL2X| CMP X FPLP X X CL3P X X X CL2P X X X X CMR X X X X X FPLR X X X X X X CL3R X X X X X X X CL2R X X X X X X X X CM X X X X X X X X X FPL X X X X X X X X X X CL3 X X X X X X X X X X X PLTC X X X X X X X X X X X X CL2 X X X X X X X X X X X X X CMX X X X X X X X X X X X X X X CL3X X X X X X X X X X X X X X X X CL2X X X X X X X X X X X X X X X X X BASED ON 1987 NATIONAL ELECTRICAL CODE SUBSTITUTION CHART. 1. PLENUM CABLE must pass the modified Steiner Tunnel Tes-UL910. 2. RISER CABLE must pass UL1666 flame test. 3. GENERAL BLDG WIRING must pass UL1581 vertical tray flame test. 4. RESTRICTED USE must pass UL1581 VW-1 test. This table courtesy of GEPCO International. via AV-Sync (404) 320-6202